Line protection

An overhead line runs for kilometres through open country, where lightning, wind, birds and vegetation reach its insulation. Its protection must clear a fault on the line fast, from both ends, and must not trip for a fault on the next line or bus. This topic explains distance protection and its zones, the pilot schemes that send signals between the line's ends, and line differential protection. It then explains directional earth fault protection and auto-reclosing, and what the design specifies for the protection of its lines. The zones, selectivity and backup of Principles of protection apply throughout.

Before this topic: Principles of protection · Voltage transformers and CVTs · Symmetrical components

1Faults on a line

A line's insulation is air and its insulator strings. Lightning, birds, branches, wind and polluted insulators bridge it (Faults and fault current, Causes of faults). Many of these faults are transient: the arc clears when the line is opened, and the line can be closed again (Auto-reclosing).

A line's towers are earthed less effectively than a substation, and few earthed objects surround the conductors. A line-to-earth fault on a line can therefore have a high fault resistance, and it draws a limited current (Kasztenny and others §II.A). Such a fault does not threaten the stability of the network. The line runs through public space, however, so the protection must still detect it with adequate sensitivity and speed.

The protection of a line takes its currents from the current transformers (CTs) of the line bay and its voltages from the line's voltage transformer (Voltage transformers and CVTs, Purpose). It trips the breaker at its own end. The protection at the other end trips the remote breaker, and the 2 ends work as one scheme when a channel joins them.

2Distance protection

A distance relay responds to both the voltage and the current at its location. The voltage restrains it, and the fault current operates it, so the relay in effect measures the impedance from its location to the fault (RUS Bulletin 1724E-300 §12.3.4). A line's impedance is proportional to its length. For a fault without resistance, a fault at a fraction of the line's length therefore shows the relay that fraction of the line's impedance, whatever the source and the fault current. Fault resistance and infeed from the remote end change the measured impedance.

The relay operates when the measured impedance falls inside its characteristic on the R-X diagram, a plane of resistance and reactance. The basic characteristic is a circle through the origin, whose diameter is the reach along the line's impedance angle (RUS 1724E-300 §12.3.4). A fault behind the relay lies outside the circle, so the relay is inherently directional.

Distance protection has 3 advantages over overcurrent protection. Its reach is fixed by the line's impedance, regardless of the network's voltage and current. It can operate at fault currents below the load current. It has little transient overreach (RUS 1724E-300 §12.4.2.1.3). It needs a voltage source, the line's voltage transformer, which adds to its cost. The device number of the distance relay is 21 (Principles of protection, Device function numbers).

3The zones of a distance relay

A distance relay has several elements, each with its own reach and time delay, called zones (Figure 1). The step distance scheme uses no channel, and each end trips for the faults within its zones. RUS 1724E-300 §12.4.2.1.3 gives the typical settings:

ZoneTypical reachTypical delayTask
Zone 185 % to 95 % of the line impedancenone intendedTrips at once for faults on most of the line
Zone 2120 % to 150 % of the line impedance18 to 30 cyclesCovers the end of the line not reached by zone 1
Zone 3200 % to 225 % of the line impedance60 to 120 cyclesRemote backup for the next line

Zone 1 stops short of the far end of the line. Set 10 % short of the remote end, it trips for no fault but one on the protected line (RUS 1724E-300 §12.4.6). With the remote end set the same, 80 % of the line is covered at once from both ends. On a short line the reach settings become small, near the limits of the relay, and zone 1 can overreach and trip for a fault on the adjacent line (RUS 1724E-300 §12.4.2.1.3).

Zone 2 reaches beyond the far end of the line into the adjacent lines, without reaching past their far ends. It is delayed, so the protection of the adjacent line clears a fault there first. A fault near one end of the line is cleared in sequence: the near breaker trips in zone 1 and the remote breaker after the zone 2 delay. The zone 2 delay of 18 to 30 cycles is 0.3 s to 0.5 s at the 60 Hz of the RUS bulletin.

Zone 3 reaches through the next line to back up a failure there. Its long reach can encroach on the load impedance and respond to power swings, so it is applied with caution (RUS 1724E-300 §12.4.2.1.3). A zone 3 may instead look in the reverse direction, behind the relay, where a pilot scheme uses it.

Figure 1.The zones of a distance relay at bus A, drawn as their reach along the lines and their operating time. Zone 1 trips with no intended delay, zone 2 and zone 3 after their delays. The drawing is schematic and not to scale.

