SCADA and substation automation (IEC 61850)

A grid's control centres watch and operate its substations from far away, and a substation's own devices exchange information to protect, interlock and control its bays. Traditional supervisory control and data acquisition (SCADA) links a control centre to a terminal in each substation. Substation automation now joins the protection and control devices of a substation in one network. This topic explains SCADA, the station, bay and process levels of a substation automation system, the IEC 61850 series that standardises its communication, the time synchronisation it needs and the security of its networks. It closes with what the design lists for these systems.

Before this topic: Control and the control room · Current transformers · Voltage transformers and CVTs

1SCADA and the remote terminal unit

The CEA defines SCADA as a system that acquires data from remote locations over communication links and processes it at a central control location for monitoring, supervision, control and decision support (CEA Connectivity Regulations 2007, Reg. 2). In the traditional system, a master station at the energy control centre communicates with a remote terminal unit (RTU) in each substation (RUS Bulletin 1724E-300 §14.1). The RTU has little or no capability of its own to control. The master station takes the control decisions, and the RTU carries them out through its control relays.

The RTU reads the positions of the breakers and the tap changers from contacts on these devices. Transducers convert the measured watts, vars, volts and amperes into analogue signals wired to the RTU. The RTU multiplexes these data and sends them to the master station as serial data (RUS 1724E-300 §14.1).

A substation connected to the grid in India must provide voice and data communication and the transfer of on-line operational data to the load despatch centre. The data include the voltage, the frequency, the line flows and the status of the breakers and isolators (disconnectors, IEC 60050), as Reg. 6(3) of the CEA Connectivity Regulations 2007 lists them. The owner integrates its controls and telemetering into the SCADA system of the state or region (CEA Connectivity Regulations 2007, Reg. 6(5)). A telecontrol protocol carries these data from the substation's gateway to the control centres, and a utility's specification names IEC 60870-5-104 for this link (POWERGRID automation specification §3.3.4).

2Substation automation and its devices

Substation automation uses computers, communications and networks to monitor and control the substation, locally and from remote centres (RUS 1724E-300 §14.1). It keeps the functions of SCADA and adds monitoring and control through devices that have their own processing. An intelligent electronic device (IED) is such a device: a digital relay, a multifunction meter, a digital fault recorder, a sequence of events recorder or a programmable logic controller (RUS 1724E-300 §14.4.2).

An IED often does 2 jobs. It performs its own function, such as protection, and because it is connected to the current and voltage transformers, it also calculates power system data. These data include the power flows, the currents, voltages and symmetrical components, the fault current, the relay targets, the sequence of events and the recorded waveforms. The IEDs deliver them over a network, which removes the separate transducers and their wiring (RUS 1724E-300 §14.4.2).

A utility's specification lists the parts of a substation automation system (SAS) (POWERGRID automation specification §1.2):

  • bay control units, one per bay, for the control and monitoring of the bay's devices
  • merging units and switchgear controllers, in a substation with a process bus
  • the station human-machine interface (HMI) with its servers
  • a redundant switched Ethernet local area network
  • redundant gateways for monitoring and control from the remote control centres
  • disturbance recorder and engineering computers

The station HMI and the bay control units are the control positions of Control and the control room, Control positions and their priority. The protection functions run in their own IEDs, separate from the bay control units (POWERGRID automation specification §3.1).

3Station, bay and process levels

A substation automation system is built on distributed intelligence, with each function placed as close as possible to the process (POWERGRID automation specification §2.2). Its architecture has 3 levels, which Figure 1 shows.

  • Station level. It holds the functions of the whole substation, which a bay cannot perform: the station HMI, the alarm and event lists of the substation and the gateway to the remote control centres.
  • Bay level. The IEDs of each bay perform its control, monitoring and protection. Each bay control unit works independently of the others, so that a fault in one bay's unit does not affect another bay.
  • Process level. It lies in the switchyard, with the instrument transformers and the switchgear. It exists only in a system with a process bus, where merging units send the measured values to the bay level and switchgear controllers connect the switchgear to it.
Figure 1.The levels of a substation automation system. The station bus joins the station level to the bays, and in bay 1 a process bus joins the bay's IEDs to the merging unit and the switchgear controller, while bay 2 keeps its copper wiring. The drawing is schematic and not to scale.

The levels are joined by 2 networks. The station bus carries the SCADA, interlocking and engineering traffic between the station level and the IEDs of the bays, and between the bays. The process bus extends the digital network into the yard, among the primary equipment, for protection and interlocking (Bettler and others, IEC 61850 process bus case studies §I). The terms come from the work on the Utility Communications Architecture in the late 1990s, and they still name 2 overlapping groups of applications.

