Glossary
A
- AC distribution board (ACDB)
- The two-section low-voltage switchboard, joined by a normally open bus coupler, that the auxiliary transformers and the DG set feed.
- Topic: AC auxiliary supply
- air circuit breaker (ACB)
- The breaker of an incomer of the ACDB, and of a feeder whose current is above the largest MCCB rating, in IEC 60947-2 rated currents.
- Topic: AC auxiliary supply
- air-insulated switchgear (AIS)
- Switchgear in an open yard, with air as the insulation between its live parts.
- Topic: Bus schemes
- allowable stroke current ()
- The smallest stroke current that can flash over the insulation of a protected level.
- Topic: Direct stroke shielding by the rolling sphere, Eq. (3)
- alternating current (AC)
- Current that reverses its direction at the frequency of the network, as the auxiliary supply distributes it to the substation's low-voltage loads.
- Topic: AC auxiliary supply
- altitude correction factor ()
- The factor of IEC 60071-2 by which the design multiplies the electrical distances of a site above the standard altitude.
- Topic: Electrical clearances, Eq. (1)
- aluminium conductor steel-reinforced (ACSR)
- A stranded conductor of aluminium wires on a steel core, the conductor of the yard's equipment interconnection.
- Topic: Direct stroke shielding by the rolling sphere
- apparent resistivity ()
- The resistivity a Wenner reading gives at one spacing, for a resistance read at a spacing .
- Topic: Soil resistivity and Wenner readings, Eq. (1)
- automatic mains failure panel (AMF)
- The panel that starts the DG set when the transformer supply of the auxiliary switchboard is lost.
- Topic: AC auxiliary supply
- automatic transfer switch (ATS)
- The switch through which the standby generator of the ANSI / IEEE set's station service starts.
- Topic: AC auxiliary supply
- availability-based tariff (ABT)
- The tariff for which the line bay carries the main and check meters of the grid connection in the IEC + CEA / CBIP set.
- Topic: Bays and their equipment
B
- base impedance ()
- The impedance that the rated voltage and the rated apparent power of a piece of equipment define.
- Topic: Per-unit quantities
- basic lightning impulse insulation level (BIL)
- The lightning impulse withstand voltage of a voltage level, a peak value in kVp.
- Topic: Insulation levels
- basic switching impulse insulation level (BSL)
- The switching impulse level that the ANSI / IEEE set takes from IEEE C37.04-2018 Table 6 at its highest voltage level.
- Topic: Insulation levels
- bay
- The set of equipment that connects one circuit to the buses of a high-voltage switchyard.
- Topic: Bays and their equipment
- bill of materials (BOM)
- The list of the substation's equipment and materials that the design calculates, with a specification, a unit, a quantity and the spares of each line.
- Topic: Bill of materials
- bus post insulator (BPI)
- An insulator that supports a tubular bus, one more per tube than the tube's spans.
- Topic: Bill of materials
- bus reactor
- A shunt reactor on an HV bus, in a circuit position of its own, that absorbs reactive power to hold down the bus voltage.
- Topic: Reactive power equipment
- bus scheme
- The way the circuits of a substation connect to its buses, which sets its number of circuit breakers and the arrangement of the yard's bays.
- Topic: Bus schemes
C
- capacitor voltage transformer (CVT)
- The voltage transformer at the line entry of a line bay, also the voltage transformer of an HV bus above the 33 kV level.
- Topic: Bays and their equipment
- capacity rating factor ()
- The rated ampere-hours of a cell per ampere of load held for a time , from the cell's discharge curve to the end-of-discharge voltage.
- Topic: DC system, Eq. (2)
- Central Board of Irrigation and Power (CBIP)
- The board whose manuals the IEC + CEA / CBIP set joins with the IEC standards and the CEA regulations.
- Topic: The IEC + CEA / CBIP set
- circuit breaker (CB)
- The switching device of a bay, rated at the level's voltage, its design fault level and the bay current, whose number follows the bus scheme.
- Topic: Circuit breakers and isolators
- corona radius ()
- The radius of the corona envelope that forms around a conductor under a lightning stroke's surge.
- Topic: Direct stroke shielding by the rolling sphere, Eq. (1)
- coupling capacitor voltage transformer (CCVT)
- The name of the capacitor voltage transformer in the ANSI / IEEE set's bill of materials.
- Topic: Instrument transformers
- current transformer (CT)
- The instrument transformer that measures the current of a bay's circuit, next to its circuit breaker.
- Topic: Bays and their equipment
D
- DC distribution board (DCDB)
- The two-section board, joined by a normally open coupler, that the chargers and batteries feed and from which the DC loads are supplied.
