Earthing and grounding

Earthing and grounding design per IEEE 80-2013

Earth-mat and ground grid design for AIS and GIS substations in uniform soil: tolerable voltages, conductor size, grid resistance, mesh and step voltages. The documents are a layout, typical details and a report.

The earth mat with the mesh voltage of 578 V and the tolerable touch voltage of 685 V, per IEEE 80-2013
Capabilities

Calculations and documents

The grid is checked against the tolerable touch and step voltages of IEEE 80-2013. The results go to the layout, the report and the bill of materials.

Tolerable voltages and sizing
  • Surface derating factor per IEEE 80 §7.4 Eq. 27
  • Tolerable touch and step voltages per IEEE 80 §8.3: Eq. 29 and 32 (50 kg) or Eq. 30 and 33 (70 kg)
  • Conductor size per IEEE 80 §11.3.1 Eq. 37
  • Decrement factor and grid current per IEEE 80 §15.10 Eq. 79 and §15.1 Eq. 63–64
Grid results
  • Grid resistance per IEEE 80 §14.2 Eq. 52
  • Ground potential rise per IEEE 80 §16
  • Mesh voltage per IEEE 80 §16.5.1 Eq. 80–91, and step voltage per §16.5.2 Eq. 92–94
  • Mesh spacing selected by the design
  • Electrodes at the perimeter, surge arresters, instrument transformers, neutral points, lightning masts and shield-wire towers
Inputs
  • Soil resistivity entered or from Wenner measurements, with a season factor
  • Surface layer resistivity and thickness
  • Fault current and durations, current split factor and X/R
  • Burial depth, ambient temperature and electrode size
Documents
  • Layout in DXF and PDF
  • Typical details in DXF and PDF
  • Calculation report in PDF: inputs, calculation trail, results and quantities
  • Quantities in the bill of materials
Standards sets

Materials and criteria per standards set

The IEEE 80-2013 method applies on both sets. The materials, sizes, body weight and words follow the standards set of the project.

ItemIEC, CEA and CBIPANSI, IEEE and NESC
Words on the documentsEarthing, earth matGrounding, ground grid
Verdict50 kg body, 70 kg for information70 kg body, 50 kg for information
ConductorMild steel rod, with a corrosion allowanceAnnealed soft-drawn copper, 4/0 AWG to 1000 kcmil
Electrodes40 mm × 3 m mild steel rods3/4 in × 10 ft copper-clad steel rods
Burial depth, new project0.6 m18 in
Connections and typical detailsWelded joints, riser, rod electrode and electrode pitExothermic connections, riser, rod electrode and test well
SheetsA1, metricANSI D, feet and inches, from 1″ = 20′
Sample project

Results, 220/33 kV pooling substation

The mesh and step voltages are below their tolerable limits for a 50 kg body. Sample design per IEC, CEA and CBIP.

Mesh voltage (Em)IEEE 80 §16.5.1 Eq. 80
578 V
Tolerable touch voltage (50 kg)685 V
Step voltage (Es)IEEE 80 §16.5.2 Eq. 92
1451 V
Tolerable step voltage (50 kg)2246 V
Design soil resistivity (ρ)
150 Ω·m
Grid size
155.0 m × 133.4 m
Conductors
40 × 35, mesh spacing 3.97 m
Electrodes
144, 40 mm × 3 m
Grid current (IG)
31.85 kA
Grid resistance (Rg)
0.476 Ω
Ground potential rise (GPR)
15.15 kV
Calculation trail

Equation, input values, result and clause per step

The calculation trail shows how the design reaches its results, in the order of the IEEE 80 design procedure.

  1. 1Soil resistivityIEEE 80 §13.4.2 (uniform soil)
    ρ0 100 Ω·m (entered), season factor 1.5ρ = 150 Ω·m
  2. 2Surface deratingIEEE 80 §7.4 Eq. 27
    ρs 3000 Ω·m, hs 0.10 mCs = 0.705
  3. 3Tolerable touch and step voltages (50 kg)IEEE 80 §8.3 Eq. 32, Eq. 29
    ts 0.50 sEtouch = 684.6 V, Estep = 2246.3 V
  4. 4Conductor sizeIEEE 80 §11.3.1 Eq. 37
    Steel 1020, I 50 kA (rating), 20.24 kA calculated, tc 1.00 s, Tm 500 °C, Ta 50 °C (ambient)A = 608.9 mm² → Ø 40 mm MS rod (+6 mm corrosion)
  5. 5Grid currentIEEE 80 §15.10 Eq. 79, §15.1 Eq. 63–64
    X/R for Df 20, tf 0.50 s, Sf 0.6, 3I0 50 kADf = 1.062, IG = 31.85 kA
  6. 6Grid resistance (Sverak)IEEE 80 §14.2 Eq. 52
    A 20 677 m², LT 11 193 m, h 0.60 mRg = 0.476 Ω
  7. 7Ground potential riseIEEE 80 §16, design procedure, step 6
    IG 31.85 kA, Rg 0.476 ΩGPR = 15.15 kV The rise of earth potential is above the tolerable touch voltage, so the mesh and step check follows.
  8. 8Mesh voltageIEEE 80 §16.5.1 Eq. 80–91
    n 37.37, Km 0.224, Ki 6.174, LM 11 438 mEm = 577.6 V ≤ 684.6 V
  9. 9Step voltageIEEE 80 §16.5.2 Eq. 92–94
    Ks 0.415, Ki 6.174, LS 8438 mEs = 1450.6 V ≤ 2246.3 V
  10. 10Spacing searchDesign rule
    start 10 m, step 0.5 m, minimum 3 mtrial S = 4.00 m → 40 × 35 conductors, D = 3.97 m, 144 electrodes
Drawings

Earth-mat layout and typical details

Documents of a sample project, generated by SubstationLayout and marked as samples. Not for construction.

The sample earth-mat layout
Earth-mat layoutSSL-E-EAR-001 · Rev 0 · 1 page · PDF · 53 KB
Download
The sample earthing typical details
Earthing typical detailsSSL-E-EAR-002 · Rev 0 · 1 page · PDF · 30 KB
Download
Document

Earthing calculation report

The report states the inputs and their sources, the calculation trail, the results against their limits and the quantities.

  • Page 1 of the sample earthing calculation report
  • Page 2 of the sample earthing calculation report
  • Page 3 of the sample earthing calculation report
Earthing calculation reportSSL-C-EAR-001 · Rev 0 · 4 pages · PDF · 84 KB
Download