Optical fibre is immune to electrical interference, which gives it distinct advantages in a substation. RUS 1724E-300 §14.4.5.1 recommends fibre-optic links for the IEDs that perform protection functions. A utility's specification runs the station network over fibre in a fault-tolerant ring, so that the failure of one fibre does not interrupt the communication (POWERGRID automation specification §2.2).

4IEC 61850

IEC 61850 is the series of standards for communication networks and systems for power utility automation. It applies to power utility automation with the substation automation system at its core, and it standardises the communication between IEDs (IEC 61850-5:2013+AMD1:2022, abstract). Before a common standard, manufacturers used their own protocols, and costly interface modules converted between them (RUS 1724E-300 §14.1).

Data model. IEC 61850 models a substation automation system as logical nodes, with their data objects and data attributes (POWERGRID automation specification §2.2). Each logical node has a standard name and represents a function or a piece of primary equipment in the model. The logical node XCBR is the interface to a circuit breaker and XSWI the interface to an isolator. TCTR and TVTR are the interfaces to a current transformer and a voltage transformer (POWERGRID automation specification §7.0). The configuration of the devices is exchanged in the substation configuration language of IEC 61850-6 (POWERGRID automation specification §7.0).

Client-server reports. An operator's commands and the information shown at the HMI pass between the station level and the IEDs as client-server communication, which serves SCADA, metering, monitoring and engineering access (Bettler and others §I). A bay control unit sends its indications to SCADA by these messages, and it puts in GOOSE messages only the signals that other IEDs need (Energy Queensland STNW3046 §6.2).

GOOSE messages. A GOOSE message carries status and control signals from one IED to others, machine to machine (Bettler and others §I). One IED publishes the message on the network, and the IEDs that need it subscribe to it. Interlocking signals between bays travel as GOOSE messages, and on a process bus so do the protection trips (Interlocking between the devices of a bay, Electrical, mechanical and key interlocks; STNW3046 §6.2; POWERGRID automation specification §7.0). A subscribing IED raises an alarm when a GOOSE message it subscribes to fails to arrive. It uses only messages that carry their quality attribute, and it discards duplicated or intruding messages, which it detects from the message's state and sequence numbers (POWERGRID automation specification §3.2.4.7, §6.0).

Sampled values. A merging unit digitises the secondary values of conventional current and voltage transformers and publishes them on the process bus as sampled values (POWERGRID automation specification §7.0). The protection IEDs subscribe to these streams in place of the copper wiring from the instrument transformers. An IED that receives no sampled values, or improper ones, does not perform the functions that use them, and it raises an alarm (POWERGRID automation specification §7.0). A switchgear controller near the breaker and isolators publishes their positions in GOOSE messages and subscribes to the GOOSE messages that carry the commands to them (Bettler and others §II.A).

The devices of a process bus work in the switchyard's temperature, humidity and electromagnetic environment, and they meet the environmental requirements of IEC 61850-3. Redundancy protocols and a network in which the failure of one switch or one fibre interrupts no communication keep the protection in service (POWERGRID automation specification §7.0).

5Time synchronisation

A fault is analysed from events recorded by many devices, often in several substations. The records can be compared only if the devices keep one time. A substation connected to the grid at 220 kV or above has disturbance recording and event logging facilities. This equipment is synchronised to a global common time reference (CEA Connectivity Regulations 2007, Schedule Part I, 5).

A utility's specification requires time synchronisation from a satellite signal of the Global Positioning System (GPS), received at the station level (POWERGRID automation specification §2.2). The bay control units are synchronised over the station network of the automation system. In a substation without that network, a separate time input such as the IRIG-B time code synchronises them (POWERGRID automation specification §4.2.2). Events are time-tagged to a resolution of 1 ms (POWERGRID automation specification §3.2.3).

Sampled values need a closer time reference, because a protection IED combines samples taken by different merging units. Accurate time synchronisation is critical to a process bus with sampled values (Bettler and others §II). The precision time protocol (PTP) of IEEE 1588 provides precise synchronisation of clocks in packet-based networks. A utility's specification synchronises its merging units by PTP over the same Ethernet network that carries the sampled values, without a separate time cable (POWERGRID automation specification §7.0). The station HMI raises an alarm for each device that loses its time synchronisation (POWERGRID automation specification §3.2.4.7).

