LibraryReferenceEarthing

Surface layer and Cs

A surface layer is a layer of crushed rock, of high resistivity, spread over the soil of the switchyard. It adds resistance at a person's feet and so raises the tolerable touch and step voltages (IEEE Std 80-2013 §7.4).

Read first: Tolerable body current

1The layer at a person's feet

The contact resistance of one foot is , where is the layer's resistivity (Tolerable body current, From current to voltage). A layer of higher resistivity than the soil raises that resistance, so the same body current needs a higher voltage. The design takes a layer of 3000 Ω·m and 0.10 m by default, set on the Site & soil page.

2The derating factor

Over a soil of lower resistivity, a layer of finite depth gives a lower resistance at the feet than a deep layer of its own resistivity. The derating factor corrects the layer's resistivity for its depth.

(1)
IEEE Std 80-2013 §7.4, Eq. 27
where
surface layer derating factor
resistivity of the soil below the layerΩ·m
resistivity of the surface layerΩ·m
depth of the surface layerm

is 1 when the layer's resistivity equals the soil's, since the numerator is then zero. It rises towards 1 as the layer deepens (Figure 1). With no surface layer, a depth of 0 m, the design takes = 1. In a two-layer soil, is the upper layer's resistivity with the season factor (Two-layer soil, How the design uses the layers).

0.50.60.70.80.91.00.000.050.100.150.200.250.30Depth of the surface layer hs (m)Derating factor Csρs 1000 Ω·mρs 3000 Ω·m
0.150 m · ρs 3000 Ω·m: 0.781 · ρs 1000 Ω·m: 0.804
Figure 1.The derating factor rises with the depth of the surface layer, for layers of 1000 Ω·m and 3000 Ω·m over soil of 150 Ω·m. The design service calculated the values by Eq. (1).
Example 1The derating factor of the default 220 kV project

Given soil of 150 Ω·m below a layer of 3000 Ω·m and 0.10 m.

Derating factor by Eq. (1):

Result The layer's effective resistivity at the feet is 0.705 of its own. The tolerable touch voltage is 685 V and the tolerable step voltage 2246 V (Tolerable body current, Example 1).

Sources

[1]IEEE Std 80-2013, IEEE Guide for Safety in AC Substation Grounding. §7.4, Eq. 27.

CitationSubstationLayout Reference, Surface layer and Cs, revision 1, 8 Nov 2026, https://substation.solarlayout.app/library/reference/surface-layer