Structures and foundations

The structures of an outdoor switchyard hold the conductors and the equipment at the heights and spacings the clearances require. Line gantries carry the incoming lines and the strung buses, and equipment support structures carry the breakers, the switches, the instrument transformers, the surge arresters and the bus insulators. Each structure stands on a foundation that passes its loads into the soil. This topic explains the loads on a structure, the members and finishes of steel structures, and the types of foundation. It then states what the design specifies and counts.

Before this topic: Yard layout · Busbars and conductors · Site, survey and environmental considerations

1Structures of a switchyard

RUS Bulletin 1724E-300 names 3 functional types of substation structure: line support structures, equipment support structures and the column-and-beam structure of a distribution substation (§7.2). This topic treats the first 2, which make up an outdoor switchyard. Line support structures terminate the incoming and outgoing lines and hold strung buses. They consist of 2 towers and a crossarm, the beam, from which the conductors hang, as single-bay or multibay structures (RUS 1724E-300 §7.2.1). In the IEC + CEA / CBIP set's word, such a structure is a gantry. The conductors and the shield wires pull on it, so it is usually highly stressed and needs the most design effort (RUS 1724E-300 §7.2.1).

Equipment support structures carry one item each: a bus support, a switch stand, a surge arrester stand or a line trap support (RUS 1724E-300 §7.2.2). In a low-profile yard they act as vertical cantilevers, with wind and short-circuit forces as their main design forces. Figure 1 shows both types and their loads. An isolator (disconnector, IEC 60050) support carries a moving blade. RUS 1724E-300 specifies switch stands more rigid than bus supports, because the blade must return to its narrow saddle when it closes (§7.2.2).

Figure 1.A line gantry and an equipment support with the loads on them. The conductor tension and the wind act on the gantry, and the wind, the short-circuit force and the dead load act on the support. Both pass their loads through anchor bolts into concrete foundations. The drawing is schematic and not to scale.

2Loads on a structure

A structure is designed for the most critical combination of its loads. The loads are of 6 kinds, and each set's documents describe them:

  1. Conductor tension. A line or strung bus pulls on the gantry's beam. The substation engineer specifies the tension that gives the maximum load on the structure, under the most severe combination of temperature, wind and ice (RUS 1724E-300 §2.4.1). The line support structure is designed for the wires at right angles to the crossarm and for wires deviating by 15° from it (RUS 1724E-300 §7.4.2). The tensions of the strung conductors are in Busbars and conductors, Strung buses and flexible conductors.
  2. Short-circuit forces. A fault current drives the phase conductors apart and loads their supports (Short-circuit forces on busbars, Load on the supports).
  3. Wind. The wind presses on the members, the insulators, the equipment and the conductors (Wind load).
  4. Ice. Ice adds weight and enlarges the area the wind acts on.
  5. Seismic. An earthquake accelerates the masses on the structure (Seismic load).
  6. Dead, operating and construction loads. These are the weight of the structure and its equipment, the dynamic loads of switching, and the loads of hoisting and pulling equipment into place (RUS 1724E-300 §7.4.5, §7.4.9).

RUS 1724E-300 designs the equipment stands for the applicable wind, ice, short-circuit, dead and dynamic operating loads. In its experience, wind plus short-circuit forces usually produce the maximum stresses, and ice is usually not the controlling load (RUS 1724E-300 §7.4.5). The bus supports are also designed for the combination of extreme wind and short-circuit loads, a check of stress that does not consider deflection (RUS 1724E-300 §7.4.10). Seismic loads are not usually combined with ice and wind loads (RUS 1724E-300 §7.4.7).

The ANSI / IEEE set multiplies each load of a line support structure by an overload factor. For the National Electrical Safety Code (NESC) loading districts, RUS 1724E-300 gives 1.65 on the wire pull, 2.50 on the wind and 1.50 on the vertical load, for metal and prestressed concrete structures (§7.4.2). Its high-wind, heavy-ice and seismic cases take 1.3. The IEC + CEA / CBIP set applies its factors to the foundations (Foundations in the IEC + CEA / CBIP set). The service conditions of the CEA standard specification for transformers and reactors list the seismic zone, with its ground acceleration, and the wind zone, and name no ice load (Ch. 2 §10.0).

