Busbars and conductors
The buses and conductors of a switchyard carry the load current between the lines, the transformers and the switching devices. A bus is either rigid, a tube held on post insulators, or strung, a stranded conductor pulled between insulator strings on gantries. Shorter conductors connect the buses to the equipment of each bay. This topic explains the materials and shapes of these conductors, how they are supported, what limits their current and their diameter, and the fittings that join them. It closes with the tubes and the line conductors the design specifies.
Before this topic: Bays and their equipment · Three-phase systems
1Buses and connections in a switchyard
A bay connects a circuit to the main buses through its switching devices and instrument transformers (Bays and their equipment). The main buses run along the yard and carry the sum of the currents of the bays connected to them. Each bay has its own connections: from the bus to the first isolator (disconnector, IEC 60050), from device to device along the bay, and from the last device to the line or the transformer. A connection from a bus down to the equipment below it is a tap. The design's 3D model calls these taps droppers.
Conductors of 2 families serve these purposes. A rigid conductor is a bar, a shape or a tube that keeps its form between supports. A flexible conductor is a cable stranded from many small wires. RUS Bulletin 1724E-300 describes both and the bus systems built from them (§4.10). The choice affects the structures, the clearances and the space the yard needs, as the next sections show.
2Conductor materials
Copper and aluminium are the materials of substation buses and equipment connections. The trend in construction is towards aluminium, and copper is used mainly to extend existing copper systems (RUS 1724E-300 §4.10.1). The conductivity of aluminium is 50 % to 60 % of that of copper, depending on the alloy. An aluminium conductor therefore needs a larger cross-section for the same current. Its larger diameter adds to the wind and ice loads, but it lowers the corona at higher voltages. For the same current, a copper conductor weighs approximately twice as much as an aluminium one.
Aluminium is used as pure aluminium wire, as alloys, and with a core of steel for strength. Rigid round tubes are usually specified in alloy 6061-T6 or 6063-T6. The 6063-T6 alloy has a conductivity approximately 23 % higher than 6061-T6, and its minimum yield strength is 29 % lower. It can therefore carry more current but may need shorter spans between supports (RUS 1724E-300 §4.10.2.5). Alloy 6101-T6 is also among the alloys and tempers generally used for bus conductors, as extruded rod, bar, tube and pipe. A manufacturer's data give it the minimum yield strength of 6063-T6 (AFL, Mechanical properties of aluminum bus conductors).
3Rigid buses
A rigid bus is a conductor that spans from one support to the next without a tension in its length. Flat bars and structural shapes such as angles and channels are used mainly at lower voltages, because of corona. Round tubes are the shape most used in outdoor substations. They are stiffer than bars or angles of the same current rating, so they span further. Their round surface is efficient structurally and electrically and keeps corona low at higher voltages (RUS 1724E-300 §4.10.2.3).
Tubes are made as aluminium pipe in standard sizes. A size is named by its nominal pipe size in inches, the iron pipe size (IPS), with a schedule that sets the wall thickness. RUS 1724E-300 lists the properties of Schedule 40 aluminium pipe from ½ inch to 6 inches: its diameters, area, weight, moment of inertia and section modulus (Table 4-14). The outside diameter of a size does not equal its nominal size: a 4 inch pipe measures 4.5 inches, 114.3 mm, outside.
Figure 1 shows a tubular bus in elevation. The tube rests on bus post insulators, each on a steel support structure (Insulators and bushings, Post insulators). The distance between supports is the span.
Span and deflection. The span is limited by the stress in the tube and by its sag between supports. The loads are the tube's own weight, ice, wind and the forces of a short circuit. RUS 1724E-300 gives a procedure: choose the tube for the continuous current, set the phase spacing from the clearance tables, add the loads, then find the longest span and the deflection (§4.11.2). In its example, a 3 inch Schedule 40 tube of 6063-T6 for 1800 A at 161 kV is first laid out on spans of 11.43 m. Its deflection of 10.1 cm exceeds the limit of 5.72 cm, 1/200 of the span, so the bus is laid out on spans of 9.14 m (RUS 1724E-300 §4.11.3.6).
