Surface layer and Cs
A surface layer is a layer of crushed rock, of high resistivity, spread over the soil of the switchyard. It adds resistance at a person's feet and so raises the tolerable touch and step voltages (IEEE Std 80-2013 §7.4).
Read first: Tolerable body current
1The layer at a person's feet
The contact resistance of one foot is , where is the layer's resistivity (Tolerable body current, From current to voltage). A layer of higher resistivity than the soil raises that resistance, so the same body current needs a higher voltage. The design takes a layer of 3000 Ω·m and 0.10 m by default, set on the Site & soil page.
2The derating factor
Over a soil of lower resistivity, a layer of finite depth gives a lower resistance at the feet than a deep layer of its own resistivity. The derating factor corrects the layer's resistivity for its depth.
| surface layer derating factor | ||
| resistivity of the soil below the layer | Ω·m | |
| resistivity of the surface layer | Ω·m | |
| depth of the surface layer | m |
is 1 when the layer's resistivity equals the soil's, since the numerator is then zero. It rises towards 1 as the layer deepens (Figure 1). With no surface layer, a depth of 0 m, the design takes = 1. In a two-layer soil, is the upper layer's resistivity with the season factor (Two-layer soil, How the design uses the layers).
Given soil of 150 Ω·m below a layer of 3000 Ω·m and 0.10 m.
Derating factor by Eq. (1):
Result The layer's effective resistivity at the feet is 0.705 of its own. The tolerable touch voltage is 685 V and the tolerable step voltage 2246 V (Tolerable body current, Example 1).
[1]IEEE Std 80-2013, IEEE Guide for Safety in AC Substation Grounding. §7.4, Eq. 27.