Symbols

SymbolMeaningUnitTopic
symmetrical earth fault currentkAGrid current
Wenner spacingmTwo-layer soil
minimum cross-section of the conductormm²Conductor sizing
area of the matm²Grid resistance and GPR
height of the protected levelmMasts and shield wires
thermal coefficient of resistivity at 20 °C1/°CConductor sizing
plan point of the sphere's centreMasts and shield wires
voltage factor, $c_{\max}$ or $c_{\min}$Short-circuit currents by IEC 60909-0
surface layer derating factorStep voltage
surface layer derating factor ([[surface-layer]])Tolerable body current
C_s$, $\rho_s$, $t_sderating factor and resistivity of the surface layer, shock time ([[surface-layer]])Mesh voltage and touch voltage
diameter of the mat's conductormMesh voltage and touch voltage
plan distance of the element from $c$mMasts and shield wires
spacing between parallel conductorsmMesh voltage and touch voltage
decrement factorGrid current
the base of the natural logarithmDirect stroke shielding by the rolling sphere
driving voltage, the maximum system voltage line to neutralkVShort-circuit duty by IEEE C37.010
lowest height the sphere reaches at $P$mMasts and shield wires
corona inception gradientkV/mDirect stroke shielding by the rolling sphere
mesh voltageVMesh voltage and touch voltage
tolerable step voltageVStep voltage
tolerable step voltage for a person of 50 kgVStep voltage
E_{\mathrm{touch50}}$, $E_{\mathrm{step50}}tolerable touch and step voltage for a person of 50 kgVTolerable body current
step voltage of the matVStep voltage
system frequencyHzShort-circuit duty by IEEE C37.010
burial depth of the matmGrid resistance and GPR
depth of the upper layermTwo-layer soil
height of the protected conductor above the groundmDirect stroke shielding by the rolling sphere
height of the site above the {{clear.altitude_220.alt_std}} the clearances hold for, 0 below itmElectrical clearances
lowest height of the sphere's centre over $c$mMasts and shield wires
depth of the surface layermStep voltage
rms fault currentkAConductor sizing
initial symmetrical short-circuit currentkAPeak current and thermal equivalent current
initial symmetrical current of a line-to-earth faultkAShort-circuit currents by IEC 60909-0
single-phase fault level of the grid at the remote buskASymmetrical components
initial symmetrical current of a line-to-line faultkAShort-circuit currents by IEC 60909-0
current in phase L2 of a line-to-line-to-earth fault (phase L3 with $\underline{a}^2$)kAShort-circuit currents by IEC 60909-0
initial symmetrical current of a three-phase faultkAShort-circuit currents by IEC 60909-0
current to earth of a line-to-line-to-earth faultkAShort-circuit currents by IEC 60909-0
three-phase fault level of the grid at the remote buskAShort-circuit currents by IEC 60909-0
zero-sequence currentASymmetrical components
I_3$, $I_1symmetrical three-phase and line-to-ground currentskAShort-circuit duty by IEEE C37.010
body current that a person of 50 kg toleratesAStep voltage
I_{B,50}$, $I_{B,70}body current a person of 50 kg or 70 kg toleratesATolerable body current
maximum grid currentkAGrid current
maximum grid current ([[grid-current]])AGrid resistance and GPR
rated closing and latching current, peakkACircuit breakers and isolators
rated current of the neutral grounding resistorAEarthing of the neutral
thermal equivalent short-circuit currentkAPeak current and thermal equivalent current
peak short-circuit currentkAPeak current and thermal equivalent current
allowable stroke currentkADirect stroke shielding by the rolling sphere
rated short-circuit current of the breaker, r.m.s. symmetricalkACircuit breakers and isolators
striking distance factorDirect stroke shielding by the rolling sphere
reflection factor of the interfaceTwo-layer soil
ratio of the transformer's zero-sequence to positive-sequence impedanceShort-circuit currents by IEC 60909-0
$1/\alpha_0$, the inverse of the coefficient at 0 °C°CConductor sizing
atmospheric correction factor for altitudeElectrical clearances
peak factorPeak current and thermal equivalent current
peak factor by [[#eq-kappa]] from the R/X ratio at the fault locationPeak current and thermal equivalent current
correction for the burial depth, with $h_0$ = 1 mMesh voltage and touch voltage
irregularity factorMesh voltage and touch voltage
correction for the inner meshes, 1 with electrodes on the perimeterMesh voltage and touch voltage
spacing factor for mesh voltageMesh voltage and touch voltage
spacing factor for step voltageStep voltage
correction factor of a power station unit with an on-load tap changerPer-unit quantities
correction factor of a network transformerShort-circuit currents by IEC 60909-0
l$, $nlength of the line, number of parallel circuitskm,Short-circuit currents by IEC 60909-0
total length of horizontal conductormStep voltage
L_C$, $L_Rtotal length of horizontal conductor and of electrodesmMesh voltage and touch voltage
effective length for mesh voltagemMesh voltage and touch voltage
perimeter of the matmMesh voltage and touch voltage
length of one electrodemMesh voltage and touch voltage
total length of electrodesmStep voltage
effective length of conductor and electrodes for step voltagemStep voltage
total buried length, conductor and electrodesmGrid resistance and GPR
L_x$, $L_ylength and width of the matmMesh voltage and touch voltage
exponent of the correction, which the design takes as 1Electrical clearances
factor for the heat effect of the DC componentPeak current and thermal equivalent current