Thermal expansion. A tube lengthens as it warms. Its change of length follows
| change of length of the conductor | m | |
| coefficient of linear thermal expansion, per °C for aluminium and per °C for copper | 1/°C | |
| initial length of the conductor | m | |
| change of temperature | °C |
A 30 m length of aluminium tube that warms by 50 °C grows by m, that is 34.5 mm. A bus fixed at both ends would push that length into its insulators and the equipment terminals. The bus is therefore divided into sections, each with one fixed support and slip supports that let the tube slide. Expansion couplers or expansion terminals take up the movement. RUS 1724E-300 recommends sections of 30.48 m (100 feet) or less. It connects circuit breakers, transformers and voltage transformers through flexible conductors or expansion connectors, so the movement does not reach their bushings (RUS 1724E-300 §4.11.2.8).
Couplers. Tubes are supplied in lengths of 3.05 m to 12.2 m and are joined by couplers (RUS 1724E-300 §4.10.5.1). A weld or a clamp weakens the tube locally. Couplers are therefore placed where the bending moment is smallest, at points of the span that RUS 1724E-300 tabulates for continuous spans (§4.11.2.9).
Wind vibration. A steady, low-speed wind across a tube makes it vibrate. When the frequency of the wind's force is close to the natural frequency of the span, the span resonates and the vibration can damage the insulators. This is aeolian vibration. RUS 1724E-300 advises damping for spans longer than approximately 6 m (§4.11.2.10). The usual method is a length of scrap cable laid loose inside the tube, held in by end caps. The other method is a prefabricated damper fitted in each span.
4Strung buses and flexible conductors
A strung bus, which RUS 1724E-300 calls a strain bus, is a flexible conductor held in tension between suspension insulator strings on gantries (Insulators and bushings, Suspension insulators). It needs large supporting structures, and it moves with temperature, wind and ice. The clearances of Table 4-7 of the bulletin are for rigid conductors. For flexible conductors, the bulletin raises the phase-to-phase, phase-to-earth and ground clearances by at least 50 % (RUS 1724E-300 §4.9). The conductors are usually strung at a tension of approximately 13.35 kN or less, to limit the size of the structures and the risk of a break above the equipment (RUS 1724E-300 §4.12.1.7). Taps from a strung bus are left slack, so their tension does not load the equipment (RUS 1724E-300 §4.12.1.9).
Flexible conductors are stranded in concentric layers of wires. Most are all copper, all aluminium or aluminium conductor steel-reinforced (ACSR) (RUS 1724E-300 §4.10.3). An ACSR conductor has a core of galvanised steel wires and one or more layers of hard-drawn aluminium wires around it (Figure 2). The steel core reinforces the conductor. IS 398 (Part 2):1996 counts both the aluminium and the steel wires in the breaking load, and the aluminium wires alone in the resistance (Annex A). An all-aluminium alloy conductor (AAAC) is stranded from aluminium alloy wires alone, with no steel core. The planning data of the Central Electricity Authority (CEA) list AAAC equivalents of the ACSR sizes, at 53.0 % of the conductivity of annealed copper (CEA Manual on Transmission Planning Criteria 2023, Annexure II, Table I(f)).
ACSR sizes are known by code names, such as the animal names of the conductors in the table. Each name stands for one stranding and size. The table gives the stranding as the number and diameter of the aluminium wires and of the steel wires.
| Code name | Aluminium wires | Steel wires | Overall diameter | Direct-current resistance at 20 °C |
|---|---|---|---|---|
| Dog | 6 × 4.72 mm | 7 × 1.57 mm | 14.15 mm | 0.2792 Ω/km |
| Panther | 30 × 3.00 mm | 7 × 3.00 mm | 21.00 mm | 0.1390 Ω/km |
| Zebra | 54 × 3.18 mm | 7 × 3.18 mm | 28.62 mm | 0.06868 Ω/km |
| Moose | 54 × 3.53 mm | 7 × 3.53 mm | 31.77 mm | 0.05552 Ω/km |
| Bersimis | 42 × 4.57 mm | 7 × 2.54 mm | 35.04 mm | 0.04242 Ω/km |
The values of Zebra, Moose, Bersimis and Panther are those of the CEA's planning data (Annexure II, Tables I(b) to I(e)). Those of Dog are from IS 398 (Part 2):1996 and a manufacturer's catalogue of IS 398 conductors.
