Active, reactive and apparent power
In a direct-current circuit the power is the voltage times the current. In an alternating-current circuit the current can be shifted in time from the voltage, and the product of the root-mean-square value (RMS) of the voltage and that of the current no longer gives the power that does work. This topic splits that product into active power, which does the work, and reactive power, which moves to and fro between the source and the fields of the circuit. It defines the power factor and the three-phase power, and explains why a substation design rates its equipment and its reactive power devices by them.
Before this topic: Voltage, current and impedance in AC circuits · Three-phase systems
1Instantaneous power
The power that flows into an element at an instant is the product of its voltage and its current at that instant, . With sine waves of voltage and current shifted by the angle , this product is the sum of 2 terms:
The first term pulses at twice the frequency, stays at or above zero, and has the average . It is the power that the element takes and keeps, as heat in a resistance or as work in a motor. The second term swings between and and has an average of zero. It is the energy that an inductance or a capacitance holds in one quarter-cycle and returns in the next (Voltage, current and impedance in AC circuits, Inductance and capacitance).
| instantaneous power | W | |
| , | instantaneous voltage and current | V, A |
| active power, the average of | W | |
| reactive power | var | |
| angle by which the current lags the voltage | ° | |
| angle of the voltage wave at the time zero | rad |
2Active, reactive and apparent power
The powers of a single-phase circuit follow from the RMS voltage , the RMS current and the angle by which the current lags the voltage:
The active power is in watts (W). The reactive power is in volt-amperes reactive (var). The apparent power is in volt-amperes, symbol VA. The different units mark 3 quantities that would otherwise share the unit of a volt times an ampere. A substation works in kW, kvar and kVA or in MW, Mvar and MVA.
The reactive power is positive when the current lags the voltage, as in an inductance, and negative when it leads, as in a capacitance. An inductive load absorbs reactive power, and a capacitor supplies it. In complex form the 3 powers are one quantity, , the complex power.
| , | RMS voltage and current | V, A |
| angle by which the current lags the voltage | ° | |
| apparent power | VA |
3The power triangle
Active and reactive power add at a right angle, as resistance and reactance do in an impedance. They form the 2 sides of a right triangle whose long side is the apparent power (Figure 1):
The angle of the triangle is the angle between the voltage and the current. With the power factor and the active power known, the reactive power is .
4Power factor
The power factor is the ratio of the active power to the apparent power. For sine waves it is the cosine of the angle between the voltage and the current:
A power factor of 1 means a current in phase with the voltage, with no reactive power. A lower power factor means more current for the same active power. A power factor is lagging when the current lags the voltage, as for an inductive load, and leading when the current leads.
Power factor correction brings the power factor towards 1. It adds a capacitance to a circuit that is inductive, or an inductance to one that is capacitive, until their reactive powers cancel.
| power factor |
5Three-phase power
A balanced three-phase circuit carries the same power in each phase. Its total is 3 times the power of one phase, , with the phase voltage . With the line voltage (Three-phase systems, Eq. (2)), the apparent power is:
The active and the reactive power follow as and . The three-phase power of a balanced set is constant in time, since the pulses of the 3 phases cancel (Three-phase systems, Why power systems are three-phase).
The equation also gives the current from the power: . This is how a transformer's rating in MVA gives its rated current on each side.
| line voltage (RMS) | V | |
| phase voltage (RMS) | V | |
| line current (RMS) | A |
6Why reactive power matters to a substation
Reactive power does no work, but its current flows in the conductors, the switchgear and the transformers. The current follows the apparent power, not the active power. A transformer, a breaker or a cable is therefore rated by its current or its apparent power, in A or MVA. The current also heats the conductors in proportion to its square, so a low power factor raises the losses.
Reactive power is tied to the voltage. For a line modelled as a reactance between the sending voltage and the receiving voltage , at an angle between them, the reactive power sent into the line is:
At a small angle the cosine is close to 1, and depends on the difference between the 2 voltage magnitudes. Reactive power flows from the higher voltage towards the lower. The active power, , depends on the angle instead. A line also has capacitance, and a long line that is lightly loaded can have a receiving voltage above its sending voltage. Shunt reactors compensate that rise on many transmission lines, and a substation can carry them (Reactive power equipment, The bus reactor).
A grid code requires a plant to supply or absorb reactive power over a range of power factor at its connection to the grid (Reactive power equipment, The reactive power range at the interconnection). The substation's reactive power devices supply that range.
| , | voltage magnitudes at the sending and the receiving end | kV |
| reactance of the line | Ω | |
| angle between the sending and the receiving voltage | ° | |
| reactive power sent into the line | Mvar |
7In the design
The design calculates the plant's apparent power from its capacity and a power factor of 0.95, the value of the reactive power range at the grid connection. The interconnecting transformers (ICTs) are rated for that apparent power with a margin (Power transformers, Number and rating).
On the IEC + CEA / CBIP set the design places a static var generator (SVG) on the medium-voltage (MV) buses. On Auto, its rating comes from a reactive power study of the network up to the interconnection point, where the plant meets the grid. The default plant's SVG is 116.0 Mvar in total, 58.00 Mvar on each of the 2 MV sections (Reactive power equipment, The SVG of the IEC + CEA / CBIP set). That is more than the plant's 82.2 Mvar at a power factor of 0.95 (Example 1). The transformers and the line absorb reactive power between the MV buses and the interconnection point. The ANSI / IEEE set rates its static synchronous compensator (STATCOM) at the reactive power of the plant at a power factor of 0.95, . For a plant of 250 MW that is 82.2 Mvar, rounded up to 83 Mvar (Reactive power equipment, The STATCOM of the ANSI / IEEE set).
Given: the default plant of 250 MW at a power factor of 0.95, connected at 220 kV through ICTs from the 33 kV bus.
Angle of the power triangle: , with = 0.329.
Apparent and reactive power by Eq. (4) and Eq. (3):
Currents by Eq. (5):
Result: at a power factor of 0.95 the plant's 250 MW need 263.2 MVA, with 82.2 Mvar of reactive power. The current on the high-voltage (HV) side is 690.6 A, against 656.1 A at a power factor of 1.
- Explain the difference between active and reactive power.
Answer 1
Active power is the average of the instantaneous power and does work; reactive power is exchanged between the source and the fields of the circuit with an average of zero (Instantaneous power).
- Calculate the apparent power of a load of 4 MW and 3 Mvar.
Answer 2
By the power triangle, = 5 MVA (Eq. (3)).
- Find the power factor of that load.
Answer 3
The power factor is = 4/5 = 0.8 (Eq. (4)).
- Calculate the HV current of the default plant at its power factor.
Answer 4
gives 690.6 A at 220 kV for 263.2 MVA (Example 1).
- Explain why a transformer is rated in MVA and not in MW.
Answer 5
The current that heats a transformer follows the apparent power, which includes the reactive power, so the rating states the apparent power (Why reactive power matters to a substation).
[1]MIT 6.061 Notes Ch. 2, 6.061 Introduction to Power Systems, Class Notes Chapter 2: AC Power Flow in Linear Networks. §7, Eq. 65; §7, Eq. 61 to 63; §7, Eq. 63; §7, Eq. 62; §9.
[2]MIT 6.061 Notes Ch. 3, 6.061 Introduction to Power Systems, Class Notes Chapter 3: Polyphase Networks. §8.2, Eq. 55 and 56.
[3]NEETS Module 2, Navy Electricity and Electronics Training Series, Module 2: Introduction to Alternating Current and Transformers.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.