basic lightning impulse insulation level of the protected levelkVDirect stroke shielding by the rolling sphere
rise of earth potential of the matVGrid resistance and GPR
thermal capacity per unit volumeJ/(cm³·°C)Conductor sizing
duty factor on the symmetrical currentShort-circuit duty by IEEE C37.010
geometry factor of the matMesh voltage and touch voltage
order of the reflectionTwo-layer soil
factor for the heat effect of the AC component, {{sc.peak_220.n}} far from a generatorPeak current and thermal equivalent current
n_a$, $n_bfactors of the geometry factor for a rectangular matMesh voltage and touch voltage
angular frequency, $2\pi f$rad/sGrid current
protected point, in planMasts and shield wires
plant capacityMWReactive power equipment
the ratio of a circle's circumference to its diameterSoil resistivity and Wenner readings
Q_{\mathrm{SVG}}$, $Q_{\mathrm{STATCOM}}total rating of the reactive power device, plus and minusMvarReactive power equipment
radius of the protected conductormDirect stroke shielding by the rolling sphere
resistance the earth tester readsΩSoil resistivity and Wenner readings
ratio of the resistance to the reactance of the positive-sequence impedance at the fault locationPeak current and thermal equivalent current
R_1$, $X_1positive-sequence resistance and reactance of a line circuitΩ/kmShort-circuit currents by IEC 60909-0
resistance of the bodyΩStep voltage
corona radiusmDirect stroke shielding by the rolling sphere
contact resistance of one foot on the surface layerΩStep voltage
grid resistanceΩGrid resistance and GPR
resistivity of the soilΩ·mGrid resistance and GPR
apparent resistivity of the soilΩ·mSoil resistivity and Wenner readings
resistivity of the soil below the surface layerΩ·mStep voltage
resistivity of the soil below the layerΩ·mSurface layer and Cs
\rho_1$, $\rho_2resistivity of the upper and the lower layerΩ·mTwo-layer soil
apparent resistivity at spacing $a$Ω·mTwo-layer soil
resistivity of the conductor at 20 °CµΩ·cmConductor sizing
resistivity of the surface layerΩ·mStep voltage
resistance of the neutral grounding resistorΩEarthing of the neutral
resistance of the neutral earthing resistorΩSymmetrical components
distance between successive electrodesmSoil resistivity and Wenner readings
radius of the rolling sphere of the protected levelmMasts and shield wires
striking distance, the radius of the rolling spheremDirect stroke shielding by the rolling sphere
rated asymmetrical capability of the breaker per unit of its rated short-circuit current, at $t$Short-circuit duty by IEEE C37.010
split factorGrid current
contact parting timemsShort-circuit duty by IEEE C37.010
ratio of the MV to the HV nominal voltageEarthing of the neutral
ambient temperature°CConductor sizing
DC time constant of the fault current, which IEEE 80-2013 writes $T_a$sGrid current
DC time constant of the faultmsShort-circuit duty by IEEE C37.010
duration of the currentsConductor sizing
duration of the faultsGrid current
duration of the short-circuit currentsPeak current and thermal equivalent current
maximum allowable temperature°CConductor sizing
rated ratio of the generator transformer, HV over LVPer-unit quantities
duration of the shock currentsStep voltage
rated short-circuit voltage of the transformer%Short-circuit currents by IEC 60909-0
nominal voltage of the MV systemkVEarthing of the neutral
U_n$, $U_{nQ}nominal voltage of the faulted bus, of the grid buskVShort-circuit currents by IEC 60909-0
rotation operator, $e^{j2\pi/3}$Short-circuit currents by IEC 60909-0
nominal voltage of the HV buskVPer-unit quantities
U_r$, $S_rrated voltage and rated apparent power of the equipmentkV, MVAPer-unit quantities
U_{rG}$, $S_{rG}rated voltage and rated apparent power of the generatorkV, MVAPer-unit quantities
U_{rT}$, $S_{rT}rated voltage on the HV side, rated apparent powerkV, MVAShort-circuit currents by IEC 60909-0
U_{rT}$, $S_{rT}rated voltage of the transformer on the side considered, rated apparent powerkV, MVAPer-unit quantities
U_{rTHV}$, $U_{rTLV}rated voltages of the generator transformer, HV and LV sidekVPer-unit quantities
phase angle of the generator at its rated power factorPer-unit quantities
subtransient reactance of the generator, per unit of its ratingPer-unit quantities
ratio of reactance to resistance of the fault pathGrid current
X_1$, $R_1$, $X_0$, $R_0positive- and zero-sequence reactance and resistance at the fault, from the separate reductionsΩShort-circuit duty by IEEE C37.010
relative reactance of the transformer, $X_T$ per unit of $U_{rT}^2/S_{rT}$Short-circuit currents by IEC 60909-0
relative reactance of the transformerPer-unit quantities
height of a wire, tower or mastmMasts and shield wires
zero-sequence impedance of a MV sectionΩEarthing of the neutral
Z_1$, $Z_2$, $Z_0positive-, negative- and zero-sequence impedance at the fault locationΩShort-circuit currents by IEC 60909-0
base impedance, $U_r^2/S_r$ΩPer-unit quantities
impedance of the generatorΩPer-unit quantities
Z_Q$, $R_Q$, $X_Qimpedance, resistance and reactance of the network feederΩShort-circuit currents by IEC 60909-0
Z_{Q1}$, $Z_{Q0}positive- and zero-sequence impedance of the grid feederΩSymmetrical components
surge impedance of the conductor under coronaΩDirect stroke shielding by the rolling sphere
impedance of the power station unit, referred to the HV busΩPer-unit quantities
Z_T$, $X_Timpedance and reactance of the transformerΩPer-unit quantities
zero-sequence impedance of the ICT, seen from the HV sideΩEarthing of the neutral
impedance of the generator transformer, referred to its HV sideΩPer-unit quantities