6Cyber security

The CEA Cyber Security Guidelines 2021 bring the control systems, the communication networks, the protection devices, the RTUs and the programmable controllers of the power sector within their scope (CEA Cyber Security Guidelines 2021 §2.4). They are issued under the CEA Connectivity Regulations, which require compliance with the government's cyber security guidelines (CEA Cyber Security Guidelines 2021 §1.5, §2.0). The guidelines require the hard isolation of operational systems from internet-facing systems, and an electronic security perimeter around the critical systems (CEA Cyber Security Guidelines 2021, Article 1(a), Article 4). Firewalls pass only whitelisted addresses, only the ports and services that operation requires are enabled, and patches are validated and digitally signed by the manufacturer (CEA Cyber Security Guidelines 2021, Article 1(a), Article 5(c)). IEC 62351 is the series of standards for the security of the communication protocols of power systems, IEC 61850 and IEC 60870-5 among them (IEC TS 62351-1:2007, abstract). A utility's specification requires its substation automation system to conform to it, with a firewall between the automation network and the outside networks (POWERGRID automation specification §1.6, §4.1.6).

7In the design

The design does not design the SCADA or the substation automation system. It lists the items that a project's secondary systems must meet, the supply they need and the communication path to the grid.

The compliance checklist of the IEC + CEA / CBIP set carries the items for these systems, which the design does not check, so their status is Needs your answer:

  • real-time data and communication to the load despatch centres, by SCADA, an RTU and the optical fibre of the line's earth wire, under the CEA Connectivity Regulations 2007, Reg. 6(3) and 6(5)
  • substation automation and communication to IEC 61850, Parts 5, 6, 7 and 8

The station service loads include the SCADA, RTU, SAS servers and network, 3 kW of continuous demand (AC auxiliary supply, The load list). The direct current (DC) distribution board has a feeder for the SCADA, RTU and SAS equipment (Control and the control room, In the design). In the IEC + CEA / CBIP set from 66 kV up, a note on the single-line diagram states that the lines carry power line carrier communication (PLCC) through their line traps. The same note states that the optical fibre of the line's earth wire carries the wideband communication (PLCC and fibre communication, In the design).

The design does not choose the IEDs, design the station or process bus, configure IEC 61850 or specify the time synchronisation and cyber security of a project.

Review questions
  1. Describe the roles of the master station and the RTU in a traditional SCADA system.
    Answer 1

    The master station at the control centre takes the control decisions, and the RTU in the substation reports positions and measurements and carries out the commands through its control relays (SCADA and the remote terminal unit).

  2. Name the data a substation sends to the load despatch centre under the CEA Connectivity Regulations.
    Answer 2

    The voltage, the frequency, the line flows and the status of the breakers and isolators, among the on-line operational data of Reg. 6(3) (SCADA and the remote terminal unit).

  3. State the functions of the station, bay and process levels.
    Answer 3

    The station level holds the HMI, the alarm and event lists and the gateway, and the bay level the control, monitoring and protection of each bay. The process level holds the merging units and switchgear controllers in the yard (Station, bay and process levels).

  4. Distinguish a GOOSE message from sampled values.
    Answer 4

    A GOOSE message carries status and control signals published by one IED to the IEDs that subscribe to it, and sampled values carry the digitised currents and voltages from a merging unit (IEC 61850).

  5. Explain why a process bus needs a precise time reference.
    Answer 5

    A protection IED combines sampled values from different merging units, so the samples must share one accurate time, which PTP provides over the same network (Time synchronisation).

  6. Name the standard series for the security of the IEC 61850 communication protocols.
    Answer 6

    IEC 62351, the series of standards for the security of the communication protocols of power systems (Cyber security).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[2]POWERGRID automation specification, Technical Specification, Section: Sub-station Automation System.

[3]Bettler and others, IEC 61850 process bus case studies, Case Studies of IEC 61850 Process Bus Systems Using GOOSE and Sampled Values: Recent Installations and Research.

[4]CEA Connectivity Regulations 2007, Central Electricity Authority (Technical Standards for Connectivity to the Grid) Regulations, 2007.

[5]CEA Cyber Security Guidelines 2021, CEA (Cyber Security in Power Sector) Guidelines, 2021.

[6]Energy Queensland STNW3046, Substation Standard STNW3046: Standard for Interlocking.

[7]IEC 61850, Communication networks and systems for power utility automation.

[8]IEC 62351, Power systems management and associated information exchange, Data and communications security, Part 1: Communication network and system security, Introduction to security issues.

[9]IEC 60870-5-104, Telecontrol equipment and systems, Part 5-104: Transmission protocols, Network access for IEC 60870-5-101 using standard transport profiles.

[10]IEEE 1588, IEEE Standard for a Precision Clock Synchronization Protocol for Networked Measurement and Control Systems.

[11]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, SCADA and substation automation (IEC 61850), revision 4, 9 Nov 2026, https://substation.solarlayout.app/library/reference/substation-automation