Circuit breakers
A circuit breaker is the switching device that clears a fault. It closes and opens its circuit under load and under fault, and it carries the fault current until it opens. This topic explains how a breaker interrupts the current, the media and mechanisms that do the work, and the ratings that specify a breaker. It closes with the breakers the design specifies for the high-voltage (HV) yard and the medium-voltage (MV) switchgear.
Before this topic: Faults and fault current · Bays and their equipment
1What a circuit breaker does
A circuit breaker closes and interrupts an electric circuit between separable contacts, under both load and fault conditions (RUS Bulletin 1724E-300 §5.3.1). It has 3 duties. It makes the current when it closes, it carries the current while closed, and it breaks the current when it opens. The fault current is the hardest case of each duty.
Other switching devices share some of these duties. An isolator (disconnector, IEC 60050) isolates a circuit, and it opens or closes only at a negligible current (Isolators and earth switches). A load switch makes and breaks normal currents but not a short-circuit current. The circuit breaker is the general-purpose device, because it makes, carries and breaks currents under normal and abnormal conditions (Cahier Technique 193 §1).
A breaker opens on a trip signal from relays, which sense the fault through current transformers. Its ratings follow from studies of the load flow, the short-circuit currents, the transient voltages and the protection (RUS 1724E-300 §5.3.1.1).
2The arc and its interruption
A mechanical breaker cannot interrupt a current without an arc. Its contacts cannot part at the instant the current passes through zero. A current whose root-mean-square value (RMS) is 10 kA at 50 Hz still has an instantaneous value of 4.4 kA at 1 ms before its zero. If the gap became an insulator at once, the circuit's inductance would drive the voltage across the gap high enough to break it down (Cahier Technique 193 §2.1).
When the contacts part, the current continues through an arc. The arc is a column of plasma, made of ions and electrons of the medium or of metal vapour from the contacts. It stays conductive while the energy it dissipates keeps it hot. The arc voltage stays well below the network voltage, so the current runs on to its next natural zero.
At current zero, the arc's input of energy stops for an instant. The interruption succeeds when the medium cools and becomes insulating faster than the voltage across the gap rises. 2 conditions determine it (Cahier Technique 193 §2.1):
- Thermal interruption. Directly after current zero, a small post-arc current still flows. If the power it dissipates exceeds the medium's cooling, the gap heats up again and conducts, which is a thermal failure.
- Dielectric recovery. The dielectric strength of the gap must then rise faster than the voltage across it, or the gap breaks down again.
The voltage that appears across the contacts after interruption is the recovery voltage. While it oscillates towards the network voltage, it is called the transient recovery voltage (TRV). In an inductive circuit, the network voltage is near its peak when the current passes through zero, so the TRV rises fast, at several kilovolts per microsecond. A breakdown within a quarter cycle after current zero is a re-ignition, and a later one is a restrike. The standards assign a rated TRV to each rated voltage, and a breaker's breaking capacity is the largest current it breaks at its rated voltage with that TRV.
3Interrupting media
The medium between the contacts does the work of interruption. It must carry away the arc's heat, recover its dielectric strength fast, conduct well while hot and insulate well when cold (Cahier Technique 193 §3.1). These media have been used:
- Air at atmospheric pressure lengthens and cools the arc in a chamber of refractory plates. It is limited to approximately 24 kV. Compressed air, blown at 20 bar to 40 bar, has been used up to 800 kV (Cahier Technique 193 §3.2).
- Oil is decomposed by the arc into a bubble of mainly hydrogen, which blows out the arc at current zero. Oil breakers were used from 5 kV to 150 kV (Cahier Technique 193 §3.3), and they are now available only as remanufactured or used equipment (RUS 1724E-300 §5.3.2).
- Vacuum has no gas to ionise, and the arc burns in metal vapour from the contacts. The gap recovers fast, but the contact gap needed for dielectric strength grows fast above 30 kV to 50 kV (Cahier Technique 193 §3.4). Vacuum breakers are mainly used at MV. RUS 1724E-300 §5.3.2, of 2001, lists outdoor vacuum breakers for voltages up to 38 kV.
