Neutral earthing resistors

A neutral earthing resistor (NGR) connects the neutral of a transformer or a generator to earth through a set resistance. In an earth fault, the fault current returns through it, and its resistance limits that current to a value chosen in the design. It also holds the neutral near earth potential and so limits the overvoltages of an intermittent fault. The ANSI / IEEE standards call it a neutral grounding resistor. This topic explains the task of an NGR, how its current, time rating and resistance are chosen, how it is built, how a neutral is formed where a winding is a delta, and the NGRs of the design. The methods of earthing a neutral are compared in Earthing of the neutral.

Before this topic: Earthing of the neutral · Faults and fault current

1The task of an NGR

An NGR is a purpose-made resistor between the neutral of a network and earth. Its purpose is to limit the earth-fault current and the voltage at the point of the fault (Savostianik, How to size an NGR, §1). A resistor in the neutral adds 3 times its resistance to the zero-sequence impedance, so it dominates the earth-fault current (Earthing of the neutral, The neutral and the earth-fault current). In a bolted earth fault the full phase voltage appears across it.

Limiting the fault current. A limited current causes less heating and mechanical stress in the conductors, the cable screens and the windings. The fault current still operates the protective relays, which clear the fault, usually within a few seconds (Post Glover, Low resistance neutral grounding resistors). The damage at the fault is limited, and further faults are prevented.

Limiting the transient overvoltage. In an unearthed network, or one earthed through too high an impedance, an intermittent earth fault can charge the network's capacitance step by step. The phases and the neutral can then rise to several times the nominal voltage above earth, and insulation fails elsewhere (Savostianik, §1). A resistor in the neutral discharges that capacitance between the strikes of the arc. With the resistor's current at or above the capacitive earth-fault current, the transient overvoltages after re-strikes are reduced (Cook and others, 2019, §II).

2Low-resistance and high-resistance earthing

The current of an NGR places the network in one of 2 classes, which suit different protection.

Low-resistance earthing. The resistor limits the earth-fault current to a moderate level, typically 50 A or more, so that the relays detect the fault and trip it (Post Glover, Low resistance neutral grounding resistors). The relays clear the fault within seconds, and the resistor carries its current for that time.

High-resistance earthing. The resistor limits the current to a few amperes, so that the network can stay in service with an earth fault. A generator is often earthed through a single-phase transformer whose secondary is loaded by a resistor. That resistor is typically sized for a primary earth-fault current of 2 A to 12 A, rated for one minute or continuously (Post Glover, Neutral grounding resistor with transformer). A network that only alarms on an earth fault needs an NGR with a continuous time rating (Savostianik, §2.2).

3The current of an NGR

The let-through current of an NGR, , is the current it passes in a bolted earth fault, with the phase voltage across it. It is the NGR's current rating, and it fixes its resistance (Resistance, voltage and time rating).

The charging current sets the minimum. The network's conductors, cables, transformers and motors have capacitance to earth. The current that flows when one phase of an unearthed network touches earth is the charging current, (Savostianik, §1). To avoid transient overvoltages, the let-through current must be equal to or greater than the charging current (Savostianik, §2.3). Cook and others give the same rule for a resistance-earthed tertiary network, from a technical brochure on shunt reactors (2019, §II). For a planned network, the charging current is estimated from the capacitance of its cables, transformers, machines and capacitor banks. Savostianik gives 1 A per MVA of the supply as an upper estimate for medium-voltage networks (§2.3).

The fault current. In a resistance-earthed network the earth-fault current is the sum of the NGR's current and the charging current (Savostianik, §1). The NGR's current is in phase with the voltage and the charging current leads it by 90°, so the currents add as phasors.

Selectivity sets a higher value. A feeder's earth-fault relay must not trip for a fault on another feeder. Its setting is therefore above the charging current of the largest feeder. To detect a fault through some impedance as well, the let-through current is chosen at 5 times or more of the relay's setting (Savostianik, §3). A low-resistance NGR is therefore rated well above the charging current.

4Resistance, voltage and time rating

An NGR is specified by its voltage, its current and its time rating (Savostianik, §2). It is rated for the network's line-to-neutral voltage, the voltage across it in a bolted earth fault (Savostianik, §2.1). Its resistance is that voltage over its let-through current, , with the nominal phase-to-phase voltage of the network (Earthing of the neutral, The MV system: resistance earthing).

