Ampacity of conductors
The ampacity of a bare conductor is the continuous current at which it reaches its limiting temperature in the assumed weather. The rating rests on a balance of heat: the current and the sun heat the conductor, and the air carries the heat away by convection and radiation. This topic takes the balance of Busbars and conductors, Eq. (2) apart, term by term, in the forms of IEEE Std 738 and CIGRE Technical Brochure 601 as published applications of them write it. It then shows how wind, ambient temperature, emissivity and the sun change the result, what sets the limiting temperature, and how the method applies to a tubular bus. A worked example rates a tube of the typical size of the default project's main bus, and the last section gives the rating the design calculates.
Before this topic: Busbars and conductors · Bus and bay current ratings
1The heat balance and the rating
A conductor in the steady state neither gains nor loses heat. The heat generated in it per metre equals the heat it gives to the surroundings per metre (Busbars and conductors, Eq. (2)). The current enters the balance only through the Joule heat . All the other terms depend on the conductor's temperature , the ambient temperature , the weather and the surface. A rating calculation therefore fixes at the limiting temperature, evaluates the other terms, and solves for the current:
| continuous current rating of the conductor, root-mean-square value | A | |
| heat lost by convection per metre | W/m | |
| heat lost by radiation per metre | W/m | |
| heat gained from the sun per metre | W/m | |
| alternating-current resistance per metre at the conductor temperature | Ω/m | |
| conductor temperature, the limiting temperature for a rating | °C | |
| ambient air temperature | °C |
The same equation solved the other way gives the conductor's temperature for a known current. That calculation needs an iteration, since appears inside each term (Kanálik and others 2019 §2). IEEE Std 738 and CIGRE TB 601 both write this balance, as the sources that apply them show. They differ in the empirical forms of the convective and solar terms. Kanálik and others report Schmidt's comparison of the 1993 IEEE method and the 1992 CIGRE method, which gave similar results (Kanálik and others 2019 §1). The Abboud and others study of the Idaho National Laboratory applies the IEEE forms, and the Energy Queensland busbar standard STNW3014 applies the TB 601 forms. The IEEE forms in this topic are those of IEEE Std 738-2012, which IEEE Std 738-2023 has superseded. Figure 1 shows the 4 terms on the cross-section of a tube.
2Resistance and Joule heating
The Joule heat per metre is . The resistance rises with temperature, so a hotter limit gains less current than the rise of temperature suggests. STNW3014 takes the direct-current resistance at 20 °C and corrects it linearly:
| resistivity of the conductor material at 20 °C | Ω·m | |
| outside diameter of the conductor | m | |
| inside diameter of a tube, 0 for a solid round conductor | m | |
| temperature coefficient of resistance at 20 °C | 1/°C |
The first factor is the resistance per metre of the tube's annular cross-section. For a stranded conductor, STNW3014 takes the supplier's resistance at 20 °C in its place. Alternating current crowds towards the surface of a conductor (skin effect) and redistributes under the field of a nearby conductor (proximity effect), which raises the resistance. STNW3014 multiplies the resistance by a factor for both effects. It finds the skin effect negligible for the tubes and the stranded conductors it lists, except one stranded conductor of 673 mm² (STNW3014 §6.1.3, Annex A.2). RUS Bulletin 1724E-300 finds the proximity losses negligible at a spacing of 45.7 cm or more (Busbars and conductors, Current rating).
3Radiation
A warm surface radiates heat in proportion to the fourth power of its absolute temperature. The conductor radiates to the sky and the ground and receives radiation from them at the ambient temperature. The net loss per metre, in the form IEEE Std 738 uses, is
| emissivity of the conductor surface | ||
| Stefan–Boltzmann constant, | W/(m²·K⁴) |
The constant 17.8 comes from the Stefan–Boltzmann law. A surface of area per metre radiates , with in kelvin. Writing as moves the factor into the constant, and . Kanálik and others give the TB 601 form of the same loss as (Kanálik and others 2019 Eq. 23).
The emissivity is the ratio of the power the surface radiates to that of a black body at the same temperature. It rises as the surface weathers. Kanálik and others give, after TB 601, 0.2 to 0.3 for a new conductor and 0.8 to 0.9 for one weathered in an industrial or heavy agricultural environment (Kanálik and others 2019 §2). RUS Bulletin 1724E-300 takes 0.5 for weathered aluminium and 0.8 for weathered copper (RUS 1724E-300 §4.10.4).
4Solar heating
The sun heats the conductor in proportion to the radiation it intercepts and to the share its surface absorbs. Kanálik and others give the TB 601 form of the gain per metre as
| solar absorptivity of the conductor surface | ||
| global solar radiation on the conductor | W/m² |
Abboud and others write the IEEE Std 738 gain as a product of 4 factors (Abboud and others 2018 Eq. 8). They are the absorptivity, the solar and sky heat flux corrected for elevation, the sine of the effective angle of the sun's rays, and the projected area per metre. STNW3014 builds from the direct and the diffuse radiation, the sun's altitude and azimuth, the clearness of the sky and the albedo of the ground (STNW3014 Annex A.1.1.3). The albedo is the share of the radiation the ground reflects. STNW3014 gives 0.2 for grass, 0.4 for concrete and 0.25 to 0.4 for the crushed rock of many substations, depending on its colour and size (STNW3014 §5.1.4).
