Capacitor banks and harmonic filters

A shunt capacitor bank supplies reactive power to the network at the point where it is connected. It raises the voltage there and improves the power factor of the load it serves. A bank is built from many capacitor units, connected in series and in parallel, with fuses and a protection that detects failed units. Switching a bank causes inrush currents and overvoltages, and the bank forms a resonant circuit with the inductance of the network. A reactor in series with the bank limits the inrush, detunes the resonance or turns the bank into a harmonic filter. This topic explains these subjects and the harmonic filter banks of the design.

Before this topic: Active, reactive and apparent power · Harmonics and voltage unbalance · Circuit breakers

1The task of a shunt capacitor bank

An inductive load draws a lagging current and absorbs reactive power (Active, reactive and apparent power, Power factor). The reactive current flows through the lines and transformers that feed the load, adds to their losses and lowers the voltage at the load. A capacitor draws a leading current, so it supplies reactive power instead of absorbing it. Shunt capacitor banks at substations improve the power factor and the voltage by supplying this leading reactive power to the network (RUS Bulletin 1724E-300 §5.6.1).

The reactive power of a three-phase bank follows from the voltage and its capacitance:

(1)
Cahier Technique 142 §1
where
reactive power of the bankMvar
phase-to-phase voltage at the bankkV
angular frequency, rad/s
capacitance per phase, in starF
current of the bank, root-mean-square valuekA

The reactive power rises with the square of the voltage. A bank therefore supplies less when the voltage is low, which is when the network needs it most. A bank supplies a fixed amount of reactive power, and it is switched in or out in steps to follow the load. Fast control of reactive power needs a static compensator (SVC and STATCOM, Switched and dynamic compensation).

2Capacitor units and the arrangement of a bank

A capacitor unit is a sealed can of capacitor elements with 1 or 2 bushings. A bank of a given rating and voltage is made of series groups, each of several units in parallel (RUS 1724E-300 §5.6.4). Units of the highest available voltage rating give the fewest series groups. That gives the most economical bank and the most sensitive detection of unbalance.

The number of parallel units in a series group is limited at both ends. The operating voltage of a unit must not exceed 110 % of its rated voltage. When a unit fails and its fuse operates, the remaining units of its group share the group's voltage and their voltage rises. The number of parallel units is chosen so that the loss of one unit keeps the others within that limit. Too many units in parallel raise the energy that the healthy units discharge into a failed one, and the case of the failed unit can rupture.

Open-rack banks carry the units in frames of aluminium or galvanised steel, inside a fence (RUS 1724E-300 §5.6.3.1). They supply large blocks of reactive power at voltages up to 765 kV. Metal-enclosed banks hold the units, the switching device and the protection inside an earthed enclosure. They supply medium-size blocks on distribution systems up to 34.5 kV.

Connections. The 3 phases of a bank are connected in star (wye) or in delta:

  • Earthed star. The neutral is connected to earth. If the phase has a single series group, a unit's fuse carries the full short-circuit current of the network when the unit fails.
  • Unearthed star. The neutral floats. The healthy phases limit the current into a failed unit to at most 3 times the bank's phase current, so a fuse of lower breaking capacity serves. The neutral needs the full insulation of a line.
  • Double star. The bank is split into 2 stars with their neutrals joined, a double-star bank (Figure 1). It suits banks of large reactive power, and a current transformer between the neutrals detects unbalance.
  • Delta. It is used at the lower voltages, where the network voltage equals the voltage rating of one unit.
Figure 1.A double-star capacitor bank. Each phase leg is a series connection of groups of capacitor units in parallel, and the current transformer between the neutrals measures the unbalance current that a failed unit causes. The drawing is schematic and not to scale.