- SF6 is an electronegative gas with a de-ionisation time constant of 0.25 ms. It is more commonly used from 34.5 kV to 765 kV (RUS 1724E-300 §5.3.2), and at extra-high voltage it is practically the only medium (Cahier Technique 193 §3.6).
An SF6 interrupter blows gas along the arc as the current approaches zero. Figure 1 shows the principle of the puffer interrupter. The moving contact carries a cylinder over a fixed piston, and the opening travel compresses the gas in it. The compressed gas flows through an insulating nozzle along the arc and out through the hollow contact. The arc is cooled and then extinguished by fresh gas at current zero (Cahier Technique 193 §3.5).
The puffer principle takes its blowing energy from the operating mechanism, so it needs a strong mechanism. A self-blast interrupter, also called self-expansion, uses the arc's own heat. At high currents, the arc heats the gas in a closed volume and raises its pressure. At current zero, this gas expands through the nozzle and blows out the arc (Cahier Technique 193 §3.5). The breaker then needs mechanical energy only to move its contacts (Siemens High-Voltage Products, Circuit-Breakers). A self-blast interrupter is often combined with a piston that assists at low currents, and the combination is used at MV and HV (Cahier Technique 193 §3.5).
4Operating mechanisms
The operating mechanism stores the energy that opens and closes the contacts. It must open the breaker on a trip signal from any position, and close and latch it against the rated short-circuit current (RUS 1724E-300 §5.3.4). These kinds are in use:
- Spring. A motor compresses a closing spring and holds it charged. On a close signal, the spring closes the breaker and at the same time charges the opening spring. The stored energy is enough for an open-close-open sequence, and the motor recharges the closing spring within 10 s (RUS 1724E-300 §5.3.4.5).
- Hydraulic. Energy stored at high pressure drives hydraulic fluid into a servomechanism that closes and trips the breaker. In the pneumohydraulic form, compressed air pressurises the fluid, and the stored energy suffices for at least 5 close-open operations at rated short-circuit current (RUS 1724E-300 §5.3.4.3).
- Pneumatic. Compressed air or gas applies the closing and tripping forces directly. Air stored on the breaker suffices for at least 2 close-open operations at rated short-circuit current (RUS 1724E-300 §5.3.4.4).
In RUS 1724E-300 §5.3.4.5, of 2001, the spring mechanism serves the lower voltages, up to 72.5 kV. A self-blast interrupter needs less operating energy than a puffer interrupter. One manufacturer lists spring-operated SF6 breakers from 72.5 kV to 800 kV, and hydraulic mechanisms for its breakers of 80 kA breaking current (Siemens High-Voltage Products, Circuit-Breakers).
A breaker's 3 poles are either ganged to one mechanism or operated each by its own mechanism. With independent-pole operation, each pole has its own means to trip (RUS 1724E-300 §5.3.2). The mechanism carries an operation counter, a device for slow closing during maintenance, and a lock that guards maintenance staff from an unintended operation (RUS 1724E-300 §5.3.4).
5Dead-tank and live-tank breakers
An outdoor HV breaker is built in one of 2 ways, shown in Figure 2. In a live-tank breaker, the interrupter's housing stands on an insulator column and is at line potential. In a dead-tank breaker, the interrupter is inside an earthed metal tank, and the line connects to it through bushings (RUS 1724E-300 §5.3.2).
The dead tank has its advantages where several current transformers are needed per pole. Ring-core current transformers fit around its bushings, which makes the breaker compact. Its low centre of gravity also gives it a high seismic withstand (Siemens High-Voltage Products, Dead-Tank Circuit-Breakers). RUS 1724E-300 §5.3.2 states that most breakers above 242 kV are live-tank breakers, and that dead-tank breakers are also in use there.
6Ratings
A breaker's rating summarises its characteristics in terms of voltage, current and time (RUS 1724E-300 §5.3.3). The IEC and the ANSI / IEEE standards name the ratings differently, with close meanings:
- Rated voltage, the highest voltage for equipment in IEC terms and the rated maximum voltage in ANSI / IEEE terms. It is the upper limit of operation (RUS 1724E-300 §5.3.3.1.2).