The absorptivity also rises as the surface weathers, from 0.2 for a bright new conductor to 0.9 for a weathered one in an industrial environment (Kanálik and others 2019 §2). STNW3014 sets the absorptivity equal to the emissivity. It takes 0.85 for aged conductors, accepts 0.5 for aluminium in rural areas and avoids values below 0.5 (STNW3014 §5.1.3).
5Convection
Convection is the heat carried away by the air flowing past the surface. It is usually the largest loss, even in still air (Kanálik and others 2019 §2). The wind drives forced convection. In still air, the air warmed at the surface rises and draws cooler air in, which is natural convection.
Forced convection. IEEE Std 738 gives the forced loss by 2 empirical equations:
| wind speed | m/s | |
| density of air | kg/m³ | |
| dynamic viscosity of air | kg/(m·s) | |
| thermal conductivity of air | W/(m·°C) | |
| wind direction factor |
The group is the Reynolds number of the flow around the conductor. The properties of the air are taken at the film temperature, the mean of and . Statnett's linerate documentation reports that IEEE Std 738-2012 finds the first equation correct at low wind speeds and the second at high ones, and takes the larger of the two (Statnett linerate, IEEE 738 convective cooling). The wind direction factor is 1.0 for a wind square to the conductor and 0.388 for a wind along it (Abboud and others 2018 Eq. 12).
Natural convection. In still air the loss is
As linerate reports and implements IEEE Std 738-2012, the forced and the natural loss are both calculated, and the larger is (Statnett linerate, IEEE 738 convective cooling).
The TB 601 form. STNW3014, applying CIGRE TB 601, expresses convection through the Nusselt number , the ratio of the heat convected to the heat conducted through the air. Its thermal conductivity of air is , the quantity IEEE Std 738 calls :
| thermal conductivity of air at the film temperature | W/(m·°C) | |
| Nusselt number | ||
| Reynolds number | ||
| , | constants for the range of and the surface | |
| kinematic viscosity of air at the film temperature | m²/s |
The constants and change with the range of the Reynolds number and differ for smooth and stranded surfaces. A wind at an angle to the conductor multiplies the Nusselt number by a factor of the angle (STNW3014 Annex A.1.1.2, Table 10). Natural convection takes its own Nusselt number from the product of the Grashof and Prandtl numbers (Kanálik and others 2019 Eq. 17 to Eq. 20). The air's density in both forms falls with the altitude, which lowers the convective loss and with it the rating (STNW3014 §5.1.5).
6Effect of the conditions
The terms respond to the conditions in different ways. The wind enters only the forced convection, through the Reynolds number raised to a power of 0.47 to 0.81. The rating therefore rises with the wind, but less than in proportion. Abboud and others note that the error in the cooling rate scales approximately as the square root of the wind speed (Abboud and others 2018, Introduction). A 10 % error in the wind then gives a 5 % error in the cooling. A wind along the conductor cools far less than one across it, through .
The ambient temperature enters the convective and radiative losses through the difference . A hotter day narrows that difference, so the rating falls. The emissivity raises the radiative loss, and an equal absorptivity raises the solar gain. RUS Bulletin 1724E-300 notes that the ampacity is usually higher for a greater emissivity (RUS 1724E-300 §4.10.4).
The sun adds heat that the current can no longer supply, so a rating with the sun is lower than a rating at night. For these reasons the rating conditions are stated with the rating. Kanálik and others report the conditions that the European standard for overhead lines above 45 kV takes for a line's rating (Kanálik and others 2019 §6). They are an ambient temperature of 35 °C, 1000 W/m² of sun, a wind of 0.5 m/s at 45° to the conductor, and 0.5 for the absorptivity and the emissivity. STNW3014 does not take a wind below 0.5 m/s, since natural convection removes heat at a rate similar to that wind (STNW3014 §5.1.6). the table shows the size of each effect on the tube of Example 1.
7The limiting temperature
The limiting temperature is chosen, not calculated. Above it, the conductor or what it connects to is damaged, or a strung conductor sags below its clearance. Aluminium oxidises at its surface and anneals, losing strength, if it runs too hot. The limit RUS Bulletin 1724E-300 gives for a bus conductor is in Busbars and conductors, Current rating. The bulletin notes that higher operating temperatures are a trend, that rises of 50 °C and more have been used, and that temperatures that damage the conductor or the connected equipment are to be avoided (RUS 1724E-300 §4.10.4).