Bundled conductors. At the higher voltages one phase is carried on 2 or more subconductors in parallel, a bundle. Spacers, often spacer dampers, keep the subconductors apart and stop them from clashing (NPTEL, Power System Analysis, Chapter 1). The CEA's planning data gives standard line parameters per configuration (Annexure II, Table I(a)). Its lines are single Dog at 66 kV and single Panther at 132 kV. At 220 kV they are single or twin Zebra and Moose, and at 400 kV bundles of 2 to 4 subconductors, among them twin and quad Moose. At 765 kV they are quad Bersimis or 6 Zebra subconductors. The next section explains why the extra-high-voltage phases are bundled.
5Corona and the conductor diameter
Corona is a partial discharge in the air at the surface of a conductor. It starts where the electric field at the surface, the surface voltage gradient, exceeds the dielectric strength of the air, which then ionises. Corona wastes power, interferes with radio and communication circuits, makes a hissing noise and produces ozone (NPTEL, Power System Analysis, Chapter 1). RUS 1724E-300 calls corona a localised, incomplete dielectric failure (§2.3.1.4).
Corona is strongest on small radii. RUS 1724E-300 names small-diameter conductors and energised parts of small radius as its causes, and larger diameters tend to minimise it (§2.3.1.5, §4.10.1). A conductor sized only for its current can therefore be too thin for its voltage. RUS 1724E-300 therefore sets minimum conductor sizes against corona, from 138 kV upwards, for connections to voltage transformers and coupling capacitors, whose currents are small. At 345 kV the equipment jumpers are bundled conductors (RUS 1724E-300 §2.3.1.5). Conductor fittings and other energised parts seldom cause serious corona at 230 kV and below. At 345 kV the bulletin calls for corona shields and connectors designed to limit corona (RUS 1724E-300 §2.3.1.5).
A bundle of 2 or more subconductors per phase, close together, lowers the surface gradient considerably (NPTEL, Power System Analysis, Chapter 1). This is why the extra-high-voltage lines of Strung buses and flexible conductors use twin, quad and larger bundles. Specifications for these conductors require a test of the visible corona extinction voltage and a test of the radio interference voltage on a sample (BHEL specification for ACSR conductors, Annexure C).
The corona of this section is the steady discharge at the operating voltage. The corona radius of the rolling sphere method is a different quantity: the envelope that forms around a conductor under a lightning surge (Direct stroke shielding by the rolling sphere, Eq. (1)).
6Clamps, connectors and fittings
Bus sections are joined, tapped and terminated by 4 methods: bolting, clamping, compression and welding (RUS 1724E-300 §4.10.5.1). A connector must be equivalent to the conductor itself, electrically and mechanically. In the ANSI / IEEE practice of RUS 1724E-300, substation connectors are designed and tested to NEMA CC1 (§4.10.5.1).
Bolted connections join flat surfaces, and they are the usual connection to an equipment terminal, since they let the equipment be removed. A terminal lug is clamped, compressed or welded to the conductor and bolted to the terminal. Where aluminium meets copper, the copper part is placed below the aluminium, so that copper salts do not wash onto the aluminium.
Clamp-type connectors hold the conductor by a number of bolts. Copper or bronze connectors are used on copper, and all-aluminium connectors on aluminium.
Compression connectors splice flexible conductors and fit terminal lugs to them, and they are also made for round tubes. A hydraulic tool compresses the fitting around the conductor, and a gauge checks the result.
Welded connections are used mainly on round aluminium tubes. A properly made weld has a resistance close to that of the conductor, so it does not form a hot spot. Large substations use them widely.
Other fittings serve the mechanics of the bus: expansion couplers and expansion terminals (Rigid buses), end caps and dampers, the spacers of a bundle, and the clamps that hold a tube on its post insulator.
7Current rating
The continuous current rating of a bare conductor, its ampacity, is the current at which its temperature reaches the chosen limit in the assumed weather. In the steady state, the heat the current generates in the conductor's resistance, with the heat of the sun, equals the heat the conductor loses by convection to the air and by radiation:
| current in the conductor, root-mean-square value | A | |
| alternating-current resistance of the conductor per unit length at the conductor temperature | Ω/m | |
| heat gained from the sun per unit length | W/m | |
| heat lost by convection per unit length | W/m | |
| heat lost by radiation per unit length | W/m |
The equation is the heat balance of IEEE Std 738, as a study of the Idaho National Laboratory applies it to transmission lines. Solved for , it gives the rating at the limiting temperature. The convective loss rises with the wind speed and with a wind square to the conductor. The radiative and solar terms depend on the surface's emissivity and absorptivity.
