Three-phase systems

A three-phase system carries power on 3 circuits whose voltages are equal sine waves, shifted in time by a third of a cycle. Generators, lines, transformers and substations are built for it. This topic explains why 3 phases are used, how the phases follow each other, and how windings and loads connect in star or in delta. It derives the factor between the phase and the line quantities, and closes on the neutral and the balanced load.

Before this topic: Voltage, current and impedance in AC circuits

1Why power systems are three-phase

Three-phase circuits use their conductors economically: in a balanced set the neutral carries no current and can be small or left out (Balanced loads and the neutral). A balanced three-phase set also delivers a constant power, where a single phase delivers a power that pulses at twice the frequency. These 2 reasons, the economical use of conductors and the constant power of a balanced set, explain why most power systems use 3 phases.

The power of one phase pulses because its voltage and current pass through zero twice in each cycle. The pulses of the 3 phases are shifted by a third of a cycle, and their sum is constant. A constant power suits generators and motors, which convert it to and from a mechanical torque.

2Phase sequence

The 3 voltages of a balanced set have the same root-mean-square value (RMS) and the same frequency. They are shifted from each other by 120°, a third of a cycle:

(1)
MIT 6.061 Notes Ch. 3 §3, Eq. 9 to 11

The phase sequence is the order in which the phases reach their peaks: a, then b, then c. As phasors, the 3 arrows are 120° apart and turn counterclockwise together (Figure 1). A transformer's terminals are marked in the same order, for example 1U, 1V and 1W on the high-voltage side.

The sum of the 3 voltages of a balanced set is zero at each instant. For the phasors, the 3 arrows placed head to tail close a triangle. The same holds for the 3 currents of a balanced load.

where
, , voltages of the phases a, b and c to the neutralV
peak value of a phase voltageV
angular frequency, rad/s
Figure 1.The phase voltages of a balanced set are 120° apart. The line voltage between phases a and b is the difference of their phase voltages, times as long and 30° ahead of . The drawing is schematic and not to scale.

3Star and delta connections

The 3 windings of a source, a load or a transformer side connect in one of 2 ways (Figure 2). In a star connection, also called wye (Y), one end of each winding joins a common point, the neutral point. The other ends connect to the 3 lines. In a delta connection (D or Δ), the windings join end to end in a closed ring, and the lines connect to the corners.

A star connection has 4 terminals, the 3 lines and the neutral. A delta connection has 3, with no neutral point. Under balanced conditions the difference does not matter. It matters when the currents are unbalanced, as during an earth fault, because a star has a neutral point that can be earthed. A delta side has none of its own. Where it must be earthed, a separate earthing transformer, connected in zigzag or in star-delta, provides the neutral.

Figure 2.A star connection has its windings between the lines and the neutral point N. A delta connection has its windings between the lines. The drawing is schematic and not to scale.

4Phase and line quantities

The phase voltage of a star is the voltage of one line to the neutral, across one winding. The line voltage is the voltage between 2 lines. It is the difference of 2 phase voltages, and its magnitude is times the phase voltage:

(2)
MIT 6.061 Notes Ch. 3 §4, Eq. 24 to 26

The line voltages also form a balanced three-phase set. They lead the phase voltages by 30°, as Figure 1 shows. A system's nominal voltage, such as 220 kV, is its line voltage. In a star, the line current flows through one winding, so the winding current equals the line current.

In a delta, the voltage across one winding is the line voltage. The current of a line is the difference of the currents of the 2 windings that meet at its corner. In a balanced delta, the line current is therefore times the winding current, . A balanced delta of impedances draws the same line currents as a balanced star of .

The rating of three-phase equipment, in volt-amperes, is the phase voltage times the current, taken for the 3 phases: . With the line voltage and the line current, the same form holds for a star and for a delta (Active, reactive and apparent power, Three-phase power).

where
line voltage, between 2 lines (RMS)V
phase voltage, of a line to the neutral (RMS)V
line current (RMS)A
winding current of a delta (RMS)A
impedance of one branch of a deltaΩ
rating of the three-phase equipmentVA

5Balanced loads and the neutral

A balanced load has the same impedance in the 3 phases. Its 3 currents have equal magnitudes and are 120° apart, so their sum is zero. The neutral conductor of a balanced star therefore carries no current, and many three-phase circuits run without one.

When the impedances differ, the load is unbalanced. In a star whose neutral is connected to the source, a current flows in the neutral. In a star without that connection, the load's star point moves away from the potential of the source's neutral, and the 3 phase voltages at the load differ even when the source is balanced. An earth fault unbalances the currents, and the way the neutral is connected to earth then sets the fault current (Earthing of the neutral).

An unbalanced set of currents is calculated as the sum of balanced sets, the method of symmetrical components (Symmetrical components, Balanced sequence systems).

6In the design

The design states its bus voltages as line voltages, 220 kV and 33 kV for the default project. The phase voltages are 127.0 kV and 19.05 kV. The single-line diagram (SLD) draws one line for the 3 phases of a circuit (Single-line diagram (SLD)).

The default interconnecting transformer (ICT) has the vector group YNyn0, whose letters Transformer principles, Vector groups explains. YN marks its high-voltage (HV) winding as a star with the neutral brought out to a terminal. Its medium-voltage (MV) winding, marked yn, is a star with its neutral brought out too. The default ICT has no third winding. A transformer with a delta tertiary adds the letter d to its group (Power transformers, Vector groups and neutral earthing). The design earths the HV neutral solidly and the MV neutral through a neutral earthing resistor (Earthing of the neutral, The design's transformer neutrals).

At its rating of 160 MVA, one ICT carries 419.9 A in each HV line and 2799 A in each MV line. Each phase carries a third of the rating, 53.3 MVA.

Example 1Winding current of a delta high-voltage winding

Given: a 33 kV / 11 kV project with the defaults of the 33 kV voltage level, with transformers of 6.3 MVA, vector group Dyn11. The HV winding is a delta and the low-voltage winding a star.

Line current on the HV side at the rating, from the rating (Phase and line quantities):

Winding current of the delta, the line current over :

Phase voltage of the star side, by Eq. (2):

Result: each HV winding carries 63.6 A at the full line voltage of 33 kV, while each HV line carries 110.2 A. Each low-voltage winding has 6.35 kV across it.

Review questions
  1. Give the reasons for using a three-phase system.
    Answer 1

    A three-phase system uses its conductors economically, and a balanced set delivers a constant power (Why power systems are three-phase).

  2. Calculate the phase voltage of the default 220 kV bus.
    Answer 2

    The phase voltage is the line voltage over , 127.0 kV (Eq. (2), In the design).

  3. Explain why a delta connection has no neutral point.
    Answer 3

    A delta joins its windings end to end in a closed ring with the lines at the corners, so it has 3 terminals and no common point (Star and delta connections).

  4. Find the winding current of a balanced delta whose line current is .
    Answer 4

    The winding current is , since a line current is the difference of the currents of 2 windings (Phase and line quantities, Example 1).

  5. State the current in the neutral of a balanced star load.
    Answer 5

    The 3 currents are equal and 120° apart, so their sum and the neutral current are zero (Balanced loads and the neutral).

Sources

[1]MIT 6.061 Notes Ch. 3, 6.061 Introduction to Power Systems, Class Notes Chapter 3: Polyphase Networks. §3, Eq. 9 to 11; §4, Eq. 24 to 26.

[2]Noratel, Technical information: The three-phase transformer.

[3]Solectria white paper on effective grounding, Effective Grounding for PV Plants.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.