| Symbol | Meaning | Unit | Topic |
|---|---|---|---|
| symmetrical earth fault current | kA | Grid current | |
| Wenner spacing | m | Two-layer soil | |
| minimum cross-section of the conductor | mm² | Conductor sizing | |
| area of the mat | m² | Grid resistance and GPR | |
| height of the protected level | m | Masts and shield wires | |
| thermal coefficient of resistivity at 20 °C | 1/°C | Conductor sizing | |
| plan point of the sphere's centre | Masts and shield wires | ||
| voltage factor, $c_{\max}$ or $c_{\min}$ | Short-circuit currents by IEC 60909-0 | ||
| surface layer derating factor | Step voltage | ||
| surface layer derating factor ([[surface-layer]]) | Tolerable body current | ||
| C_s$, $\rho_s$, $t_s | derating factor and resistivity of the surface layer, shock time ([[surface-layer]]) | Mesh voltage and touch voltage | |
| diameter of the mat's conductor | m | Mesh voltage and touch voltage | |
| plan distance of the element from $c$ | m | Masts and shield wires | |
| spacing between parallel conductors | m | Mesh voltage and touch voltage | |
| decrement factor | Grid current | ||
| the base of the natural logarithm | Direct stroke shielding by the rolling sphere | ||
| driving voltage, the maximum system voltage line to neutral | kV | Short-circuit duty by IEEE C37.010 | |
| lowest height the sphere reaches at $P$ | m | Masts and shield wires | |
| corona inception gradient | kV/m | Direct stroke shielding by the rolling sphere | |
| mesh voltage | V | Mesh voltage and touch voltage | |
| tolerable step voltage | V | Step voltage | |
| tolerable step voltage for a person of 50 kg | V | Step voltage | |
| E_{\mathrm{touch50}}$, $E_{\mathrm{step50}} | tolerable touch and step voltage for a person of 50 kg | V | Tolerable body current |
| step voltage of the mat | V | Step voltage | |
| system frequency | Hz | Short-circuit duty by IEEE C37.010 | |
| burial depth of the mat | m | Grid resistance and GPR | |
| depth of the upper layer | m | Two-layer soil | |
| height of the protected conductor above the ground | m | Direct stroke shielding by the rolling sphere | |
| height of the site above the {{clear.altitude_220.alt_std}} the clearances hold for, 0 below it | m | Electrical clearances | |
| lowest height of the sphere's centre over $c$ | m | Masts and shield wires | |
| depth of the surface layer | m | Step voltage | |
| rms fault current | kA | Conductor sizing | |
| initial symmetrical short-circuit current | kA | Peak current and thermal equivalent current | |
| initial symmetrical current of a line-to-earth fault | kA | Short-circuit currents by IEC 60909-0 | |
| single-phase fault level of the grid at the remote bus | kA | Symmetrical components | |
| initial symmetrical current of a line-to-line fault | kA | Short-circuit currents by IEC 60909-0 | |
| current in phase L2 of a line-to-line-to-earth fault (phase L3 with $\underline{a}^2$) | kA | Short-circuit currents by IEC 60909-0 | |
| initial symmetrical current of a three-phase fault | kA | Short-circuit currents by IEC 60909-0 | |
| current to earth of a line-to-line-to-earth fault | kA | Short-circuit currents by IEC 60909-0 | |
| three-phase fault level of the grid at the remote bus | kA | Short-circuit currents by IEC 60909-0 | |
| zero-sequence current | A | Symmetrical components | |
| I_3$, $I_1 | symmetrical three-phase and line-to-ground currents | kA | Short-circuit duty by IEEE C37.010 |
| body current that a person of 50 kg tolerates | A | Step voltage | |
| I_{B,50}$, $I_{B,70} | body current a person of 50 kg or 70 kg tolerates | A | Tolerable body current |
| maximum grid current | kA | Grid current | |
| maximum grid current ([[grid-current]]) | A | Grid resistance and GPR | |
| rated closing and latching current, peak | kA | Circuit breakers and isolators | |
| rated current of the neutral grounding resistor | A | Earthing of the neutral | |
| thermal equivalent short-circuit current | kA | Peak current and thermal equivalent current | |
| peak short-circuit current | kA | Peak current and thermal equivalent current | |
| allowable stroke current | kA | Direct stroke shielding by the rolling sphere | |
| rated short-circuit current of the breaker, r.m.s. symmetrical | kA | Circuit breakers and isolators | |