3Wind load

The wind load is the design wind pressure times the area exposed to the wind. In the IEC + CEA / CBIP set it follows IS 875 (Part 3):1987. The basic wind speed is read from the standard's wind map of India for the site (IS 875 (Part 3):1987 §5.2). It is a peak gust averaged over approximately 3 s, at 10 m above ground in open terrain, with a 50-year return period. The design wind speed at a height modifies it for the risk, the terrain and the topography (IS 875 (Part 3):1987 §5.3):

(1)
IS 875 (Part 3):1987 §5.3

The design wind pressure follows from the design wind speed (IS 875 (Part 3):1987 §5.4):

(2)
IS 875 (Part 3):1987 §5.4
where
design wind speed at height m/s
basic wind speed of the site, from the standard's wind mapm/s
probability factor, the risk coefficient for the structure's class and design life
terrain, height and structure size factor
topography factor
design wind pressure at height N/m²

The coefficient 0.6 is in SI units. IS 875 chose it for the average atmospheric pressure and air temperature of Indian conditions (§5.4). The pressure grows with the square of the speed, so a site 10 % windier carries 21 % more wind load. The standard takes the design wind speed as constant up to 10 m above the mean ground level, and the factor varies it with height above that (IS 875 (Part 3):1987 §5.3, §5.3.2). The terrain category runs from category 1, exposed open terrain with few obstructions, to category 4, large city centres (IS 875 (Part 3):1987 §5.3.2).

The wind force on a structure, or on a part of it, is the design wind pressure times the area exposed to the wind and a coefficient for the shape (IS 875 (Part 3):1987 §6.3):

(3)
IS 875 (Part 3):1987 §6.3
where
wind force in the direction the coefficient's table givesN
force coefficient of the structure or member
effective frontal area, the area projected on a plane normal to the windm²

IS 875 writes the design pressure in this equation as . The force coefficient is dimensionless; it is called the drag coefficient when the force is in the direction of the wind (IS 875 (Part 3):1987 §3.1.7). The force differs from one face of a structure to another, so the total load is calculated for each wind direction (IS 875 (Part 3):1987 §6.3).

The ANSI / IEEE set's guide gives 2 methods (RUS 1724E-300 §7.4.8). The first takes the pressure on flat and cylindrical surfaces from the square of the design wind speed, with the projected area of a lattice structure taken as 1.5 times the area of its exposed members. The second follows the ASCE 7-95 loading standard, with the 3-second gust at 10 m as the basic wind speed. It multiplies the square of the speed by a drag coefficient, a height and exposure factor, a gust factor of 0.8 or 0.85 and an importance factor of 1.15 for substations. The wind load fluctuates, and RUS 1724E-300 advises members larger than the calculation requires for rigidity against effects it does not model (§7.4.5).

4Seismic load

An earthquake moves the ground, and the inertia of the structure and its equipment resists the motion. The seismic load is therefore a horizontal force proportional to the mass. A tall support with a heavy head, such as a breaker or a current transformer, is the most exposed. RUS 1724E-300 notes that some substation equipment is inherently shock resistant, but its foundations, structures, anchors, insulation and conductors may not be (§2.3.4).

IS 1893 (Part 1):2002 divides India into seismic zones II, III, IV and V and gives each a zone factor , from 0.10 in zone II to 0.36 in zone V (§6.4.2, Table 2). The design horizontal seismic coefficient of a structure is:

(4)
IS 1893 (Part 1):2002 §6.4.2
where
design horizontal seismic coefficient
zone factor for the maximum considered earthquake in the zone
importance factor, from the structure's function and the consequences of its failure
response reduction factor, from the structure's ductile or brittle behaviour
average response acceleration coefficient, from the period and the founding soil

The factor 2 reduces the zone factor of the maximum considered earthquake to that of the earthquake the structure is designed for. The ratio is not taken above 1.0. For a structure whose period is below 0.1 s, is not taken below , whatever the value of (IS 1893 (Part 1):2002 §6.4.2). The CEA standard specification requires clamping devices that fix a transformer or reactor to its foundation against movement in an earthquake (Ch. 2 §11.3.4).

