Standards and scope

Standards and application range

Standards sets, voltage levels, bus schemes and plant types of SubstationLayout. A project takes one standards set.

3D models of substations across both standards sets: 33 kV to 765/400 kV, and 69 kV to 345/230 kV
Application range

Substation types and arrangements per standards set

IEC, CEA and CBIP

  • Pooling substations for wind, solar, hybrid, thermal and other plants
  • HV: 33 kV, 66 kV, 132 kV, 220 kV and 400 kV, and 765 kV for switching. MV: 11 kV and 33 kV
  • Switching (HV/HV) substations from 132/33 kV to 765/400 kV, with auto-transformers at 220 kV and 400 kV and banks of single-phase units at 765 kV
  • Generator bays with generator transformers, station transformers and an 11 kV station board for synchronous plants
  • Double main bus, one-and-a-half breaker, single sectionalised bus and single bus schemes
  • Air-insulated (AIS) or gas-insulated (GIS) switchgear per HV yard, GIS in an indoor hall with SF6/air bushings
  • MV indoor switchgear or outdoor AIS
  • Line bays, transformer bays, bus coupler, bus reactor, switchable line reactors at 765 kV and future bays
  • Static var generators and harmonic filters on the MV bus
  • Soil resistivity from Wenner measurements
  • 50 Hz or 60 Hz. A1 sheets, metric units

ANSI, IEEE and NESC

  • Pooling substations for wind, solar, hybrid and other inverter-based plants
  • HV: 69 kV, 115 kV, 138 kV, 161 kV, 230 kV and 345 kV. Collector bus: 34.5 kV
  • Switching (HV/HV) substations: 345/230 kV, 345/138 kV, 345/115 kV, 230/138 kV, 230/115 kV, 230/69 kV, 161/69 kV, 138/69 kV and 115/69 kV
  • Autotransformers at 230 kV and 345 kV with a 13.8 kV tertiary
  • Ring bus with 3 or 4 circuit positions, one-and-a-half breaker, double main bus, single sectionalised bus and single bus schemes
  • AIS or GIS switchgear per HV yard. Ring bus on AIS
  • 34.5 kV indoor switchgear or outdoor AIS
  • Line bays, transformer bays, bus coupler, bus reactor and future bays
  • STATCOM on the 34.5 kV bus, sized at 0.95 power factor at rated output (FERC Order No. 827), a value for the reactive power study
  • IEEE 693 qualification level as an input, printed on the yard notes and the BOM
  • Soil resistivity from Wenner measurements
  • 60 Hz. ANSI D sheets, feet and inches, AWG and kcmil
Voltage levels

Voltage levels and ratings per standards set

Rated values at the level. The bus scheme is the default on a new project, and you select another on the HV switchyard page. Plant capacity and transformer sizes are the design's values, not a standard's.

ANSI, IEEE and NESC

Nominal HVRated maximumBILDesign fault levelDefault bus schemePlant capacityTransformer sizes
69 kV72.5 kV350 kV31.5 kARing bus20–60 MW20–50 MVA
115 kV123 kV550 kV40 kARing bus50–150 MW40–100 MVA
138 kV145 kV650 kV40 kARing bus50–200 MW40–120 MVA
161 kV170 kV750 kV40 kARing bus80–250 MW60–150 MVA
230 kV245 kV900 kV50 kAOne-and-a-half breaker150–290 MW100–168 MVA
345 kV362 kV1300 kV50 kAOne-and-a-half breaker300–1000 MW315 MVA, split LV

Rated maximum voltage, BIL and fault levels per IEEE C37.04-2018 Tables 6, 12 and 16.

IEC, CEA and CBIP

Nominal HVRated maximum (Um)BILDesign fault levelDefault bus schemePlant capacityTransformer sizes
33 kV36 kV170 kV25 kASingle sectionalised bus5–25 MW5–20 MVA
66 kV72.5 kV325 kV31.5 kASingle sectionalised bus20–50 MW20–50 MVA
132 kV145 kV650 kV40 kADouble main bus50–150 MW31.5–100 MVA
220 kV245 kV1050 kV50 kADouble main bus150–300 MW100–250 MVA
400 kV420 kV1425 kV63 kAOne-and-a-half breaker500–1000 MW160–315 MVA, split LV
765 kV800 kV2100 kV50 kAOne-and-a-half breakerSwitching1500 MVA
Standards

Standards and editions applied

A year names the edition the design applies, which may precede the current edition. An entry with no year names the standard without an edition. Transformer sizes, yard geometry and several size lists are the design's values. The compliance checklist states the criterion, the design value and a status per item, and you answer the manual items.

ANSI, IEEE and NESC

StandardApplied to
IEEE C37.010-2016Short-circuit duty, E/X method
IEEE C37.04-2018Rated maximum voltage, BIL and breaker ratings
IEEE C37.13-2015Low-voltage power circuit breaker frames
IEEE 80-2013Grounding method
IEEE 998-2012Rolling sphere, HV yard
IEC 62305-3LPL I sphere, building and MV areas
IEEE 485-2020Battery sizing
IEEE 946-2020Charger sizing
NESC, ANSI C2-2007Rules 110A and 124A: fence and live parts
RUS Bulletin 1724E-300Clearances and phase spacing (Tables 4-7 and 4-8), from ANSI C37.32-1996 and NEMA SG-6-1995
IEEE C37.2-1996Device numbers, as RUS Bulletin 1724E-300 Appendix F reprints them
IEEE C57.13-1993Instrument transformers, as RUS Bulletin 1724E-300 §5.10 reprints it
IEEE C57.12.10-1988Transformer impedance at 69 kV to 161 kV, as RUS Bulletin 1724E-300 Table 5-11 reprints it
FERC Order No. 827Reactive power at 0.95 power factor

IEC, CEA and CBIP

StandardApplied to
IEC 60909-0:2016Short-circuit currents
IEEE 80-2013Earthing method
IEEE 998-2012Rolling sphere, HV yard
IEC 62305-3LPL I sphere, building and MV areas
IEEE 485-2020Battery sizing
IEEE 946-2020Charger sizing
IEC 60947-2ACB and MCCB ratings
ISO 8528-5DG set motor-start dip, class G3
IEC 61869Instrument transformers
IEC 62271-203:2022GIS checklist items
IEC 60071-1:2019GIS checklist items
IEC 81346Designations on the SLD
IEC 60617Symbols on the SLD
CEA, CBIPClearances and checklist items