| striking distance factor | Direct stroke shielding by the rolling sphere | ||
| reflection factor of the interface | Two-layer soil | ||
| ratio of the transformer's zero-sequence to positive-sequence impedance | Short-circuit currents by IEC 60909-0 | ||
| $1/\alpha_0$, the inverse of the coefficient at 0 °C | °C | Conductor sizing | |
| atmospheric correction factor for altitude | Electrical clearances | ||
| peak factor | Peak current and thermal equivalent current | ||
| peak factor by [[#eq-kappa]] from the R/X ratio at the fault location | Peak current and thermal equivalent current | ||
| correction for the burial depth, with $h_0$ = 1 m | Mesh voltage and touch voltage | ||
| irregularity factor | Mesh voltage and touch voltage | ||
| correction for the inner meshes, 1 with electrodes on the perimeter | Mesh voltage and touch voltage | ||
| spacing factor for mesh voltage | Mesh voltage and touch voltage | ||
| spacing factor for step voltage | Step voltage | ||
| correction factor of a power station unit with an on-load tap changer | Per-unit quantities | ||
| correction factor of a network transformer | Short-circuit currents by IEC 60909-0 | ||
| l$, $n | length of the line, number of parallel circuits | km, | Short-circuit currents by IEC 60909-0 |
| total length of horizontal conductor | m | Step voltage | |
| L_C$, $L_R | total length of horizontal conductor and of electrodes | m | Mesh voltage and touch voltage |
| effective length for mesh voltage | m | Mesh voltage and touch voltage | |
| perimeter of the mat | m | Mesh voltage and touch voltage | |
| length of one electrode | m | Mesh voltage and touch voltage | |
| total length of electrodes | m | Step voltage | |
| effective length of conductor and electrodes for step voltage | m | Step voltage | |
| total buried length, conductor and electrodes | m | Grid resistance and GPR | |
| L_x$, $L_y | length and width of the mat | m | Mesh voltage and touch voltage |
| exponent of the correction, which the design takes as 1 | Electrical clearances | ||
| factor for the heat effect of the DC component | Peak current and thermal equivalent current | ||
| basic lightning impulse insulation level of the protected level | kV | Direct stroke shielding by the rolling sphere | |
| rise of earth potential of the mat | V | Grid resistance and GPR | |
| thermal capacity per unit volume | J/(cm³·°C) | Conductor sizing | |
| duty factor on the symmetrical current | Short-circuit duty by IEEE C37.010 | ||
| geometry factor of the mat | Mesh voltage and touch voltage | ||
| order of the reflection | Two-layer soil | ||
| factor for the heat effect of the AC component, {{sc.peak_220.n}} far from a generator | Peak current and thermal equivalent current | ||
| n_a$, $n_b | factors of the geometry factor for a rectangular mat | Mesh voltage and touch voltage | |
| angular frequency, $2\pi f$ | rad/s | Grid current | |
| protected point, in plan | Masts and shield wires | ||
| plant capacity | MW | Reactive power equipment | |
| the ratio of a circle's circumference to its diameter | Soil resistivity and Wenner readings | ||
| Q_{\mathrm{SVG}}$, $Q_{\mathrm{STATCOM}} | total rating of the reactive power device, plus and minus | Mvar | Reactive power equipment |
| radius of the protected conductor | m | Direct stroke shielding by the rolling sphere | |
| resistance the earth tester reads | Ω | Soil resistivity and Wenner readings | |
| ratio of the resistance to the reactance of the positive-sequence impedance at the fault location | Peak current and thermal equivalent current | ||
| R_1$, $X_1 | positive-sequence resistance and reactance of a line circuit | Ω/km | Short-circuit currents by IEC 60909-0 |
| resistance of the body | Ω | Step voltage | |
| corona radius | m | Direct stroke shielding by the rolling sphere | |
| contact resistance of one foot on the surface layer | Ω | Step voltage | |
| grid resistance | Ω | Grid resistance and GPR | |
| resistivity of the soil | Ω·m | Grid resistance and GPR | |
| apparent resistivity of the soil | Ω·m | Soil resistivity and Wenner readings | |
| resistivity of the soil below the surface layer | Ω·m | Step voltage | |
| resistivity of the soil below the layer | Ω·m | Surface layer and Cs | |
| \rho_1$, $\rho_2 | resistivity of the upper and the lower layer | Ω·m | Two-layer soil |