The resistor turns the fault's energy into heat. While the fault lasts it dissipates the power

(1)
Savostianik, How to size an NGR §2.2
where
power dissipated in the NGR at its let-through currentW
let-through current of the NGRA
resistance of the NGRΩ
energy dissipated in the NGR during the faultJ
duration of the current, at most the time ratings

The time rating is the time for which the NGR carries its let-through current, and it must do so repeatedly. For networks that trip on an earth fault, a 10 s rating is typically recommended, and 30 s and 60 s ratings are also available. Alarm-only networks need a continuous rating (Savostianik, §2.2). In the ANSI / IEEE practice, the temperature rise of the resistor follows IEEE C57.32 for the specified duty (Post Glover, Neutral grounding resistor with transformer).

Example 1NGR of the default 220 kV project

Given: the default project's NGR at the 33 kV neutral of an interconnecting transformer (ICT): 1000 A for 10 s, with the resistance of 19.05 Ω that Earthing of the neutral, Example 1 calculates from the phase voltage.

Power at the let-through current, by Eq. (1):

Energy for the time rating: = 19.05 MW × 10 s = 190.5 MJ.

Result: the NGR of 19.05 Ω dissipates 19.05 MW at its let-through current, and 190.5 MJ for its time rating.

5Construction

An NGR is a bank of resistor elements in a ventilated enclosure, insulated from the enclosure for the line-to-neutral voltage. The elements are stamped grids or edge-wound strips of stainless steel, chosen by the current (Post Glover, Zigzag grounding transformers). They are of chromium stainless steel or nickel-chromium alloy, double insulated, and the frames are joined by copper bus (Post Glover, Neutral grounding resistor with transformer). A material with a low temperature coefficient of resistivity keeps the resistance, and so the current, closer to the rating as the elements heat.

The enclosure is for indoor or outdoor installation, of galvanised steel, painted steel or stainless steel. It has lifting eyes, standoff insulators and removable covers, and its openings are screened. The neutral and the earth connections enter by cable or through bushings. A current transformer, with a junction box for its secondary wiring, can be mounted inside, beneath the resistor (Post Glover, Low resistance neutral grounding resistors). It measures the neutral current for the earth-fault protection.

An open NGR leaves the network unearthed: no zero-sequence current flows in an earth fault, and the fault can stay undetected. Heat cycles, corrosion, humidity, dust, vibration and animals are known causes of NGR failure. Continuous monitoring of the NGR guards against an open resistor (Savostianik, §5).

6Earthing transformers

A delta winding has no neutral, and a network fed only from delta windings has no point at which to connect an NGR. An earthing transformer creates a neutral for it, which is earthed directly or, more commonly, through an NGR. Figure 1 draws an NGR at a star neutral and at the neutral of an earthing transformer.

Figure 1.An NGR at the neutral of a star winding, and at the neutral of a zigzag earthing transformer connected to a network fed by a delta winding. The drawing is schematic and not to scale.

The zigzag earthing transformer is a three-phase auto-transformer with no secondary winding (Post Glover, Zigzag grounding transformers). Each phase has 2 windings on different legs, wound so that they present a high impedance to the normal phase currents. In an earth fault the current divides equally between the 3 legs. These zero-sequence currents are in phase, and the zigzag connection presents a low impedance to them. The fault current is then limited by the NGR, the fault's resistance and the zigzag's small reactance.

The earthing transformer is connected on the line side of the main breaker, as close as possible to the power transformer's secondary terminals, one per power transformer. A second earthing transformer is not connected to the same section of the network at the same time. Its rating matches the NGR's: continuous for the charging current, and the NGR's current for the NGR's time rating. The rules for choosing an NGR apply equally to an NGR at such an artificial neutral (Savostianik, §2).

7Standards

IEEE C57.32-2015 sets the requirements, terms and tests for neutral grounding devices. Its scope covers devices that control the ground current or the potentials to ground of an alternating-current network: grounding transformers, ground-fault neutralizers, resistors, reactors and their combinations. NGRs are typically designed to the requirements of IEEE Std 32 and its successor, IEEE C57.32 (Savostianik, §1). IEC 60076-6:2007 covers neutral-earthing reactors and earthing transformers among the reactors. CEA Safety Regulations 2023 permit a neutral earthed through an impedance to limit the fault current, and set no numeric limit for it (Reg. 50(2)).

