Types of substation
Substations are classified by the function they perform in the power system and by the way their high-voltage (HV) equipment is insulated. The function determines which transformers, bays and buses a substation has. The construction determines how much land it takes and how its equipment is housed. This topic describes the types of both kinds, what each changes in a design, and which of them SubstationLayout designs.
Before this topic: Substations in the power system
1Types by function
The function of a substation is read from the voltages it connects. Figure 1 draws the types as their connections and their central equipment.
The Occupational Safety and Health Administration (OSHA) describes the transmission and distribution substations in its Electric Power eTool. A step-up substation receives power from a nearby generating station. A large power transformer raises the voltage for transmission to distant places. A step-down substation stands at a switching point of the grid. It lowers the transmission voltage to the sub-transmission voltage and feeds sub-transmission or distribution lines. A distribution substation stands near the consumers. It lowers the transmission or sub-transmission voltage to the levels the consumers use (OSHA Electric Power eTool, Substations). The same source notes that one substation may combine 2 or more of these types.
2Switching substations
A switching substation connects lines without changing their voltage. The International Electrotechnical Vocabulary defines it as a substation that includes switchgear and usually busbars, but no power transformers (IEV 605-01-02). Its circuit breakers connect and disconnect the lines, and its buses let the network route power between them.
A substation that joins an upper and a lower transmission voltage has power transformers between them. In India these transformers are called interconnecting transformers (ICTs) (CEA Manual on Transmission Planning Criteria 2023, Abbreviations). The manual specifies that their size and number be such that the outage of one unit does not overload the remaining ICTs or the network below them (CEA Manual on Transmission Planning Criteria 2023 §5.2.3). SubstationLayout also calls the step-up transformers of a pooling substation ICTs, and tags them ICT-1 and ICT-2 on its drawings (Bays and their equipment, Transformer bay).
3Pooling substations
A generation pooling substation connects generating stations to evacuate their power, and a load-serving substation connects loads (Substations in the power system, The pooling substation of a generating plant).
The CEA Manual on Transmission Planning Criteria 2023 §5.2.2 sets a limit on the transformation capacity of one substation per voltage level, with a column for each category. At 400 kV the limit for a generation pooling substation is higher than for a load-serving one. At the other levels the manual gives the same capacity for both.
4Converter stations
A converter station joins an alternating current (AC) network to a high-voltage direct current (HVDC) link. At the sending end it converts AC to direct current (DC), and at the receiving end it converts DC back to AC (Siemens Energy, High-voltage direct current transmission solutions). The link between the 2 stations may be an overhead line, an underground cable or a submarine cable.
HVDC transmission is used to carry power over long distances. It can also connect grids that are not synchronous or that run at different frequencies (Siemens Energy). India's regional grids are joined into a national grid by high-capacity AC and HVDC corridors (CEA Manual on Transmission Planning Criteria 2023 §1.1.5). SubstationLayout does not design converter stations, and this library describes them as context only.
5Types by construction
The high-voltage switchgear of a substation is insulated by air or by gas. In a substation with air-insulated switchgear (AIS), the live parts stand in an open yard, separated by air. In a substation with gas-insulated switchgear (GIS), the switchgear is enclosed in gas-filled modules. Gas-insulated switchgear takes a smaller area and can be installed indoors, in busy urban areas and in harsh environments (Hitachi Energy, GIS substations).
A hybrid substation combines gas-insulated and air-insulated switchgear (Hitachi Energy, Hybrid substations). One form is a bay module that encloses the functions of a complete switchgear bay in a gas-insulated housing and connects to the substation's air-insulated busbars (Hitachi Energy, Hybrid switchgear). IEC 62271-205:2008 covers compact switchgear assemblies above 52 kV. Its scope includes assemblies of AIS components only, and assemblies that combine AIS and GIS components, which it calls mixed technology switchgear (MTS).