- Topic: DC system
- decrement factor ()
- The factor that raises the symmetrical fault current to the effective value of the asymmetric current over the fault's duration.
- Topic: Grid current, Eq. (1)
- diesel generator set (DG)
- The standby generator of the IEC + CEA / CBIP set's auxiliary supply, which supplies the full auxiliary load when both auxiliary transformers are out.
- Topic: AC auxiliary supply
- direct current (DC)
- Current of one direction, as a battery and its chargers supply it to the protection, control and trip circuits when the AC auxiliary supply is lost.
- Topic: DC system
- direct stroke lightning protection (DSLP)
- The shielding of a switchyard's live parts against lightning strokes that would otherwise terminate on them.
- Topic: Direct stroke shielding by the rolling sphere
- direct-on-line start (DOL)
- A motor start that draws several times the motor's full-load current at a low power factor, which causes a transient voltage dip on the supply.
- Topic: AC auxiliary supply
- double main bus
- A bus scheme with a circuit breaker per bay and a bus coupler between its two buses.
- Topic: Bus schemes
- Drawing Exchange Format (DXF)
- The CAD file format of the drawings, drawn from the same model of a sheet as the screen and the PDF file.
- Topic: Drawing conventions
- duty cycle
- The current a battery must deliver, period by period, over the time it supports the substation without a charger.
- Topic: DC system
E
- electric overhead travelling crane (EOT)
- The crane of a GIS hall, which the BOM lists with the hall.
- Topic: Gas-insulated switchgear (GIS)
- electrical clearance
- A least distance in air that the switchyard keeps around its live parts.
- Topic: Electrical clearances
G
- gas-insulated bus duct (GIB)
- A gas-insulated duct that carries a circuit out of the GIS hall, one of the exits the SLD marks, with the SF6/air bushing and the cable end.
- Topic: Gas-insulated switchgear (GIS)
- gas-insulated switchgear (GIS)
- Switchgear of gas-insulated modules in an indoor hall, the GIS hall.
- Topic: Gas-insulated switchgear (GIS)
- grid current ()
- The part of an earth fault's current that flows from the earth mat into the soil, raised for the DC offset of the fault current.
- Topic: Grid current
- grid resistance ()
- The resistance of the earth mat to remote earth.
- Topic: Grid resistance and GPR, Eq. (1)
- ground clearance
- The equipment level of a yard, the height of its live parts above the ground.
- Topic: Electrical clearances
H
- harmonic filter
- A tuned bank of capacitors and reactors on an MV section, whose rating comes from a harmonic study.
- Topic: Reactive power equipment
- high-voltage (HV)
- The voltage level of the substation's switchyard and of its lines to the grid.
- Topic: Bays and their equipment
- highest system voltage ()
- The first insulation rating of a voltage level, by which IEC 60071-1:2019 divides the levels into range I and range II.
- Topic: Insulation levels
- horizontal centre-break isolator (HCB)
- The design's three-phase, motor-operated HV isolator, rated at the bay's current and the level's ratings.
- Topic: Circuit breakers and isolators
I
- initial symmetrical current ()
- The symmetrical short-circuit current at the first instant of a fault.
- Topic: Short-circuit currents by IEC 60909-0
- Institute of Electrical and Electronics Engineers (IEEE)
- The institute whose standards, with the ANSI standards and the NESC, make up the ANSI / IEEE set.
- Topic: The ANSI / IEEE set
- interconnecting transformer (ICT)
- A power transformer of the substation, connected to the HV buses through its transformer bay.
- Topic: Bays and their equipment
- irregularity factor ()
- The factor of IEEE Std 80-2013 in the mesh and step voltages, which grows with the mat's geometry factor .
- Topic: Mesh voltage and touch voltage, Eq. (6)
L
- lightning mast
- A mast that protects what the shield wires leave exposed, placed by the design one at a time where it protects the most exposed points.
- Topic: Masts and shield wires
- lightning protection level (LPL)
- A level of IEC 62305-3, for which Table 2 gives the radius of the rolling sphere.
- Topic: Direct stroke shielding by the rolling sphere
- line reactor
- A shunt reactor at the end of a 765 kV line, switched by its own circuit breaker, with its neutral earthed through a neutral grounding reactor.
- Topic: Reactive power equipment
- load tap changer (LTC)
- The ANSI / IEEE set's name for the on-load tap changer.
- Topic: Power transformers
- low-voltage (LV)
- The voltage level of the substation's AC auxiliary supply and its switchboard, and of the lower-voltage side of a transformer.
- Topic: AC auxiliary supply
- low-voltage power circuit breaker (LVPCB)
- The breaker of the ANSI / IEEE set's station service incomers, coupler and feeders above the molded-case breaker range, in the frame sizes of IEEE C37.13-2015.