4Pilot schemes

The step distance scheme clears a fault near either end of the line in the zone 2 time. A pilot scheme removes that delay. It compares the relays' decisions at all the terminals of the line through a communication channel, which may be pilot wires, microwave, optical fibre or power line carrier (RUS 1724E-300 §12.4.2.2). The common schemes are these:

  • Permissive overreaching transfer trip. Each end has an element that reaches beyond the far end. It sends a trip signal, and it trips its own breaker when it also receives the signal from the other end. The scheme is secure, because both ends must detect the fault. A fault could short out a power line carrier signal, so carrier is not recommended for it (RUS 1724E-300 §12.4.2.2.1).
  • Permissive underreaching transfer trip. Zone 1 trips its own breaker and sends a trip signal. The remote end trips on that signal only when its own overreaching element confirms the fault (RUS 1724E-300 §12.4.2.2.1).
  • Directional comparison blocking. Each end has a forward element that reaches past the far end, and a reverse element that starts a blocking signal. A fault beyond one end makes that end block the other. With no blocking signal, both ends trip after a short delay of 6 ms to 16 ms for the channel. The breakers trip without the channel, so the channel's failure can cause an overtrip but not a failure to trip (RUS 1724E-300 §12.4.2.2.1).

The device number of the carrier or pilot-wire relay is 85. Lines at 345 kV normally have 2 primary relay schemes with pilot protection (RUS 1724E-300 §12.4.2). The CEA Connectivity Regulations 2007 require 2 main numerical distance protection schemes on the transmission lines of 220 kV and above, for new substations (CEA Connectivity Regulations 2007, Schedule Part III, 3).

5Line differential protection

Line differential protection applies the differential principle to the line (Principles of protection, The differential principle). Each end measures its currents and sends them to the other ends over a channel. Each end then forms the operate and restraint currents from its own and the remote currents. The principle responds to the currents bounding the zone, so it has high sensitivity to an internal fault and high security for an external fault (Kasztenny and others §I). It is affected little by weak sources, series compensation and power swings, which complicate protection measured at one end. Its device number is 87L.

A line is not a contained piece of apparatus, and its length brings challenges of its own (Kasztenny and others §II):

  • Channel. The relays at the ends exchange their currents over a communication channel. Analogue schemes over pilot wires reach short lines only, and microprocessor relays use digital channels, often optical fibre.
  • Alignment. The relays must compare currents sampled at the same instant. With equal delays in both directions, the relays align the data by measuring the channel's round trip. An unequal delay leaves a phase error that appears as a false operate current, and a common time reference avoids it.
  • Charging current. The line's capacitance draws a charging current that the CTs at the ends do not balance. It appears as an operate current, largest when the line is energised from one end, and the pickup must stay above it.

Line differential protection measures currents only, so it needs no voltage source and no impedance setting. A differential scheme over pilot wires, for example, needs no potential source and does not provide backup protection (RUS 1724E-300 §12.4.2.2.2). The backup of the next element then comes from another function, such as the zones of a distance relay.

6Directional earth fault protection

A line-to-earth fault through a high resistance draws a small current (Faults on a line). Directional earth fault protection is set to detect such a fault. It measures the residual current, 3 times the zero-sequence current, which flows only when the phases are unbalanced to earth (Symmetrical components, How the fault types use the sequences). A balanced load draws no residual current, so the element can be set well below the load current.

A directional overcurrent relay operates only for current flowing in a given direction (RUS 1724E-300 §12.3.9). Its directional element compares the current with a reference quantity, the polarising quantity, to find on which side of the relay the fault lies. Microprocessor relays offer a choice of polarising quantities, among them the residual current or voltage and the negative-sequence current or voltage. A residual-voltage polarised element trips for a fault in front of the relay and not for one behind it. The earth fault relay can serve as a time-delayed backup, or as a fast element in a pilot scheme. The time overcurrent relay connected in the residual circuit of the CTs is 51N, and the directional one 67N (Principles of protection, Device function numbers).

7Auto-reclosing

Most faults on open-wire overhead lines are transient, caused for example by lightning, and they clear when the circuit is disconnected from its source (RUS 1724E-300 §12.4.5.1). Service is restored by closing the breaker again. An automatic reclosing relay, device 79, recloses the breaker one or more times after the protection has tripped it (RUS 1724E-300 §12.4.5.2). Reclosing is generally not applied where permanent faults are more likely, such as on cables.