| apparent resistivity at spacing $a$ | Ω·m | Two-layer soil | |
| resistivity of the conductor at 20 °C | µΩ·cm | Conductor sizing | |
| resistivity of the surface layer | Ω·m | Step voltage | |
| resistance of the neutral grounding resistor | Ω | Earthing of the neutral | |
| resistance of the neutral earthing resistor | Ω | Symmetrical components | |
| distance between successive electrodes | m | Soil resistivity and Wenner readings | |
| radius of the rolling sphere of the protected level | m | Masts and shield wires | |
| striking distance, the radius of the rolling sphere | m | Direct stroke shielding by the rolling sphere | |
| rated asymmetrical capability of the breaker per unit of its rated short-circuit current, at $t$ | Short-circuit duty by IEEE C37.010 | ||
| split factor | Grid current | ||
| contact parting time | ms | Short-circuit duty by IEEE C37.010 | |
| ratio of the MV to the HV nominal voltage | Earthing of the neutral | ||
| ambient temperature | °C | Conductor sizing | |
| DC time constant of the fault current, which IEEE 80-2013 writes $T_a$ | s | Grid current | |
| DC time constant of the fault | ms | Short-circuit duty by IEEE C37.010 | |
| duration of the current | s | Conductor sizing | |
| duration of the fault | s | Grid current | |
| duration of the short-circuit current | s | Peak current and thermal equivalent current | |
| maximum allowable temperature | °C | Conductor sizing | |
| rated ratio of the generator transformer, HV over LV | Per-unit quantities | ||
| duration of the shock current | s | Step voltage | |
| rated short-circuit voltage of the transformer | % | Short-circuit currents by IEC 60909-0 | |
| nominal voltage of the MV system | kV | Earthing of the neutral | |
| U_n$, $U_{nQ} | nominal voltage of the faulted bus, of the grid bus | kV | Short-circuit currents by IEC 60909-0 |
| rotation operator, $e^{j2\pi/3}$ | Short-circuit currents by IEC 60909-0 | ||
| nominal voltage of the HV bus | kV | Per-unit quantities | |
| U_r$, $S_r | rated voltage and rated apparent power of the equipment | kV, MVA | Per-unit quantities |
| U_{rG}$, $S_{rG} | rated voltage and rated apparent power of the generator | kV, MVA | Per-unit quantities |
| U_{rT}$, $S_{rT} | rated voltage on the HV side, rated apparent power | kV, MVA | Short-circuit currents by IEC 60909-0 |
| U_{rT}$, $S_{rT} | rated voltage of the transformer on the side considered, rated apparent power | kV, MVA | Per-unit quantities |
| U_{rTHV}$, $U_{rTLV} | rated voltages of the generator transformer, HV and LV side | kV | Per-unit quantities |
| phase angle of the generator at its rated power factor | Per-unit quantities | ||
| subtransient reactance of the generator, per unit of its rating | Per-unit quantities | ||
| ratio of reactance to resistance of the fault path | Grid current | ||
| X_1$, $R_1$, $X_0$, $R_0 | positive- and zero-sequence reactance and resistance at the fault, from the separate reductions | Ω | Short-circuit duty by IEEE C37.010 |
| relative reactance of the transformer, $X_T$ per unit of $U_{rT}^2/S_{rT}$ | Short-circuit currents by IEC 60909-0 | ||
| relative reactance of the transformer | Per-unit quantities | ||
| height of a wire, tower or mast | m | Masts and shield wires | |
| zero-sequence impedance of a MV section | Ω | Earthing of the neutral | |
| Z_1$, $Z_2$, $Z_0 | positive-, negative- and zero-sequence impedance at the fault location | Ω | Short-circuit currents by IEC 60909-0 |
| base impedance, $U_r^2/S_r$ | Ω | Per-unit quantities | |
| impedance of the generator | Ω | Per-unit quantities | |
| Z_Q$, $R_Q$, $X_Q | impedance, resistance and reactance of the network feeder | Ω | Short-circuit currents by IEC 60909-0 |
| Z_{Q1}$, $Z_{Q0} | positive- and zero-sequence impedance of the grid feeder | Ω | Symmetrical components |
| surge impedance of the conductor under corona | Ω | Direct stroke shielding by the rolling sphere | |
| impedance of the power station unit, referred to the HV bus | Ω | Per-unit quantities | |
| Z_T$, $X_T | impedance and reactance of the transformer | Ω | Per-unit quantities |
| zero-sequence impedance of the ICT, seen from the HV side | Ω | Earthing of the neutral | |
| impedance of the generator transformer, referred to its HV side | Ω | Per-unit quantities |