Step voltage
The step voltage is the difference in surface potential that a person bridges with the feet 1 m apart, without touching an earthed object, while fault current flows from the earth mat into the soil (IEEE Std 80-2013 §3).
Read first: Tolerable body current · Surface layer and Cs
1The surface potential during a fault
During an earth fault, part of the fault current flows from the earth mat into the soil and returns through the earth to the source. The soil around the mat rises in potential. The potential is highest over the conductors and falls with distance from them, so two points of the surface 1 m apart are at different potentials. A person standing across two such points carries a current from one foot to the other (Figure 1).
The potential falls fastest outside the mat's perimeter, where no conductor lies under the surface (Figure 2). Inside the mat it rises over each conductor and dips between them.
2The body in the circuit
The current enters at one foot, passes through the legs and leaves at the other foot. The body's resistance and the contact resistances of the two feet with the surface are in series (Figure 3). IEEE Std 80-2013 takes as 1000 Ω and the contact resistance of one foot on the surface layer as (§7). Two feet in series give the of Eq. (4).
3The tolerable step voltage
The tolerable step voltage drives the largest body current that a person of 50 kg tolerates for the duration of the shock. IEEE Std 80-2013 sets that current from the fibrillation threshold of the body. It is inversely proportional to the square root of the shock time.
A layer of crushed rock at the surface raises the contact resistance of the feet. The derating factor corrects the layer's resistivity for its finite depth over the soil below.
| body current that a person of 50 kg tolerates | A | |
| duration of the shock current | s | |
| resistivity of the soil below the surface layer | Ω·m | |
| resistivity of the surface layer | Ω·m | |
| depth of the surface layer | m | |
| surface layer derating factor | ||
| resistance of the body | Ω | |
| contact resistance of one foot on the surface layer | Ω | |
| tolerable step voltage | V | |
| tolerable step voltage for a person of 50 kg | V |
Figure 4 shows the limit against the surface layer's resistivity. Over soil of 150 Ω·m, the tolerable step voltage is 312 V without a surface layer and 2246 V with a layer of 3000 Ω·m and 0.10 m.
4The step voltage of an earth mat
For a rectangular mat in uniform soil, IEEE Std 80-2013 gives the largest step voltage from the soil's resistivity, the grid current and the mat's geometry. The effective length counts 75 % of the horizontal conductor and 85 % of the electrodes.
| step voltage of the mat | V | |
| maximum grid current | A | |
| spacing factor for step voltage | ||
| irregularity factor | ||
| effective length of conductor and electrodes for step voltage | m | |
| total length of horizontal conductor | m | |
| total length of electrodes | m | |
| spacing between parallel conductors | m | |
| burial depth of the mat | m | |
| geometry factor of the mat | ||
| the ratio of a circle's circumference to its diameter |
Eq. (7) holds for a burial depth between 0.25 m and 2.5 m (§16.5.2). The geometry factor is the one the mesh voltage uses (Eq. 84 to 88 of §16.5.1).
Given the earth mat of a new 220 kV project with the default inputs, as the design service calculates it.
| Quantity | Value |
|---|---|
| Soil resistivity, measured × season factor | 100 Ω·m × 1.5 = 150 Ω·m |
| Surface layer, resistivity and depth | 3000 Ω·m, 0.10 m |
| Shock time | 0.5 s |
| Grid current, fault current × split factor × decrement factor | 50 kA × 0.6 × 1.062 = 31 853 A |
| Mat, length × width, conductors | 155.0 m × 133.4 m, 40 × 35 |
| Mesh spacing , burial depth | 3.97 m, 0.6 m |
| Electrodes | 96 of 3 m |
| Conductor length , electrode length | 10 761 m, 288 m |
| Geometry factor (Eq. 84 to 88) | 37.37 |
Derating factor by Eq. (2):
Tolerable step voltage by Eq. (4):
Factors by Eq. (6), Eq. (8) and Eq. (7):
Step voltage by Eq. (5):
Result The step voltage of 1472 V is below the tolerable 2246 V. The mat complies with the step voltage limit.
[1]IEEE Std 80-2013, IEEE Guide for Safety in AC Substation Grounding. §5.3, Eq. 6; §7.4, Eq. 27; §8.3; §8.3, Eq. 29; §16.5.2, Eq. 92; §16.5.2, Eq. 93; §16.5.2, Eq. 94; §16.5.1, Eq. 89.