- Rated insulation level, the power-frequency and lightning impulse withstand voltages, with a switching impulse level at the highest voltages.
- Rated normal current, the continuous current in ANSI / IEEE terms. It is the RMS current the breaker carries continuously within its temperature limits (RUS 1724E-300 §5.3.3.2.1).
- Rated short-circuit breaking current, the RMS value of the symmetrical current the breaker interrupts at its rated voltage (RUS 1724E-300 §5.3.3.2.3).
- Rated short-circuit making current, the peak current the breaker closes and latches against.
- Rated short-time withstand current and its duration, the current the breaker carries while closed. One manufacturer's ratings give durations of 1 s to 3 s (Siemens High-Voltage Products, Live-Tank Circuit-Breakers).
- Rated operating sequence, the duty of openings and closings the ratings apply to.
- Rated break time, the interrupting time in ANSI / IEEE terms, from the energising of the trip coil to the interruption in all poles (RUS 1724E-300 §5.3.3.3).
The making current is a peak. A breaker that closes onto a fault meets the current's first peak, which the direct current (DC) component raises towards twice the alternating current (AC) peak (Faults and fault current, The fault current and its components). With a DC time constant of 45 ms at 50 Hz, that peak can reach 2.5 times the RMS breaking current (Cahier Technique 193 §2.3). IEEE C37.04-2018 rates the closing and latching current as a multiple of the rated short-circuit current :
| rated short-circuit current of the breaker, RMS symmetrical | kA | |
| rated closing and latching current, peak | kA |
The factors hold for a DC time constant up to the rated 45 ms. A network of higher X/R has a longer time constant and a higher first peak. For a time constant above 45 ms and up to 133 ms, the rated closing and latching current is 2.7 times (IEEE C37.04-2018 §5.6.2.3). IEC 62271-100:2008 §4.103 sets the same 2.5 at 50 Hz and 2.6 at 60 Hz for the rated short-circuit making current.
The operating sequence states the duty of a breaker that recloses. O is an opening, and CO a closing followed at once by an opening. The IEC sequence for a breaker with rapid auto-reclosing is O – 0.3 s – CO – 3 min – CO. For a breaker without it, the sequence is O – 3 min – CO – 3 min – CO or CO – 15 s – CO (Cahier Technique 193 §2.3). RUS 1724E-300 §5.3.3.5 gives the standard duty cycle of the ANSI / IEEE practice as CO, a 15 s wait, and CO. A heavier duty derates the interrupting capability. One manufacturer's HV SF6 breakers have rated break times of 2 or 3 cycles (Siemens High-Voltage Products, Circuit-Breakers).
7Metal-clad switchgear with withdrawable breakers
At MV, the breakers sit in switchgear, a line of panels indoors or in an outdoor enclosure. In the ANSI / IEEE practice, RUS 1724E-300 §5.4.1 describes metal-clad switchgear by these characteristics:
- the main switching device is removable, so it can be withdrawn from the panel
- the major parts of the primary circuit are in compartments separated by earthed metal barriers
- automatic shutters cover the live parts when the device is withdrawn
- the primary bus is covered with insulating material throughout
- mechanical interlocks secure safe and correct operation
The breaker in such a panel is predominantly a vacuum circuit breaker (VCB) (RUS 1724E-300 §5.4.1.2). Withdrawing the breaker disconnects it from the primary circuit, and the shutters then cover the live parts (RUS 1724E-300 §5.4.1).
8SF6 and the environment
SF6 is chemically inert, non-toxic and non-flammable in its pure state. The arc decomposes some of it, and most of the decomposed gas recombines as the arc cools. The small amounts of by-products are absorbed by materials placed in the enclosure for this purpose (Cahier Technique 193 §3.5).
SF6 is also a strong greenhouse gas. Over 100 years, it is 23 500 times as effective as carbon dioxide at trapping infrared radiation, and its atmospheric lifetime is more than 1000 years. High-voltage breakers are its largest use in the power industry. It escapes through leaks during manufacture, installation, maintenance and decommissioning. Leak detection and repair, recycling equipment and trained staff reduce these emissions (EPA SF6 Basics).