RUS 1724E-300 divides the substation structures into 4 types for seismic loading: racks with and without equipment, and rigid and flexible isolated supports (§7.4.7). Its simplified method takes a base shear from a zone factor, an importance factor, a site coefficient for the soil and a structure type factor. Rigid and flexible supports above 121 kV in the 2 highest seismic zones of its map are designed and qualified to IEEE 693, which also qualifies the equipment itself.

5Materials and members

Steel is used for most substation structures, for its availability and its structural properties (RUS 1724E-300 §7.1.1). Aluminium is one-third the weight of steel and resists corrosion, but its lower modulus of elasticity makes deflection and torsion a closer check (RUS 1724E-300 §7.1.2). Precast, prestressed concrete suits coastal sites with high winds and corrosion, and treated wood has a shorter life than the other materials (RUS 1724E-300 §7.1.3, §7.1.4). The BOM of the IEC + CEA / CBIP set specifies steel to IS 2062 grade E250.

A structure is built of one of 3 member types (RUS 1724E-300 §7.3):

  • Lattice. Angle members form the chords and the lacing of a box truss. It usually gives the least weight, it is stable and rigid, and it is easy to fabricate, galvanise and ship. It needs much bolting at erection.
  • Solid profile. Wide flange shapes, pipes, tapered round or polygonal poles and square tubes. Its erection time is short and it is easy to maintain, so it is a common choice for equipment supports. A square tube resists torsion well, while a wide flange has a weak minor axis.
  • Semi-solid profile. Wide flanges or tubes braced by angles, stable and rigid like a lattice.

A structure must also be stiff enough. RUS 1724E-300 gives guideline deflection limits for line support structures at maximum tension with the overload factor (§7.4.3). A crossarm deflects within 1 % to 1.5 % of its span, and a pole's top within 4 % to 5 % of its height. A single-pole deadend that also carries backspan conductors needs the closest review.

6Galvanising and fasteners

Steel corrodes in the open air, so a substation structure carries a protective finish. Hot-dip galvanising, a coat of zinc applied by dipping the fabricated steel in molten zinc, is the most widely used finish (RUS 1724E-300 §7.7.1). It costs little to apply and maintain, resists most corrosive environments, heals minor abrasions and needs little maintenance. A member marred in handling is touched up with a zinc-rich paint. Paint systems are the alternative where a coloured finish is wanted (RUS 1724E-300 §7.7.2).

Galvanising fixes how a structure is made. A galvanised structure is not designed for field welding or field drilling, which would break the coat (RUS 1724E-300 §7.1.1). Joints to be galvanised are sealed by a small continuous weld, so the acid of the pickling bath cannot enter a crevice that the zinc cannot reach (RUS 1724E-300 §7.6). In the IEC + CEA / CBIP set's practice, OPTCL's specification for galvanised line towers and substation structures galvanises the steel to IS 4759 after the fabrication is complete. Its tower members and stubs are galvanised up to 150 mm below the top of the concrete pedestal (OPTCL Technical Specification CPC-39 §7.0).

The bolts and the hardware are galvanised too (RUS 1724E-300 §7.7.1). RUS 1724E-300 advises one type and one diameter of bolt throughout a substation's structures, where possible (§7.5). A structure loaded repeatedly by wind uses lockwashers or locknuts, so the connections do not work loose.

7Foundations

A foundation passes the loads of its structure into the soil without exceeding the soil's bearing capacity and without a settlement the structure cannot accept (RUS 1724E-300 §8.1). Its design therefore rests on the soil's properties, measured by the geotechnical investigation of the site (Site, survey and environmental considerations, Geotechnical investigation). The quantities it needs are the allowable bearing pressure, the strength of the soil, the level of the groundwater and the soil's chemistry.