- Topic: AC auxiliary supply
M
- maximum demand
- The apparent power the auxiliary supply carries with the loads at their duty factors, the vector sum of the active and reactive demand.
- Topic: AC auxiliary supply
- medium-voltage (MV)
- The voltage level of the substation's MV buses, between the transformers' low-voltage windings and the feeders.
- Topic: Bus and bay current ratings
- mesh voltage ()
- The highest touch voltage inside one mesh of the earth mat during a fault.
- Topic: Mesh voltage and touch voltage, Eq. (2)
- moulded-case circuit breaker (MCCB)
- The breaker of a load group's feeder on the ACDB, rated at the first standard current at or above the group's full-load current.
- Topic: AC auxiliary supply
- multi-ratio current transformer (MR)
- A current transformer with several ratios, the HV CT of the ANSI / IEEE set, whose full ratio is the bay current.
- Topic: Instrument transformers
N
- National Electrical Safety Code (NESC)
- The code, 2007 edition, from which the ANSI / IEEE set takes the clearance of live parts above surfaces where people stand and the fence clearance.
- Topic: Clearances of the ANSI / IEEE set
- negative-sequence impedance ()
- The impedance of the network at the fault location to a balanced set of currents in the reverse phase order, which the design takes equal to .
- Topic: Symmetrical components
- neutral grounding resistor (NGR)
- The resistor through which a transformer's MV neutral is earthed, which limits the line-to-earth fault current on the MV section.
- Topic: Bays and their equipment
O
- on-load tap changer (OLTC)
- The tap changer of the ICT, which changes the ratio over its range in steps.
- Topic: Power transformers
- one-and-a-half breaker
- A bus scheme with three circuit breakers per diameter of two circuits.
- Topic: Bus schemes
P
- peak factor ()
- The ratio of the peak short-circuit current to , which falls from 2 as the R/X ratio at the fault location rises.
- Topic: Peak current and thermal equivalent current, Eq. (2)
- peak short-circuit current ()
- The first peak of a short-circuit current, which sets the current a circuit breaker must make.
- Topic: Peak current and thermal equivalent current, Eq. (1)
- per unit (pu)
- A quantity divided by a base of the same kind: for equipment, its rated voltage, its rated apparent power or the base impedance they define.
- Topic: Per-unit quantities
- phase-to-earth clearance
- The distance from the outer phase of a bay to the edge of the bay.
- Topic: Electrical clearances
- Portable Document Format (PDF)
- The file format of the drawings and documents, drawn from the same model of a sheet as the screen and the DXF file.
- Topic: Drawing conventions
- positive-sequence impedance ()
- The impedance of the network at the fault location to a balanced set of currents in the network's phase order.
- Topic: Symmetrical components
- potential transformer (PT)
- The voltage transformer of an HV bus or bus section at the 33 kV level, in place of a CVT.
- Topic: Bays and their equipment
R
- rated short-circuit voltage ()
- A transformer's impedance in percent of its base impedance, from which the design calculates the impedance in ohms.
- Topic: Per-unit quantities, Eq. (1)
- reflection factor ()
- The factor of the interface of a two-layer soil, between −1 and 1.
- Topic: Two-layer soil, Eq. (2)
- reinforced cement concrete (RCC)
- The construction of the control building in the IEC + CEA / CBIP set's BOM, counted by the building's floor area.
- Topic: Roads, trenches and buildings
- relative reactance ()
- The reactance of a transformer per unit of its base impedance, which sets the correction factor .
- Topic: Per-unit quantities, Eq. (2)
- ring bus
- A bus scheme of the ANSI / IEEE set: a closed loop with a circuit breaker between two bus sections, each section supplying one circuit.
- Topic: Bus schemes
- rise of earth potential (GPR)
- The voltage of the earth mat above remote earth during a fault, the grid current times the grid resistance.
- Topic: Grid resistance and GPR, Eq. (3)
- rolling sphere
- A sphere rolled over the ground, the shield wires and the masts: a point the sphere cannot touch is protected from direct strokes.
- Topic: Direct stroke shielding by the rolling sphere
- Rural Utilities Service (RUS)
- The service whose Bulletin 1724E-300, a design guide for rural substations, gives the ANSI / IEEE set its yard clearances, its ring bus and its station service.
- Topic: The ANSI / IEEE set
S
- sectional clearance
- The gap between the nearest phases of the two main buses, for maintenance with one bus live.
- Topic: Electrical clearances
- shield wire
- An overhead conductor that the design runs along a column boundary of the HV yard, above the gantry beam, to shield the yard from direct strokes.
- Topic: Masts and shield wires
- single-line diagram (SLD)
- A diagram of the substation's electrical connections with one line for the three phases.