An SF6 breaker therefore has a density monitor, with relays for an alarm and a lockout of the breaker as the gas density falls (Siemens High-Voltage Products, Circuit-Breakers).
9In the design
The design specifies the breakers of a project and checks them against the short-circuit study. It sets each breaker's ratings from the voltage level: the highest voltage for equipment , the basic lightning impulse insulation level (BIL), the design fault level with its duration, and the rated current of the bay or the bus. The design fault level is the short-circuit current the HV switchgear is rated to carry for its duration and to interrupt. The bill of materials (BOM) prints the same voltage and fault ratings on a bay's breaker, isolators and instrument transformers.
The short-circuit study checks 3 of the breaker's duties at the HV and MV buses (Peak current and thermal equivalent current, The switchgear rating checks):
| Check | HV bus | HV rating | Result |
|---|---|---|---|
| Breaking current against the initial current | 22.95 kA | 50 kA | Pass |
| Making current against the peak current | 64.90 kA | 125 kA | Pass |
| Short-time current against the thermal current for 1 s | 23.50 kA | 50 kA | Pass |
The making rating is 2.5 times the rated breaking current at 50 Hz, by IEC 62271-100:2008 §4.103 in the IEC + CEA / CBIP set and by Eq. (1) in the ANSI / IEEE set. The design takes this factor of the rated 45 ms time constant in both sets, and not the 2.7 of a longer one. It compares the calculated peak current with the making rating. A bus of high X/R raises , and the check fails when exceeds the rating. At the default MV bus, the same checks give a peak current of 68.98 kA against a making rating of 78.75 kA. A switching substation steps its design fault level up to the next standard rating, because the other HV side feeds the fault through the interconnecting transformers (ICTs).
10Breaker ratings per level in the IEC + CEA / CBIP set
The CEA Construction Regulations 2022 set and the lightning impulse withstand per level (Reg. 45(1), Table 9, and Reg. 50(1), Table 14 for 33 kV). They set a minimum short-time withstand per level at 66 kV and above (Reg. 43(1), Table 6). The design's ratings of a new pooling project are these:
| Level | BIL | Design fault level | Main bus | Bays | |
|---|---|---|---|---|---|
| 33 kV | 36 kV | 170 kVp | 25 kA, 3 s | 1250 A | 800 A |
| 66 kV | 72.5 kV | 325 kVp | 31.5 kA, 1 s | 1250 A | 800 A |
| 132 kV | 145 kV | 650 kVp | 40 kA, 1 s | 2000 A | 1250 A |
| 220 kV | 245 kV | 1050 kVp | 50 kA, 1 s | 3150 A | 1600 A |
| 400 kV | 420 kV | 1425 kVp | 63 kA, 1 s | 4000 A | 3150 A |
At 400 kV the equipment also carries a switching impulse withstand voltage (SIWL) of 1050 kVp. A 33 kV HV level is the HV side of a 33/11 kV substation, and its fault level lasts 3 s as the MV switchgear's does. The user can enter the design fault level of the project, and the short-circuit study then checks the calculated currents against that value.
11Breaker ratings per level in the ANSI / IEEE set
The ANSI / IEEE set takes the rated maximum voltage and the BIL of its levels from IEEE C37.04-2018 Table 6. Its design fault level is one of the rated short-circuit currents that Tables 12 and 16 list at the level's rated maximum voltage. The bus and bay currents are continuous currents listed on the line of that short-circuit current.
| Level | Rated maximum | BIL | Design fault level | Main bus | Bays | Rated short-circuit currents listed |
|---|---|---|---|---|---|---|
| 69 kV | 72.5 kV | 350 kVp | 31.5 kA, 2 s | 2000 A | 1200 A | 20, 31.5, 40, 50 and 63 kA |
| 115 kV | 123 kV | 550 kVp | 40 kA, 1 s | 2000 A | 2000 A | 31.5, 40, 50 and 63 kA |
| 138 kV | 145 kV | 650 kVp | 40 kA, 1 s | 2000 A | 2000 A | 31.5, 40, 50, 63 and 80 kA |
| 161 kV | 170 kV | 750 kVp | 40 kA, 1 s | 2000 A | 2000 A | 31.5, 40, 50, 63, 80 and 100 kA |
| 230 kV | 245 kV | 900 kVp | 50 kA, 1 s | 3000 A | 2000 A | 31.5, 40, 50, 63 and 80 kA |
| 345 kV | 362 kV | 1300 kVp | 50 kA, 1 s | 3000 A | 2000 A | 40, 50 and 63 kA |
At 345 kV the equipment carries a basic switching impulse insulation level (BSL) of 825 kVp. The rated short-time duration is the maximum permissible tripping delay: 2 s below 100 kV and 1 s at 100 kV and above (IEEE C37.04-2018 Tables 12 and 16).