The groundwater matters most in granular soils. Buoyancy halves the effective density of a submerged sand, so a water table that rises to the base of a footing halves the part of the bearing capacity that the soil below provides (RUS 1724E-300 §8.2.4). Silts, organic soils and uncompacted fills settle unevenly over time, and soils that swell or collapse when wetted need a geotechnical engineer's design (RUS 1724E-300 §8.2.5). Sulphates and chlorides in the soil or the groundwater attack concrete and steel and set the type of cement (RUS 1724E-300 §8.2.6).

RUS 1724E-300 describes the common foundation types of the ANSI / IEEE set's practice (§8.3):

  • Drilled shaft (pier). An augered hole filled with reinforcing steel and concrete, with the anchor bolts cast in it or in a later cap. It resists overturning moments and shears best, and it is economical in quantity. Common substation sizes run from 0.61 m to 1.52 m in diameter (RUS 1724E-300 §8.3.1). RUS 1724E-300 keeps the shafts of adjacent structures at least 3 diameters apart, centre to centre, as a common rule (§8.3.2).
  • Spread footing. A pier or wall on a square or rectangular slab below grade, the pad and pier of Figure 1. It is usually preferred for transformers, breakers and other equipment. It is seated below the frost depth. RUS 1724E-300 designs a footing in uplift for a safety factor of at least 1.5 (§8.3.5.3).
  • Slab on grade. A slab of 30 cm to 60 cm on prepared subgrade, for switchgear, breakers and transformers. A transformer slab carries the weight of the unit with its oil, and the point loads of the 4 jacks that raise and level it (RUS 1724E-300 §8.3.6). The slab bears on the prepared subgrade and not on the stone of an oil sump.

RUS 1724E-300 gives a minimum reinforcing steel area of 0.0018 times the gross concrete area, to prevent shrinkage cracks as the concrete dries (§8.3.6.5). In the absence of soil data it takes an allowable bearing pressure of 48 kN/m² to 72 kN/m² for a slab, and it notes that this range may not be conservative for a given site (RUS 1724E-300 §8.3.6.4).

8Foundations in the IEC + CEA / CBIP set

Indian practice designs the foundations in reinforced cement concrete (RCC) to IS 456 by the limit state method, with a minimum concrete grade of M20 (OPTCL Technical Specification E-6 §6.1). The switchyard plinths stand at least 200 mm above the finished ground level, the top of the gravel, and a building's plinth at least 500 mm. A lean concrete layer of at least 75 mm lies under the underground structures.

The tower and equipment foundations are checked against sliding, overturning and pullout with a factor of safety of 2.2 for the normal condition and 1.65 for the short-circuit condition (OPTCL E-6 §6.1). Gantry and tower foundations take an additional factor of 1.1 for the normal, broken-wire and short-circuit conditions (OPTCL E-6 §6.3). Underground structures are checked against buoyancy with a factor of at least 1.5 at the maximum groundwater table. The foundations rest below the virgin ground level.

Transformers and breakers stand on block foundations, and a breaker's foundation is designed for its impact loading as its manufacturer states (OPTCL E-6 §6.1, §6.3). The CEA standard specification adds the transformer's own needs (Annexure-P §3.0). The transformer stands on a block foundation with a plinth 300 mm to 500 mm above the finished ground level. A rail-cum-road track lets a failed unit be moved out fully assembled with its oil. It also sizes the soak pit around the foundation (Fire protection and oil containment, Soak pits and the burnt-oil pit).

9Anchor bolts and the base

The anchor bolts tie the structure's base plate to its foundation and carry its shear, uplift and moment into the concrete. A solid-profile support may sit with its base plate on the foundation or on levelling nuts slightly above it (RUS 1724E-300 §7.4.6). Levelling nuts remove the need for close tolerances on the foundation's level and surface, and allow for fabrication tolerances when the buswork is fitted. They also keep the base plate out of standing water. The gap under the nuts is usually 1.3 cm, and the bolts may need to be larger for the bending it adds.

RUS 1724E-300 makes anchor bolts to the specification of its non-galvanised bolts and requires hot-dip galvanising for substation use (§7.5.2). In the IEC + CEA / CBIP set's practice, the galvanising of a stub runs below the top of the pedestal (Galvanising and fasteners), so the steel at the face of the concrete is protected.