The interval between the opening of the breaker and its reclosing is the dead time. It gives a transient fault the time to clear while the line is disconnected. A single-shot relay recloses once, and a multi-shot relay recloses several times. Reclosing may be done when the line is dead, or when the voltages on both sides of the breaker are in synchronism. A synchronism check compares the voltage and the phase angle across the breaker before it closes (RUS 1724E-300 §12.1.3.12). After a set number of unsuccessful reclosures, the breaker is locked open.

The line can be opened and reclosed in all 3 phases or in the faulted phase only. In single-pole reclosing, the healthy phases feed a secondary arc at the fault through their capacitance, and that arc must die out before the phase recloses (Shunt and series reactors, The neutral reactor and single-pole reclosing). Opening one phase alone needs a breaker with independent-pole operation, in which each pole has its own means to trip (Circuit breakers, Operating mechanisms). Reclosing sets the breaker's rated operating sequence, O – 0.3 s – CO – 3 min – CO for rapid auto-reclosing in the IEC sequence (Circuit breakers, Ratings).

8In the design

SubstationLayout sets no line protection: no reach, delay, scheme or reclosing. For the default project, of the IEC + CEA / CBIP set, it specifies the parts that the line's protection uses and the lines' data that a setting study starts from.

Instrument transformers. The line bay has a capacitor voltage transformer (CVT) at the line's entry and the CTs between the circuit breaker and the line isolator (disconnector, IEC 60050) (Bays and their equipment, Line bay). The CT has 5 cores, 0.2S, 0.2S, 5P20, 5P20, PS. The 2 class 5P20 cores and the class PS core serve the protection (Current transformers, In the design). The CVT's protection secondary is the class 3P secondary of 0.2, 3P, open delta (Voltage transformers and CVTs, In the design).

Channel. In this project of the IEC + CEA / CBIP set, the single-line diagram (SLD) draws a line trap on 2 phases of the 220 kV line, for power line carrier communication (PLCC) coupled through the CVTs. One of its notes states that the optical fibres of the line's earth wire carry the wideband communication (PLCC and fibre communication, In the design).

Line data. The short-circuit study models the default project's line as 10 km of Twin ACSR Moose. Its positive-sequence impedance is 0.21 Ω of resistance and 2.82 Ω of reactance. A distance relay's reaches are set as percentages of this impedance in the protection setting study.

Compliance checklist. The CEA / Indian checklist's Protection item covers line, interconnecting transformer (ICT) and bus protection per the grid code, with duplicated main protection at 220 kV. The item reads Needs your answer until the user answers it (Principles of protection, In the design).

Reclosing duty. The design does not choose the breakers' operating sequence (Circuit breakers, In the design). Where the project has line reactors, at 765 kV only, the bill of materials earths each line reactor's neutral through a neutral reactor, which suits single-pole auto-reclosing (Shunt and series reactors, The neutral reactor and single-pole reclosing).

Review questions
  1. Explain why a distance relay is selective without a current setting.
    Answer 1

    It measures the impedance from its location to the fault, which is proportional to the distance along the line, so its reach is fixed by the line's impedance (Distance protection).

  2. Give the reason zone 1 is set short of the far end of the line.
    Answer 2

    Set short of the remote end, zone 1 trips for no fault but one on the protected line, and the delayed zone 2 covers the rest (The zones of a distance relay).

  3. State the typical reach and delay of zone 2.
    Answer 3

    Zone 2 reaches 120 % to 150 % of the line impedance, with a delay of 18 to 30 cycles (The zones of a distance relay).

  4. Compare a permissive overreaching scheme with a directional comparison blocking scheme.
    Answer 4

    The permissive scheme trips when both ends detect the fault and needs the signal to trip, and the blocking scheme trips unless a blocking signal arrives, so a channel failure can cause an overtrip (Pilot schemes).

  5. Name the challenges of line differential protection that come from the line's length.
    Answer 5

    The channel between the ends, the alignment of the currents sampled at the ends and the line's charging current (Line differential protection).

  6. Explain why auto-reclosing is applied on overhead lines and not on cables.
    Answer 6

    Most overhead line faults are transient and clear when the line is opened, while faults on cables are more likely permanent (Auto-reclosing).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[2]CEA Connectivity Regulations 2007, Central Electricity Authority (Technical Standards for Connectivity to the Grid) Regulations, 2007.

[3]Kasztenny and others, Tutorial on Operating Characteristics of Microprocessor-Based Multiterminal Line Current Differential Relays.

[4]IEEE C37.2-1996, Standard Electrical Power System Device Function Numbers.

[5]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Line protection, revision 4, 9 Nov 2026, https://substation.solarlayout.app/library/reference/line-protection