The design does not choose the breaker's interrupting time. The short-circuit study takes the rated interrupting times IEEE C37.04-2018 lists for the rated maximum voltage, and the larger duty where 2 are listed: 3 or 5 cycles at 69 kV, 3 cycles at 115 kV, and 2 or 3 cycles from 138 kV to 345 kV (Short-circuit duty by IEEE C37.010).
12HV circuit breakers of the design
The HV breaker in a yard of air-insulated switchgear (AIS) is an SF6 circuit breaker, three-pole and spring operated. It is rated at the level's voltage, its design fault level and the bay current. The number of breakers follows the bus scheme: one per circuit and one for the coupler or bus section, or 3 per full diameter of a one-and-a-half breaker scheme (Bus schemes, Bus schemes of the IEC + CEA / CBIP set).
The BOM carries one spare interrupter pole per breaker type. The bay's current transformers are a separate BOM line of single-phase units. In a yard of gas-insulated switchgear (GIS), the breakers are part of the GIS bay modules (Gas-insulated switchgear (GIS)). The single-line diagram (SLD) names the breaker −Q0 in the IEC + CEA / CBIP set, and 52 in the ANSI / IEEE set after IEEE C37.2-1996.
13MV switchgear
The MV switchgear connects the transformers' low-voltage windings to the plant's collector feeders. The design offers indoor switchgear or an outdoor MV AIS yard. Indoor switchgear is a line of metal-enclosed panels in the control building, each with a withdrawable VCB (Metal-clad switchgear with withdrawable breakers). The checklist of the IEC + CEA / CBIP set has an item for type-tested, internal-arc-classified switchgear. An outdoor bay carries a VCB, 2 isolators, a current transformer and a surge arrester.
The MV bus is sectionalised, one section per transformer low-voltage winding, and the bus-section breakers are normally open. Each section has its incomer, its plant feeders, the reactive power and harmonic filter feeders and a bus voltage transformer panel. Sections 1 and 2 also feed the auxiliary transformers. The plant feeders and the spare feeder panels for future circuits are each spread evenly over the sections, the first sections taking any remainder. An indoor bus section takes a pair of panels, the breaker and a riser.
The panels share the MV level's ratings. The incomer's rated current is the smallest current of the standard series 630, 800, 1250, 1600, 2000, 2500, 3150, 4000, 5000 and 6300 A at or above the full-load current of one low-voltage winding. The bus of each section has at least the incomer's rating, because one transformer's full current can flow along the section to its incomer. The plant feeders carry a fixed rating per MV level.
| MV level | BIL | Design fault level | Feeder breaker | Indoor switchgear up to | |
|---|---|---|---|---|---|
| 33 kV | 36 kV | 170 kVp | 31.5 kA, 3 s | 1250 A | 4000 A |
| 11 kV | 12 kV | 75 kVp | 25 kA, 3 s | 630 A | 4000 A |
| 34.5 kV | 38 kV | 200 kVp | 40 kA, 2 s | 1200 A | 4000 A |
An incomer current above the indoor switchgear's top rating raises a warning. The warning advises outdoor switchgear, a lower transformer rating or more transformers. In the ANSI / IEEE set the MV breakers take the IEEE C37.04-2018 class of their system. Indoor switchgear feeds the collector cables and takes the class for cable systems, with currents 1200, 2000, 3000 and 4000 A at its rated maximum voltage. An outdoor MV yard takes the class for line systems of Table 12, with currents 1200, 2000 and 3000 A.