10In the design

The design places the structures in the yard and counts them in the Structures section of the BOM. It does not calculate the loads on a structure, its members or its foundations. The structure steel is an estimate from typical weights per structure, as Bill of materials, Example 2 shows.

The default 220 kV project lists 1 line gantry, "galvanised lattice, beam 15.5 m, peaks 18.5 m". The gantry beam stands at 15.5 m, the level the yard's clearances set (Yard layout, Bay width, phase spacing and heights). The BOM also lists 10 shield-wire towers or gantry peaks, 32 supports for single-phase units, 39 isolator supports, one per pole, and 54 bus post insulator supports. The estimated steel is 150.7 t, "IS 2062 E250, hot-dip galvanised".

The 3D model shows the equipment on its supports, without foundations (Roads, trenches and buildings, Trenches, foundations and drainage in the design). On the ANSI / IEEE set, the input Seismic qualification level prints in the yard sheet's notes, the BOM and the compliance checklist, against IEEE 693. It changes no geometry and no quantity, and the checklist item is answered from the equipment specifications.

Review questions
  1. Distinguish a line support structure from an equipment support structure.
    Answer 1

    A line support structure, the gantry, has 2 towers and a beam that carry the line and strung bus tensions, while an equipment support is a cantilever that carries one item under wind and short-circuit forces (Structures of a switchyard).

  2. Name the loads that usually produce the maximum stresses in an equipment support structure.
    Answer 2

    Wind plus short-circuit forces, with ice usually not the controlling load (Loads on a structure).

  3. Calculate the design wind pressure on a structure up to 10 m high at a site whose basic wind speed is 44 m/s, with .
    Answer 3

    The design wind speed is  m/s (Eq. (1)), and the pressure is  N/m² (Eq. (2)).

  4. Explain why a galvanised structure is not designed for field welding or drilling.
    Answer 4

    Welding or drilling in the field would break the zinc coat that protects the steel, and the joints to be galvanised are sealed by a continuous weld before galvanising (Galvanising and fasteners).

  5. Compare a drilled shaft with a spread footing as a foundation.
    Answer 5

    A drilled shaft is an augered concrete pier that resists overturning best and is economical in quantity, while a spread footing is a pier on a slab below the frost depth, usually preferred under heavy equipment (Foundations).

  6. State the factors of safety of the IEC + CEA / CBIP set's practice for tower and equipment foundations.
    Answer 6

    The factors are 2.2 against sliding, overturning and pullout for the normal condition and 1.65 for the short-circuit condition, with 1.1 more for gantry and tower foundations (Foundations in the IEC + CEA / CBIP set).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[2]IS 875 (Part 3):1987, IS 875 (Part 3): 1987, Code of Practice for Design Loads (Other than Earthquake) for Buildings and Structures, Part 3: Wind Loads. §5.3; §5.4; §6.3.

[3]IS 1893 (Part 1):2002, IS 1893 (Part 1): 2002, Criteria for Earthquake Resistant Design of Structures, Part 1: General Provisions and Buildings. §6.4.2.

[4]CEA standard specification for transformers and reactors, Standard Specifications and Technical Parameters for Transformers and Reactors (66 kV & above voltage class).

[5]OPTCL Technical Specification E-6, Technical Specification E-6, Civil Works.

[6]OPTCL Technical Specification CPC-39, Technical Specification, Biennial Procurement of hot dip Galvanized steel structure materials and HDG nuts and bolts for Transmission Line towers and Sub-Stations equipment structures.

[7]IEEE 693, IEEE Recommended Practice for Seismic Design of Substations.

[8]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.

[9]ANSI C2-2007, National Electrical Safety Code.

[10]ASCE 7-95, Minimum Design Loads for Buildings and Other Structures.

[11]IS 2062, IS 2062.

[12]IS 4759, IS 4759.

[13]IS 456, IS 456.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Structures and foundations, revision 3, 9 Nov 2026, https://substation.solarlayout.app/library/reference/structures-and-foundations