3Fuses: external, internal and fuseless

A capacitor is built for a high dielectric stress, and a calculated rate of unit failures is expected. Capacitor fuses therefore protect the network from the failures of units, rather than the units from overload (RUS 1724E-300 §5.6.7.1). A fuse isolates the failed unit with little disturbance to the rest of the bank. It must clear before the gas of the internal fault bursts the case. It also carries the normal overloads, the inrush currents and the discharge currents without operating.

External fuses. Each unit has its own fuse outside its case, in series with it. A blown fuse shows which unit has failed. Open-rack banks use externally fused units, and expulsion fuses need a clearance for their discharge.

Internal fuses. A fuse link is placed in series with each element inside the unit. The unit has many elements in parallel and few groups in series, and a failed element is cut out while the unit stays in service. Banks of internally fused units have fewer units in parallel and more series groups than externally fused banks.

Fuseless banks. A fuseless bank uses capacitor units with a polypropylene film dielectric, whose reliability removes the need for fuses in many applications. Such a bank is simpler to build and operate than a fused bank. RUS 1724E-300 reports fuseless banks mainly at 69 kV to 230 kV (§5.6.7.1).

4Unbalance protection

A failed unit or element changes the impedance of its phase, and the voltage on the remaining units of its series group rises. The protective control removes the bank from the bus before any unit exceeds 110 % of its rated voltage (RUS 1724E-300 §5.6.7.2). It measures the unbalance that the failure causes:

  • Earthed star. A current transformer (CT) in the neutral measures the neutral current. The third harmonic flows in the neutral of a healthy bank, so the relay must reject it.
  • Unearthed star. A voltage transformer between the neutral and earth measures the shift of the neutral voltage.
  • Double star. A CT between the 2 neutrals measures the current that flows when the stars become unequal. The scheme is sensitive.

The control can be set at 2 levels: an alarm at the first failures, and a trip before the voltage limit is reached. The neutral schemes of a star bank do not detect an equal loss of units in the 3 phases (RUS 1724E-300 §5.6.7.2.1, §5.6.7.2.2). They respond to unbalance only, and do not protect the units against a rise of the supply voltage on all phases.

5Ratings

IEC 60871-1 covers shunt capacitor units and banks for alternating-current power systems above 1000 V, at 15 Hz to 60 Hz, used for power factor correction and in filter circuits. IEEE 18 covers shunt power capacitors rated 216 V or higher and 2.5 kvar or more, for systems at 50 Hz or 60 Hz. A unit is specified by its rated voltage, its reactive power, its frequency, its insulation level and its fusing.

Voltage. The maximum operating voltage of a unit must not exceed 110 % of its rated voltage, the limit that the bank's arrangement and protection hold (Capacitor units and the arrangement of a bank). The switching device is rated at least 10 % above the capacitor's rated voltage for the same reason (RUS 1724E-300 §5.6.6.1).

Current. Harmonics raise the current of a capacitor, because its reactance falls as the frequency rises. Power capacitors accept 1.3 times their rated current (Cahier Technique 142 §3, Cahier Technique 152 §8.1). The switching device's continuous current includes the overvoltage, the tolerance of the capacitance and the harmonics. RUS 1724E-300 takes a total multiplier of 1.25 for an unearthed bank and 1.35 for an earthed bank (§5.6.6.1).

Insulation. The units of a high-voltage bank stand on insulated racks, and each series group sits at a different voltage to earth. The basic impulse insulation level of a unit ranges from 75 kVp to 200 kVp by its voltage rating (RUS 1724E-300 §5.6.5.3).

6Switching and inrush current

Closing a breaker on a discharged bank is close to applying a short circuit for a moment. The bank charges through the inductance of the network, and the current and voltage oscillate at a frequency set by that inductance and the bank's capacitance. Overvoltages can reach twice the network voltage, and the inrush current can reach many times the bank's rated current (RUS 1724E-300 §5.6.2.2.1).

