LibraryReferenceLightning protection

Direct stroke shielding by the rolling sphere

Direct stroke lightning protection (DSLP) shields the live parts of a switchyard against lightning strokes that would otherwise terminate on them. The Central Electricity Authority (CEA) Construction Regulations 2022 ask that the switchyard be shielded against direct lightning strokes by overhead shield wires, earth wires or masts (Reg. 44(2)(c)). The design checks the shielding by the rolling sphere method of IEEE Std 998-2012 (§6.6). This topic explains how the radius of the sphere is found for each protected level.

1The sphere and the protected level

A sphere is rolled over the ground, the shield wires and the masts. A point that the sphere cannot touch is protected (IEEE Std 998-2012 §6.6). The sphere's radius is the striking distance of the allowable stroke current , the smallest stroke current that can flash over the insulation of the protected level (§6.5). A stroke below that reaches the conductor does not flash over its insulation. Strokes with larger currents have larger striking distances, and the shield wires and masts intercept them. So the sphere depends on the protected level: its height, its conductor and its basic lightning impulse insulation level (BIL).

2The revised electrogeometric model

The design finds in four steps by the revised electrogeometric model of Mousa and Srivastava (IEEE Std 998-2012 §6.5). A conductor at height above the ground, of radius , carries the BIL of its level. Under the stroke's surge, corona forms around the conductor. The corona radius is the radius of that envelope at the BIL, with the corona inception gradient of 1500 kV/m for negative strokes.

(1)
IEEE Std 998-2012 §6.5

Eq. (1) has no closed form. The design solves it for by bisection, between a small radius and , where the left side is largest. It takes no smaller than the conductor's radius .

The surge impedance of the conductor under corona takes the corona radius in one logarithm and the conductor's radius in the other.

(2)
IEEE Std 998-2012 §6.5
(3)
IEEE Std 998-2012 §6.5
(4)
IEEE Std 998-2012 §6.5
where
height of the protected conductor above the groundm
radius of the protected conductorm
basic lightning impulse insulation level of the protected levelkV
corona inception gradientkV/m
corona radiusm
the base of the natural logarithm
surge impedance of the conductor under coronaΩ
allowable stroke currentkA
striking distance factor
striking distance, the radius of the rolling spherem

The factor is 1 for a shield wire. IEEE 998 allows 1.2 for a mast, which would protect a larger area. The design takes = 1 for the masts as well, so the mast coverage it shows is the smaller one.

Figure 1 shows the striking distance rising with the BIL. At the lowest BILs the sphere is smaller than the sphere of 20 m of IEC 62305-3 protection level I.

0102030400250500750100012501500Basic lightning impulse insulation level BIL (kVp)Striking distance S (m)Tubular bus, 9.0 mEquipment conductor, 5.9 mLPL I sphere, IEC 62305-3
Figure 1.The striking distance by Eq. (4) rises with the BIL from 170 kVp to 1425 kVp. The upper curve is the tubular bus of radius 57.15 mm at 9.0 m, and the lower curve is the equipment conductor of radius 15.9 mm at 5.9 m, as in the default 220 kV project. The design service calculated the values.

3Spheres of the protected levels

The design calculates a sphere for each protected level of the high-voltage (HV) yard from its own height, conductor radius and BIL. the table lists the levels of the default 220 kV project. The heights and the conductor radii are the design's values. The main bus is an aluminium tube of radius 57.15 mm. The equipment interconnection is aluminium conductor steel-reinforced (ACSR) Moose of radius 15.9 mm, as is the conductor at the bushing tops of the interconnecting transformers (ICT).

LevelMethodProtected heightSphere radius
HV tubular busIEEE 998 (Mousa)9.0 m29.15 m
HV equipmentIEEE 998 (Mousa)5.9 m28.97 m
ICT bushing topsIEEE 998 (Mousa)7.5 m27.99 m
33 kV outdoor areasIEC 62305 LPL I5.5 m20.0 m
Control building roofIEC 62305 LPL I6.0 m20.0 m

The transformer bushing tops take a smaller sphere than the bus, at the same BIL. Their conductor is thinner than the bus's tube, which raises the surge impedance and lowers the allowable stroke current. A switching substation's lower yard takes its spheres from its own BIL in the same way.

4The sphere of IEC 62305-3

IEC 62305-3 Table 2 gives the rolling sphere's radius per lightning protection level (LPL), as the table lists. The design takes the sphere of LPL I, the smallest and so the most protective, for the MV outdoor areas, the control building's roof and the roof of a gas-insulated switchgear (GIS) hall.

Lightning protection levelSphere radius
I20 m
II30 m
III45 m
IV60 m

The MV areas carry a BIL of 170 kVp. There the Mousa sphere is 7.8 m (IEEE Std 998-2012 §6.5). Masts at least that tall would stand no more than 11.0 m apart on a square grid to protect the ground (a protected height of 0 m), against 28.3 m for the sphere of 20 m. Both spacings are the sphere's radius times , derived from the geometry. When the HV level's own BIL is 170 kVp or less, the whole yard takes the LPL I sphere.

The IEC + CEA / CBIP set and the ANSI / IEEE set take the same spheres: the Mousa sphere for the HV yard and the LPL I sphere for the building and the MV areas.

5The rolling sphere over the yard

The design service builds the yard in three dimensions, with its lightning masts and shield wires. Figure 2 rolls the sphere of each protected level over that model and draws the level as a plane. A point that the sphere cannot touch without first touching a mast, a wire or the ground is protected (IEEE Std 998-2012 §6.6). For the default yard the sphere stays above each level at its protected points. The least margin is the smallest height between a level and the lowest point the sphere reaches over it.

Level: HV tubular bus · margin 8.09 m · Pass
Rolling sphere of the levelProtected levelShield wire
Figure 2.The sphere of 29.15 m for the HV tubular bus, by the revised electrogeometric model of Mousa and Srivastava, rolled over the default 220 kV yard with its 14 lightning masts of 25.0 m and 5 shield wires at 18.5 m. The figure opens on that level, drawn as a plane; the least margin above it is 8.09 m. The design service built the model and calculated the values.
Example 1Sphere radius of the default 220 kV tubular bus

Given the HV tubular bus of a new 220 kV project with the default inputs, as the design service calculates it.

QuantityValue
BIL1050 kVp
Bus height 9.0 m
Tube radius 57.15 mm
Corona inception gradient 1500 kV/m
Striking distance factor 1

Corona radius by Eq. (1), solved by bisection:

Surge impedance by Eq. (2):

Allowable stroke current by Eq. (3):

Striking distance by Eq. (4):

Result The rolling sphere of the HV tubular bus has a radius of 29.15 m. The HV equipment takes 28.97 m and the ICT bushing tops 27.99 m, from the same steps.

Sources

[1]IEEE Std 998-2012, IEEE Guide for Direct Lightning Stroke Shielding of Substations. §6.5.

[2]IEC 62305-3, Protection against lightning.

[3]CEA Construction Regulations 2022, Central Electricity Authority (Technical Standards for Construction of Electrical Plants and Electric Lines) Regulations, 2022.

CitationSubstationLayout Reference, Direct stroke shielding by the rolling sphere, revision 2, 8 Nov 2026, https://substation.solarlayout.app/library/reference/rolling-sphere