- Topic: Single-line diagram (SLD)
- solidly earthed neutral
- A transformer or reactor neutral connected to earth with no added impedance, as the HV neutrals of the design's ICTs are.
- Topic: Earthing of the neutral
- split factor ()
- The share of the earth fault current that flows from the earth mat into the soil.
- Topic: Grid current
- spreadsheet workbook (XLSX)
- The file in which the BOM is delivered, with a BOM sheet and a Vendors sheet.
- Topic: Bill of materials
- static synchronous compensator (STATCOM)
- The reactive power device of the ANSI / IEEE set, one on each MV section, rated on Auto for the reactive power of the plant at its rated output and a power factor of 0.95.
- Topic: Reactive power equipment
- static var generator (SVG)
- The reactive power device of the IEC + CEA / CBIP set, one on each MV section, rated on Auto at a share of the plant capacity.
- Topic: Reactive power equipment
- step voltage ()
- The difference in surface potential that a person bridges with the feet 1 m apart, without touching an earthed object, during an earth fault.
- Topic: Step voltage
- striking distance ()
- The radius of the rolling sphere for a protected level, from the allowable stroke current of that level.
- Topic: Direct stroke shielding by the rolling sphere, Eq. (4)
- subtransient reactance ()
- The reactance of a synchronous generator that its datasheet gives per unit of its own rating, from which the design calculates the generator's impedance in the short-circuit study.
- Topic: Per-unit quantities
- sulphur hexafluoride (SF6)
- The insulating gas of the GIS enclosures and of the HV circuit breakers, from which a GIS line leaves through an SF6/air bushing.
- Topic: Yard layout
- surface layer
- A layer of crushed rock of high resistivity, spread over the soil of the switchyard, that raises the tolerable touch and step voltages.
- Topic: Surface layer and Cs
- surface layer derating factor ()
- The factor that corrects the surface layer's resistivity for its finite depth over the soil below.
- Topic: Surface layer and Cs, Eq. (1)
- surge impedance ()
- The impedance of a conductor to a lightning stroke's surge under corona, from its height, its radius and the corona radius.
- Topic: Direct stroke shielding by the rolling sphere, Eq. (2)
- switching impulse withstand voltage (SIWL)
- The switching impulse withstand of a voltage level in kVp, carried at the highest levels only.
- Topic: Insulation levels
- symmetrical components
- The positive-, negative- and zero-sequence sets of balanced currents whose sum gives the currents of an unbalanced fault.
- Topic: Symmetrical components
T
- temporary overvoltage (TOV)
- The overvoltage at a surge arrester's location, given by the neutral earthing study, on which the arrester's rating depends.
- Topic: Insulation levels
- thermal equivalent current ()
- The heat of a short-circuit current over the fault's duration, expressed as a current, which sets the short-time rating.
- Topic: Peak current and thermal equivalent current, Eq. (4)
- tolerable body current ()
- The largest current a person of a given weight tolerates for the duration of a shock.
- Topic: Tolerable body current
- tolerable step voltage
- The step voltage that drives the tolerable body current through the body and the two feet in series.
- Topic: Tolerable body current, Eq. (4)
- tolerable touch voltage
- The touch voltage that drives the tolerable body current through the body and the two feet in parallel.
- Topic: Tolerable body current, Eq. (3)
- touch voltage
- The difference between the rise of earth potential of the earth mat and the surface potential where a person stands while touching an earthed structure.
- Topic: Mesh voltage and touch voltage
- two-layer soil
- A soil model of an upper layer of resistivity and depth over a lower layer of resistivity .
- Topic: Two-layer soil
V
- vacuum circuit breaker (VCB)
- The withdrawable circuit breaker of a metal-clad MV panel, and the breaker of an outdoor MV bay.
- Topic: Circuit breakers and isolators
- valve-regulated lead-acid (VRLA)
- The lead-acid battery type of the IEC + CEA / CBIP set's DC system.
- Topic: DC system
- voltage factor ()
- The factor of the equivalent voltage source : for the maximum currents and for the minimum currents.
- Topic: Short-circuit currents by IEC 60909-0
W
- water-bound macadam (WBM)
- A road construction that the BOM's road line of the IEC + CEA / CBIP set reads, with bituminous roads.
- Topic: Roads, trenches and buildings
- Wenner method
- The measurement of the soil's resistivity with four electrodes in a straight line at equal spacing, current through the outer pair and voltage across the inner pair.
- Topic: Soil resistivity and Wenner readings
Z
- zero-sequence impedance ()
- The impedance of the network at the fault location to 3 equal currents in phase, which return through earth or a neutral.
- Topic: Symmetrical components