Isolated bank. For a single bank on a bus, the network's inductance limits the inrush. Its peak and its frequency are

(2)
Cahier Technique 142 §2, §5
where
peak of the inrush currentkA
frequency of the inrush oscillationHz
three-phase short-circuit power of the network at the bank, MVA
short-circuit inductance of the network, per phaseH
network frequencyHz

The second form of follows from the first. With and (Eq. (1)), the ratio equals , and its square root is . The sources give different ranges for the inrush in practice. RUS 1724E-300 gives 5 to 15 times the steady-state current. Cahier Technique 142 gives 10 to 30 times on average, at frequencies of 300 Hz to 1000 Hz, and at most 100 times in the installations it reports. The inrush of an isolated bank is below the short-circuit current at its location, so a breaker's making rating covers it.

Back-to-back switching. When a bank is closed while another bank on the same bus is in service, the charged bank discharges into the one being closed. Only the short connection between them limits this current. Its magnitude and frequency are much higher than those of an isolated bank, and it decays within a fraction of a cycle (RUS 1724E-300 §5.6.2.2.1.2). A current-limiting reactor in series with each bank keeps the peak within the rating of the switching device. For equal banks in parallel, RUS 1724E-300 gives the inductance per phase of each bank's reactor as

(3)
RUS Bulletin 1724E-300 §5.6.2.2.4, Eq. 5-4
where
inductance of the current-limiting reactor, per phaseµH
reactive power of one bank, per phaseMvar
number of equal banks in parallel
largest permitted peak of the inrush currentkA
Example 1Reactor for back-to-back switching

Given: the example of RUS 1724E-300 §5.6.2.2.4: 2 banks of 13 500 kvar at 14.4 kV and 60 Hz, switched by devices rated 20 kA peak.

Reactive power per phase: = 4.5 Mvar.

Inductance by Eq. (3):

Continuous current of the reactor: the bank's rated current, = 541 A, times 1.25 for an unearthed bank, gives 677 A.

Result: each phase of each bank takes a reactor of at least 29.8 µH rated for 677 A.

A switching device can also reduce the transients. A circuit switcher with pre-insertion inductors, or a breaker with pre-insertion resistors, puts an impedance in series with the bank for a moment as it closes. A vacuum switch with synchronous control closes each pole near the zero of its voltage (RUS 1724E-300 §5.6.2.2.2). Most switching devices are derated for capacitor switching, and their capacitive switching rating lies well below their continuous current.

7Opening a bank and restrike

When the switching device opens, the current is interrupted at a current zero. The voltage of a capacitive circuit is then at its peak, and the bank stays charged at that peak. Half a cycle later, the network voltage has reversed, and the voltage across the open contacts reaches twice the peak (Cahier Technique 142 §2). If the gap's dielectric strength recovers more slowly than this voltage rises, the gap breaks down.

A breakdown within a quarter cycle after the current zero is a re-ignition, and causes no rise of voltage. A later breakdown is a restrike (Circuit breakers, The arc and its interruption). One restrike produces a transient of 3 times the network voltage (RUS 1724E-300 §5.6.2.2.3). Repeated restrikes can raise the voltage further, and transients from restrikes have caused failures of capacitor banks. A device rated for capacitive switching avoids restrikes. RUS 1724E-300 warns against a bank being opened by an upstream breaker that is underrated for that duty.

8Resonance with the network

A shunt capacitor bank and the inductance of the network form a resonant circuit. Resonance occurs at the frequency where the inductive and capacitive reactances are equal (RUS 1724E-300 §5.6.2.3). Seen from the bus, the bank is in parallel with the network's inductance. At the resonance frequency the impedance of the bus is high, and a small harmonic current injected there produces a large harmonic voltage (Harmonics and voltage unbalance, Effects of harmonics).

The order of this parallel resonance is (Harmonics and voltage unbalance, Eq. (3)). The inrush oscillation of an isolated bank runs in the same inductance and capacitance, so its frequency is the frequency of the parallel resonance (Eq. (2)). The short-circuit power of the network changes with its operating state, so the resonance moves when lines or transformers are switched. The impedance of a bus with a bank, and with the same bank detuned by a series reactor, is drawn in Figure 2.