The choice between them follows the site. An open yard needs the most land. A GIS needs a building, the gas handling and the supplier's modules. A hybrid substation places gas-insulated bay modules in an air-insulated layout.
6What each type changes in a design
The type sets the parts of a design that differ from one substation to another. SubstationLayout applies these rules:
| Type | What the design contains |
|---|---|
| Pooling substation of a solar, wind or hybrid plant | Plant feeders on a medium-voltage (MV) bus in sections, step-up transformers, the HV switchyard with its line bays, reactive power and harmonic filter equipment on the MV bus |
| Pooling substation of a thermal plant | One generator transformer and one HV bay per generating unit, station transformers and a station board at 11 kV, no MV collector |
| Switching substation | 2 HV yards joined by ICTs, line bays on both sides, no plant and no MV switchgear |
| AIS yard | An open yard with bays at the level's width, and the clearances the yard keeps (Electrical clearances) |
| GIS yard | An indoor GIS hall with an erection bay and a crane, the lines leaving the hall through gas-to-air bushings (Gas-insulated switchgear (GIS)) |
SubstationLayout calls its HV/HV type a switching substation, as the Substation type input names it. Its 2 HV yards are joined by ICTs, so the substation transforms the voltage between them. In the vocabulary of IEV 605-01-02, a substation without power transformers is a switching substation. A design of the service's Switching type has its own transformers (Power transformers, Switching substations).
7In the design
Of the functional types, SubstationLayout designs the pooling substation of a plant and the HV/HV switching substation. In the IEC + CEA / CBIP set it designs pooling substations from 33 kV to 400 kV, and switching substations at the pairs 765/400 kV, 400/220 kV, 400/132 kV, 220/132 kV, 220/66 kV, 132/66 kV and 132/33 kV. In the ANSI / IEEE set it designs pooling substations from 69 kV to 345 kV, and switching substations at the pairs 345/230 kV, 345/138 kV, 345/115 kV, 230/138 kV, 230/115 kV, 230/69 kV, 161/69 kV, 138/69 kV and 115/69 kV.
Each HV yard is AIS or GIS, chosen by the inputs HV insulation and, for the lower yard of a switching substation, Lower-side insulation. A GIS yard is available from 33 kV to 765 kV in the IEC + CEA / CBIP set and from 69 kV to 345 kV in the ANSI / IEEE set. A switching substation can therefore have a GIS yard on one side and an AIS yard on the other. SubstationLayout does not design mixed technology switchgear modules, converter stations, or step-down and distribution substations that serve loads. A new project is an AIS pooling substation at 220 kV.
- Name the types of substation by function.
Answer 1
Step-up, step-down and distribution substations, switching substations, generation pooling substations and converter stations (Types by function).
- Distinguish a switching substation from a step-down substation.
Answer 2
A switching substation has switchgear and usually busbars but no power transformers, while a step-down substation lowers the transmission voltage through its transformers (Switching substations).
- Explain what a converter station does.
Answer 3
It converts AC to DC at the sending end of an HVDC link and DC back to AC at the receiving end (Converter stations).
- Compare an AIS, a GIS and a hybrid substation.
Answer 4
An AIS has its live parts in an open yard insulated by air, a GIS encloses its switchgear in gas-filled modules on a smaller area, and a hybrid substation combines the two (Types by construction).
- State what a switching substation of SubstationLayout contains.
Answer 5
It contains 2 HV yards joined by ICTs, line bays on both sides, and no plant or MV switchgear (What each type changes in a design).
[1]OSHA Electric Power eTool, Electric Power Generation, Transmission, and Distribution eTool.
[2]ISO 15926-4 reference data library, Switching substation.
[3]CEA Manual on Transmission Planning Criteria 2023, Manual on Transmission Planning Criteria.
[4]Siemens Energy, High-voltage direct current transmission solutions.
[5]Hitachi Energy, Substations.
[6]IEC 62271-205:2008, High-voltage switchgear and controlgear, Part 205: Compact switchgear assemblies for rated voltages above 52 kV.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.