Given: the default project, a 220 kV double main bus with 1 line bay and 2 ICTs of 160 MVA, and a 33 kV bus in 2 sections with indoor switchgear.
HV ratings of the level: 245 kV, BIL 1050 kVp, 50 kA for 1 s, bays 1600 A, main bus 3150 A.
HV breakers, from the BOM: 4 SF6 circuit breakers, three-pole, and 1 spare interrupter pole.
MV incomer by the full-load current of one low-voltage winding, of rating at the MV voltage :
The smallest standard current at or above it is 3150 A, and the bus of each section takes the same 3150 A.
Result: the 220 kV yard has 4 breakers. The 33 kV switchgear has 2 incomers of 3150 A, 17 feeder panels of 1250 A and 1 bus-section panel set, rated 31.5 kA for 3 s.
Given: a new 230 kV pooling project of the ANSI / IEEE set at 60 Hz, with a one-and-a-half breaker scheme, 2 transformers of 168 MVA and a 34.5 kV collector bus.
HV ratings: rated maximum voltage 245 kV, BIL 900 kVp. At that voltage, IEEE C37.04-2018 Table 16 lists the rated short-circuit currents 31.5, 40, 50, 63 and 80 kA, and the design takes 50 kA for 1 s. The bays take 2000 A and the main bus 3000 A.
HV breakers: 5 SF6 circuit breakers.
MV incomer: one winding carries 2811 A at 34.5 kV. The smallest cable-system current at or above it is 3000 A, rated 40 kA for 2 s at 38 kV.
Result: the breakers are rated 50 kA at 245 kV, and the MV incomers 3000 A.
14What the design leaves to the specification
The design sets the ratings that follow from the voltage level, the fault level and the circuit currents. It does not choose a make, the tank type, the operating sequence or the breaker's interrupting time. The ANSI / IEEE short-circuit study covers the interrupting time by taking the larger duty of the listed times. SubstationLayout sets no protection relays and no reclosing. The makes of each item are kept in the Library and print beside the BOM.
- Explain why a mechanical breaker interrupts the current at a current zero and not at the instant its contacts part.
Answer 1
The contacts cannot part at the instant of zero, and a gap that became insulating at once would break down under the circuit's inductive voltage, so the current continues as an arc until the next current zero (The arc and its interruption).
- State the 2 conditions for a successful interruption at current zero.
Answer 2
The medium's cooling must exceed the power of the post-arc current, and the gap's dielectric strength must then rise faster than the transient recovery voltage (The arc and its interruption).
- Compare the puffer and the self-blast principles of an SF6 interrupter.
Answer 3
A puffer interrupter compresses the gas with a cylinder and piston driven by the mechanism, while a self-blast interrupter uses the arc's heat to raise the gas pressure, so it needs less operating energy (Interrupting media).
- Distinguish a dead-tank breaker from a live-tank breaker.
Answer 4
A live-tank breaker's interrupter is at line potential on an insulator column, and a dead-tank breaker's interrupter is in an earthed tank with the line connected through bushings (Dead-tank and live-tank breakers).
- Give the IEC rated operating sequence of a breaker for rapid auto-reclosing.
Answer 5
O – 0.3 s – CO – 3 min – CO, where O is an opening and CO a closing followed at once by an opening (Ratings).
- Check the making current of the default project's HV breakers.
Answer 6
The peak current of 64.90 kA is within the making rating of 125 kA, 2.5 times the 50 kA breaking rating (In the design).
[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.
[2]Cahier Technique 193, Cahier Technique no. 193: MV breaking techniques.
[3]Siemens High-Voltage Products, High-Voltage Products.
[4]EPA SF6 Basics, Sulfur Hexafluoride (SF6) Basics.
[5]IEEE C37.04-2018, IEEE Standard for Ratings and Requirements for AC High-Voltage Circuit Breakers. §5.6.2.3.
[6]IEC 62271-100:2008, High-voltage switchgear and controlgear.
[7]CEA Construction Regulations 2022, Central Electricity Authority (Technical Standards for Construction of Electrical Plants and Electric Lines) Regulations, 2022.
[8]IEEE C37.2-1996, Standard Electrical Power System Device Function Numbers.
[9]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.