Figure 2.The impedance of a bus against the harmonic order. A capacitor bank forms a parallel resonance with the network. A reactor in series with the bank moves the resonance below the lowest harmonic and keeps the branch inductive over the harmonics. The drawing is schematic and not to scale.
Example 2A capacitor bank on a section of the default MV bus

Given: a section of the default 220 kV / 33 kV project's medium-voltage (MV) bus at 50 Hz, and a capacitor bank of 58.00 Mvar, the rating of one static var generator (SVG) unit. The short-circuit study gives a three-phase current of 24.39 kA at the MV bus, of which 2.76 kA comes from the plant's converters. A converter is not an inductance, so the network's share is 21.63 kA.

Short-circuit power of the network:

Order of the parallel resonance, Harmonics and voltage unbalance, Eq. (3):

Inrush of the bank switched alone, Eq. (2): the rated current is 1015 A, so

Result: the bank would resonate with the network at order 4.62, between the 4th and the 5th harmonic of the plant's converters. A weaker network lowers the order towards the 4th. The peak of its inrush, 6.63 kA at 231 Hz, is 6.53 times the root-mean-square value of its rated current.

The bank in the example is a hypothetical one, chosen to show the order of the resonance at that bus. The design places no plain capacitor bank there (In the design).

9Detuned banks

A reactor in series with the bank changes the branch's behaviour over the harmonic spectrum. In a detuned bank, the reactor is chosen so that the branch's series resonance lies below the lowest harmonic present (Cahier Technique 152 §6). Over the harmonics, the branch is then inductive, as the network is. The harmonic currents divide between the branch and the network in inverse proportion to their impedances, and most of them flow into the network. The capacitors are protected from harmonic overload, and the parallel resonance moves below the spectrum.

Cahier Technique 152 states that such reactors are generally tuned between 135 Hz and 225 Hz in a 50 Hz network, that is, at orders 2.7 to 4.5 (§6). Its worked example tunes a bank to order 4.8 (Cahier Technique 152 §8.2). In that example the capacitor current falls from 1.34 times its rating with the bank alone, above the 1.3 permitted, to 1.06 times with the reactor. Cahier Technique 152 adds 2 precautions. No other plain capacitor bank on the network may bring the resonance back inside the spectrum. The resonance must also avoid the frequencies a utility uses for ripple control signals.

The reactor raises the voltage at the capacitor terminals above the bus voltage at the fundamental frequency. A detuned bank supplies more reactive power than its capacitors would at the bus voltage alone, as Eq. (4) shows for a tuned branch. The capacitors must be rated for the higher voltage.

10Harmonic filters

A harmonic filter limits the harmonic voltages of a bus to a specified low value, which a detuned bank does not (Cahier Technique 152 §7). The resonant shunt filter is a reactor and a capacitor bank tuned to the frequency of the harmonic to be removed (Harmonics and voltage unbalance, Eq. (4)). At that frequency its impedance falls to the resistance of the reactor, and it absorbs most of that harmonic's current. One branch is installed for each harmonic to be limited, and the branches together form a filter bank.

Below its tuning frequency the filter behaves as a capacitor, and it supplies reactive power at the fundamental:

(4)
Cahier Technique 152 §7.1
where
reactive power of the filter at the fundamentalMvar
tuning order,
tuning frequency of the branchHz
operating voltage of the bus at the fundamental, phase to phasekV
capacitance per phase, in starF
fundamental frequencyHz

For a branch tuned to the 5th harmonic, the factor is 25/24, so the filter supplies 1.04 times the reactive power of its capacitors at the bus voltage. The quality factor of the reactor, , with the resistance of the reactor and the characteristic reactance of the branch, sets how sharply the branch absorbs its harmonic. A high filters well but is sensitive to mistuning. The tuning drifts with the network frequency and with the temperature of the capacitors. The reactors can be adjusted to correct the tolerances of manufacture.