8In the design

The design earths the neutral of each transformer low-voltage winding that feeds the medium-voltage (MV) bus through an NGR. The Define input NGR rated current sets its let-through current, 1000 A by default. The time rating is fixed at 10 s. The resistance is the MV phase voltage over the rated current, 19.05 Ω in the default project (Example 1).

Bill of materials. The bill of materials (BOM) line "Neutral earthing resistor" specifies 33 kV, 1000 A for 10 s, 19.05 Ω. Its quantity is 2, one per ICT, for the 2 ICTs of the default project. The single-line diagram (SLD) draws the NGR at the ICT's MV star point, designated −R1.

Short-circuit study and checklist. The study adds 3 times the resistance to the zero-sequence impedance of an MV section (Earthing of the neutral, The MV system: resistance earthing). The MV line-to-earth current of the default project is 1097 A, which the checklist compares with 1.15 times the rated current, 1150 A. The checklist item reads Complies.

Earth mat. The earth mat places an electrode at each NGR, 2 in the default project. The mat is designed for the high-voltage (HV) design fault level, 50 kA in the default project, since the NGR limits the MV earth-fault current to its rating (Earthing of the neutral, The neutral and the earth-fault current).

Where the design places no NGR. A generator transformer's low-voltage winding is a delta, and the design places no NGR there. The ICTs of a switching substation are solidly earthed on both sides. At 765 kV, the neutral of a line reactor is earthed through a neutral reactor, not a resistor (Shunt and series reactors, The neutral reactor and single-pole reclosing).

The design calculates no charging current of the collector network, does not compare the NGR's current with it, and specifies no earthing transformer, current transformer or monitor for the NGR.

Review questions
  1. Explain how an NGR limits the transient overvoltage of an intermittent earth fault.
    Answer 1

    It discharges the network's capacitance between the strikes of the arc, and with a current at or above the capacitive earth-fault current the overvoltages after re-strikes are reduced (The task of an NGR).

  2. State the lower limit of an NGR's let-through current and the reason for a higher value.
    Answer 2

    It is at least the network's charging current, and selective earth-fault protection requires 5 times or more of the relay's setting (The current of an NGR).

  3. Calculate the power and the energy of the default project's NGR at its rating.
    Answer 3

    By Eq. (1), = 19.05 MW, and for 10 s the energy is 190.5 MJ (Example 1).

  4. Compare low-resistance and high-resistance earthing.
    Answer 4

    Low-resistance earthing typically passes 50 A or more so that relays trip the fault within seconds, and high-resistance earthing a few amperes that the network can carry with an alarm (Low-resistance and high-resistance earthing).

  5. Describe how a zigzag earthing transformer provides a neutral.
    Answer 5

    It is a three-phase auto-transformer whose zigzag windings present a high impedance to the phase currents and a low impedance to the zero-sequence current, and its neutral is earthed through an NGR (Earthing transformers).

  6. Name the BOM line of the default project's NGRs and their quantity.
    Answer 6

    The line "Neutral earthing resistor" specifies 33 kV, 1000 A for 10 s, 19.05 Ω, quantity 2 (In the design).

Sources

[1]Savostianik, How to size an NGR, Resistance-grounded power systems: Guideline on How to Size a Neutral-Grounding Resistor NGR (Neutral-Earthing Resistor NER). §2.2.

[2]Post Glover, Low resistance neutral grounding resistors, Low Resistance Neutral Grounding Resistors.

[3]Post Glover, Zigzag grounding transformers, Zigzag Grounding Transformers.

[4]Post Glover, Neutral grounding resistor with transformer, Neutral Grounding Resistor with Transformer.

[5]Cook and others, 2019, SDG&E Relay Standards: Updating Tertiary Bus and Reactor Protection.

[6]IEEE C57.32-2015, IEEE Standard for Requirements, Terminology, and Test Procedures for Neutral Grounding Devices.

[7]IEC 60076-6:2007, Power transformers, Part 6: Reactors.

[8]CEA Safety Regulations 2023, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.

[9]IEEE Std 32, IEEE Standard Requirements, Terminology, and Test Procedure for Neutral Grounding Devices.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Neutral earthing resistors, revision 4, 9 Nov 2026, https://substation.solarlayout.app/library/reference/neutral-earthing-resistors