Tolerable body current
The tolerable body current is the largest current a person of a given weight tolerates for the duration of a shock (IEEE Std 80-2013 §5.3). It is the starting point of the tolerable touch and step voltages, the limits an earth mat is designed to.
1The current a body tolerates
IEEE Std 80-2013 sets the tolerable current from the fibrillation threshold of the body. The current is inversely proportional to the square root of the shock time, with one constant for a person of 50 kg and another for a person of 70 kg.
| , | body current a person of 50 kg or 70 kg tolerates | A |
| duration of the shock current | s |
A shorter shock is tolerated at a higher current (Figure 1). The shock time is the fault clearing time a person is exposed to. The design takes 0.5 s by default, the backup protection's clearing time, unless a protection study gives less.
2From current to voltage
The tolerable voltage is the body current times the resistance of its path. IEEE Std 80-2013 takes the body's resistance as 1000 Ω and the contact resistance of one foot on the surface layer as (§7). In a touch, the current runs from the hand to both feet, which are in parallel: their resistance is . In a step, it runs from one foot to the other, through both feet in series: (Step voltage).
| , | tolerable touch and step voltage for a person of 50 kg | V |
| surface layer derating factor (Surface layer and Cs) | ||
| resistivity of the surface layer | Ω·m |
The equations for a person of 70 kg take 0.157 in place of 0.116 (Eq. 33 and 30). The design checks the IEC + CEA / CBIP set's mats against the limits for 50 kg and reports those for 70 kg beside them. The ANSI / IEEE set checks against the limits for 70 kg.
Given a shock time of 0.5 s, a surface layer of 3000 Ω·m and 0.10 m, and its derating factor = 0.705 (Surface layer and Cs, Example 1).
Body current by Eq. (1) and Eq. (2):
Tolerable touch voltage by Eq. (3):
Tolerable step voltage by Eq. (4):
Result The mat of the default project is designed to a tolerable touch voltage of 685 V and a tolerable step voltage of 2246 V. For a person of 70 kg the limits are 927 V and 3040 V.
[1]IEEE Std 80-2013, IEEE Guide for Safety in AC Substation Grounding. §5.3, Eq. 6; §5.3, Eq. 7; §8.3, Eq. 32; §8.3, Eq. 29.