Damped filters. A second-order damped filter adds a resistor across the reactor of a tuned branch (Cahier Technique 152 §7.2). Above its tuning frequency its impedance falls towards the resistance of the resistor, so it absorbs a wide band of harmonics, hence the name damped high-pass filter. It also damps the parallel resonance below the tuning frequency and the transients when the filter is energised. Its quality factor, , lies generally between 2 and 10, and its losses are higher than those of a resonant shunt. A damped filter may be combined with resonant shunts tuned to the lowest harmonics.

Each tuned branch forms a parallel resonance with the network below its own tuning frequency. These resonances must fall between the harmonics present, so the design of a filter bank needs a harmonic study of the network. The harmonics a plant injects and the limits it must meet are explained in Harmonics and voltage unbalance, Limits at the grid connection.

11Discharge and earthing

A disconnected bank stays charged (Opening a bank and restrike). Substation capacitor units therefore have internal discharge resistors. RUS 1724E-300 §5.6.8 specifies, in accordance with NEMA CP-1, that they reduce the residual voltage to 50 V or less within 5 minutes after disconnection. Cahier Technique 142 gives 1 to 5 minutes for the discharge through the resistors (§2).

Before people handle a disconnected bank, switches short-circuit and earth each series group, so that no hazardous voltage remains at the capacitor terminals. Interlocks can prevent the operation of these switches on a live bank and keep people out of the bank's enclosure until it is earthed.

12Series capacitors

A capacitor bank can also be connected in series with a long line (Cahier Technique 142 §1). Its negative reactance cancels part of the line's reactance, so the reactive power it supplies follows the line current. A series bank carries the line's short-circuit current, and it needs a protection that keeps that current from destroying the capacitors.

13Standards

IEC 60871-1 is the standard for shunt capacitors above 1000 V, and its 2014 edition covers units and banks. IEEE 18 is the standard for shunt power capacitors, and its 2012 edition is superseded by the edition of 2025. RUS 1724E-300 names IEEE 1036 as the guide for the application of shunt power capacitors and IEEE C37.99 as the guide for their protection. It names IEEE C37.012 for the capacitive switching of breakers, and IEEE C57.16 for the series reactors.

14In the design

The design provides harmonic filter banks and no plain shunt capacitor bank. When the harmonic study has a filter, the entered rating or the rating it gives, the design places a filter bank on each MV section at that rating. When it has none and the Define input Harmonic filter is on, its default, the design keeps a reserved filter bay on each MV section, beside the SVG (Reactive power equipment, The harmonic filters). A plant with synchronous generators and a switching substation have neither the SVG nor the filters.

Bill of materials. The bill of materials (BOM) line "Harmonic filter bay (reserved)" specifies 33 kV, rating per harmonic study, with a quantity of 2, one per section of the default project, whose harmonics are within the limits without a filter. A filter bank in the study is specified with its rating per section and its tuning order.

Single-line diagram. The single-line diagram (SLD) draws the filter as a capacitor in series with a reactor, connected to earth. Its MV panel carries the filter's rating per section and its tuning order, or, for a reserved bay, the words "(RESERVED)" and "RATING PER HARMONIC STUDY". The SLD's CT note rates the filter panel for the larger of one SVG unit and one filter. For the default project's reserved bay it is 1015 A, the rated current of one SVG unit at 33 kV.

Yard. The filter area lies beside the SVG area, inside the same fence, or in its own fence without an SVG, 15 m long per section and 10 m deep. The default project's filter area is 30 m long (Reactive power equipment, The reactive power area).