RUS 1724E-300 lists the factors for bus conductors: the material, the spacing of the conductors, the climate, the temperature rise, the emissivity and the altitude (§4.10.4). Ratings are usually for an ambient temperature of 40 °C. The rise is usually limited to 30 °C, a total of 70 °C, to prevent oxidation of the surface and annealing. The emissivity of weathered aluminium is taken as 0.5 and that of copper as 0.8. Above 1000 m the air cools a conductor less, and the bulletin reduces the rating by a factor from its Table 4-10. Closely spaced conductors share current unevenly, but the extra losses can usually be neglected at a spacing of 45.7 cm or more.
The design takes the rated currents of the buses and bays per level (Bus and bay current ratings, HV buses and bays). It calculates the ampacity of the main-bus tube and sizes the tube to the main bus's rated current (In the design). The terms of the heat balance and the rating of a tube are explained in Ampacity of conductors. The forces between the phases during a short circuit load the tube, the insulators and the structures, as Short-circuit forces on busbars explains.
8In the design
The design specifies the high-voltage (HV) main buses of an air-insulated yard as rigid aluminium tubes on bus post insulators, with one tube per phase of each bus. The level table gives each level a typical tube size, the smallest the main bus takes. The design takes the smallest tube of its standards set's table, from that size up, whose ampacity meets the main bus's rated current (Ampacity of conductors, In the design). The table of the IEC + CEA / CBIP set holds the tubes of the POWERGRID switchyard erection specification, in alloy 6101-T6. The ANSI / IEEE set's tubes are in alloy 6063-T6, the alloy of RUS 1724E-300's rating example (§4.11.3.1), of 53 % IACS conductivity (Snohomish County PUD, S0301-3). The bill of materials (BOM), the 3D model and the lightning protection step use the tube the design takes. The tube a new project takes at each level of the IEC + CEA / CBIP set, at the default maximum ambient temperature, is in the table. At 765 kV it is the tube of a 765/400 kV switching substation. The table adds the main bus's rated current and the line conductor a new project takes.
| Level | Main-bus tube | Outside diameter | Bus rated current | Line conductor of a new project |
|---|---|---|---|---|
| 33 kV | 3" IPS EH | 88.9 mm | 1250 A | ACSR Panther |
| 66 kV | 3" IPS EH | 88.9 mm | 1250 A | ACSR Dog |
| 132 kV | 3" IPS EH | 88.9 mm | 2000 A | ACSR Panther |
| 220 kV | 4.5" IPS EH | 120.0 mm | 3150 A | Twin ACSR Moose |
| 400 kV | 6" IPS H | 150.0 mm | 4000 A | Quad ACSR Moose (400 kV) |
| 765 kV | 8" IPS H | 202.0 mm | 4000 A | Quad ACSR Bersimis (765 kV) |
Tube. The default 220 kV project has a double main bus, so its yard has 6 tubes of 72.0 m. The BOM line "Aluminium tube, 4.5" IPS EH (OD 120 mm, wall 12 mm)" specifies AA 6101-T6, rated 3804 A at 50 °C ambient for the 3150 A bus, main bus and interconnection. Its quantity is 916 m, for 6 × 72 m bus + 484 m bay interconnection, with 46 m of spares, 5 % of the quantity. The bay interconnection in the BOM is tube as well. In the ANSI / IEEE set the tube is a Schedule 40 size of RUS 1724E-300 Table 4-14: a new 230 kV project's BOM lists "Aluminum tube, 6" IPS Schedule 40 (OD 6.63 in, wall 0.28 in)".
Supports. The design places a bus post insulator at each end of a tube and at spans of at most 9 m. A tube of 72.0 m has 9 of them, and the default yard 54 (Insulators and bushings, In the design). Each stands on a "Bus post insulator support", galvanised, 6.7 m. The BOM's line "Clamps, connectors and spacers" is one lot, to suit tube and equipment terminals.