Harmonic study. In the IEC + CEA / CBIP set, the design's harmonic study gives the distortion at the interconnection point (Harmonics and voltage unbalance, In the design). When a limit is not met, it gives the smallest single-tuned filter rating that meets the limits, or states that no rating in its range does. It searches the tunings 6 % below the lowest order over its limit and 6 % below the characteristic orders under it, and gives the smallest rating with its tuning. A six-pulse converter bridge injects the characteristic orders , with and = 1, 2, 3 and so on (Cahier Technique 152 §4.1). The design takes these orders as the candidate tunings for the inverters too. A rating counts only if it meets the limits with the capacitance at its rated value and across 0.95 to 1.05 of it. IEC 60871-1:2005 Annex B recommends this symmetrical tolerance of ±5 % for the units of a band-pass filter. A rating and a tuning order entered on the MV system page (Harmonic filter rating, Filter tuning order) go into the study. The rating also goes into the reactive power study, as a fixed capacitor at the MV buses (Reactive power equipment, The harmonic filters).

Checklist. The checklist item on harmonic distortion at the interconnection point is answered from the harmonic study, under the Central Electricity Authority (CEA) Connectivity Regulations or, in the ANSI / IEEE set, IEEE 519.

SubstationLayout does not design the filter's capacitors and reactor, calculate inrush currents or series reactors, or set the unbalance protection of a bank. The filter maker's design replaces the suggested tuning order.

Review questions
  1. Explain why a capacitor bank supplies less reactive power at a low voltage.
    Answer 1

    Its reactive power is , so it falls with the square of the voltage (Eq. (1)).

  2. Explain how the number of parallel units in a series group is chosen.
    Answer 2

    The loss of one unit raises the voltage on the others of its group, and the number is chosen so that they stay within 110 % of their rated voltage (Capacitor units and the arrangement of a bank).

  3. Describe the unbalance protection of a double-star bank.
    Answer 3

    A CT between the 2 neutrals measures the current that flows when a failed unit makes the stars unequal, and the control trips the bank before any unit exceeds 110 % of its rated voltage (Unbalance protection).

  4. Calculate the inductance of the reactors for the banks switched back to back in the RUS example.
    Answer 4

    By Eq. (3), each phase of each bank takes 29.8 µH, rated for 677 A (Example 1).

  5. Find the order of the parallel resonance of a bank of one SVG unit's rating on the default MV bus.
    Answer 5

    With the network's short-circuit power of 1236 MVA, gives order 4.62, between the 4th and the 5th harmonic (Example 2).

  6. Compare a detuned bank with a tuned harmonic filter.
    Answer 6

    A detuned bank has its resonance below the lowest harmonic, so it stays inductive and protects its capacitors, while a tuned filter absorbs the current of the harmonic it is tuned to (Detuned banks, Harmonic filters).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations. §5.6.2.2.4, Eq. 5-4.

[2]Cahier Technique 142, Cahier Technique no. 142: Control equipment for MV capacitor banks. §1; §2, §5.

[3]Cahier Technique 152, Cahier Technique no. 152: Harmonic disturbances in networks, and their treatment. §7.1.

[4]IEC 60871-1:2014, Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V, Part 1: General.

[5]IEC 60871-1:2005, Shunt Capacitors for AC Power Systems Having a Rated Voltage Above 1000 V, Part 1: General.

[6]IEEE 18-2012, IEEE Standard for Shunt Power Capacitors.

[7]IEEE C57.16-2025, IEEE Standard for Requirements, Terminology, and Test Code for Dry-Type Air-Core Series-Connected Reactors.

[8]IEEE 1036, IEEE Guide for the Application of Shunt Power Capacitors.

[9]IEEE C37.99, IEEE Guide for the Protection of Shunt Capacitor Banks.

[10]IEEE C37.012, IEEE Guide for the Application of Capacitive Current Switching for AC High-Voltage Circuit Breakers.

[11]Mirus white paper on IEEE Std 519-2014, A Practical and Effective Way of Applying IEEE Std 519-2014 Harmonic Limits.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.