Strung jumpers. A one-and-a-half breaker or ring bus yard carries strung jumpers from its bays over the main buses, on jumper gantries. A new 400 kV project, with a one-and-a-half breaker scheme, has them at 18.0 m, above its buses at 13.0 m.
Line conductor. The input Conductor, in the Line section of the HV switchyard page, names the conductor of the HV lines from the design's library: Twin ACSR Moose, ACSR Zebra, Quad ACSR Moose (400 kV), ACSR Panther, ACSR Dog, Quad ACSR Bersimis (765 kV). Choosing a level sets that level's conductor. From 66 kV to 765 kV these are configurations of the CEA's planning data (Strung buses and flexible conductors). The design uses it for the line's impedance in the short-circuit study (Short-circuit currents by IEC 60909-0, The impedances of the network). The default project's Twin ACSR Moose line has a positive-sequence impedance of 0.021 Ω/km and 0.28 Ω/km. In the ANSI / IEEE set, a new 230 kV project takes Twin ACSR Moose, a configuration from the same library, which is the design's choice for that set.
Lightning protection. The rolling sphere step uses the radius of the conductor at each protected level (Direct stroke shielding by the rolling sphere, Eq. (2)). It takes the tube's radius, 60.00 mm at 220 kV, for the bus level at 9.0 m. It takes the radius of ACSR Moose, 15.9 mm, for the equipment level and the transformer bushing tops.
Apart from the main-bus tube's ampacity, the design calculates no ampacity of a conductor. It calculates no corona gradient, span, deflection, sag, thermal expansion or short-circuit force of a conductor, and its BOM has no line for strung conductors.
- Compare a rigid bus and a strung bus.
Answer 1
A rigid bus is a tube that spans between post insulators without tension, while a strung bus is a stranded conductor in tension between insulator strings, which spans further but moves and needs larger clearances and structures (Rigid buses, Strung buses and flexible conductors).
- Calculate the growth of a 30 m aluminium tube that warms by 50 °C.
Answer 2
By Eq. (1) it grows by m, which expansion couplers, slip supports and flexible connections take up (Rigid buses).
- Describe the construction of an ACSR conductor.
Answer 3
It has a core of galvanised steel wires that reinforces layers of hard-drawn aluminium wires, and its resistance is that of the aluminium wires alone (Strung buses and flexible conductors, the table).
- Explain why phases at extra-high voltage are carried on bundles.
Answer 4
Corona starts where the surface gradient exceeds the strength of the air, and 2 or more subconductors per phase lower that gradient considerably (Corona and the conductor diameter).
- State the heat balance of a bare conductor.
Answer 5
The heat of the current in the resistance and of the sun equals the convective and radiative losses, (Eq. (2)).
- Name the main-bus tube of the default project and its BOM line.
Answer 6
The BOM line "Aluminium tube, 4.5" IPS EH (OD 120 mm, wall 12 mm)" specifies AA 6101-T6, rated 3804 A at 50 °C ambient for the 3150 A bus, main bus and interconnection, with a quantity of 916 m (In the design).
[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations. §4.11.2.8, Eq. 4-11.
[2]CEA Manual on Transmission Planning Criteria 2023, Manual on Transmission Planning Criteria.
[3]BHEL specification TB-XXX-316-019, Technical Specification for ACSR (Moose / Bersimis / Zebra) & AAC (Bull) Conductor.
[4]Apar ACSR catalogue, All Aluminium Conductor Steel Reinforced (ACSR).
[5]IS 398 (Part 2):1996, IS 398 (Part 2): 1996, Aluminium conductors for overhead transmission purposes, Part 2: Aluminium conductors, galvanized steel reinforced.
[6]NPTEL, Power System Analysis, Chapter 1, Power System Analysis.
[7]Abboud and others 2018, Using Computational Fluid Dynamics to Assess Dynamic Line Ratings in Southern Idaho. Eq. 6.
[8]IEEE Std 738, IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors.
[9]AFL, Mechanical properties of aluminum bus conductors, Mechanical Properties of Aluminum Bus Conductors.
[10]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.
[11]Snohomish County PUD, S0301-3, S0301-3 Aluminum Bus Conductor.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.