For a line, the maximum temperature limits the sag of the spans between structures (Abboud and others 2018, Introduction). Kanálik and others report a range of 90 °C to 110 °C for the maximum temperature of aluminium conductor steel-reinforced (ACSR) from its makers (Kanálik and others 2019 §6). By their account, the European standard for overhead lines recommends no less than 70 °C. STNW3014 rates its busbars and connections at 90 °C in continuous operation and allows 100 °C for a defined emergency (STNW3014 §5.3.2). During a short circuit a conductor may reach a much higher temperature for a short time, 250 °C in STNW3014's short-time rating (STNW3014 Annex A.4). That is a separate rating, set by the thermal equivalent current over the fault's duration (Peak current and thermal equivalent current, The thermal equivalent current).
8Ampacity of tubes
A tube is rated by the same balance, with 3 points that differ from a stranded conductor. Its surface is smooth, so the convection takes the constants of a smooth conductor. Its resistance is that of the annulus between its outside and inside diameters (Eq. (2)). Its wall is thin compared with its diameter, so the skin effect stays small, and STNW3014 finds it negligible for its tubes (STNW3014 §6.1.3).
For a given cross-section of metal, a tube of larger diameter cools better, since the convective and radiative losses grow with the diameter while the resistance stays the same. It also absorbs more sun. IEEE Std 605 provides the calculation tools for sizing a rigid or strain bus and the forces on its structure (IEEE Std 605-2023, scope). RUS Bulletin 1724E-300 selects a bus tube by its continuous current rating before it checks the spans. In its example, a 3 inch Schedule 40 tube of 6063-T6, rated 1890 A, serves a bus of 1800 A (RUS 1724E-300 §4.11.3.1). A tube that is wide enough for its current may still need a larger size or shorter spans for its strength (Short-circuit forces on busbars).
Given: the main bus of the default 220 kV project, rated 3150 A, on a tube of alloy 6101-T6 of the level's typical nominal size, 4 inch. The example takes both walls that AFL's bus pipe table lists for that size: Schedule 40, with the pipe's dimensions as RUS Bulletin 1724E-300 Table 4-14 lists them, and Schedule 80, as AFL's table gives it. The weather takes the project's Maximum ambient temperature and the conditions of Effect of the conditions. These are the lowest wind of STNW3014 across the tube, the sun of the European line standard as Kanálik and others report it, and an absorptivity and emissivity of 0.5, which STNW3014 accepts for aluminium in rural areas. The limiting temperature is the example's assumption, STNW3014's 90 °C for busbars in continuous operation (STNW3014 §5.3.2), and not a rule of either standards set.
| Quantity | Value |
|---|---|
| Outside diameter | 114.3 mm |
| Wall and inside diameter , Schedule 40 | 6.02 mm, 102.26 mm |
| Wall and inside diameter , Schedule 80 | 8.56 mm, 97.18 mm |
| Resistivity and coefficient (STNW3014 Table 3) | 3.1347 × 10⁻⁸ Ω·m, 0.00363 per °C |
| Ambient temperature | 50 °C |
| Limiting temperature (STNW3014 §5.3.2) | 90 °C |
| Wind speed , square to the tube | 0.5 m/s |
| Solar radiation | 1000 W/m² |
| Absorptivity and emissivity | 0.50, 0.50 |
Resistance by Eq. (2) at 90 °C: = 19.20 µΩ/m with the Schedule 40 wall and 13.83 µΩ/m with the Schedule 80 wall.
Convection by Eq. (7). The film temperature is 70 °C, where = 0.0286 W/(m·K) and = 19.81 × 10⁻⁶ m²/s. The Reynolds number is
The forced Nusselt number of a smooth tube is 24.9 and the natural one 20.2. The forced Nusselt number is the larger, which gives = 89.3 W/m.
Radiation and sun by Eq. (3) and Eq. (4): = 66.0 W/m and = 57.1 W/m. The net loss is 98.2 W/m. These terms depend on the outside diameter only, so they are the same for both walls.
Current by Eq. (1):
Result: in these conditions the tube carries 2261 A with the Schedule 40 wall, below the main bus's rated current of 3150 A. With the Schedule 80 wall it carries 2665 A, below that rating.
the table repeats the example for the Schedule 40 wall with one condition changed at a time.
| Condition changed | Ampacity |
|---|---|
| None (the example) | 2261 A |
| Wind 1.0 m/s across the tube | 2668 A |
| Wind 2.0 m/s across the tube | 3284 A |
| Wind along the tube | 2058 A |
| Still air | 2058 A |
| Ambient temperature 40 °C | 2638 A |
| Limiting temperature 70 °C | 987 A |
| Absorptivity and emissivity 0.85 | 2332 A |
| No sun | 2844 A |
The limiting temperature, the wind and the sun change the rating most. A wind along the tube cools it no more than still air, since the natural convection is then the larger loss. A limiting temperature only 20 °C above a hot ambient lowers the rating to less than half, which is why the limit and the ambient are stated together.
9In the design
The design rates the main-bus tube of the high-voltage (HV) yard by the heat balance of this topic and sizes the tube to the bus's rated current (Bus and bay current ratings, HV buses and bays, Busbars and conductors, In the design). The convection takes the TB 601 forms of Eq. (7), the larger of the forced and the natural loss. The radiation follows Eq. (3), the solar gain Eq. (4), and the resistance Eq. (2) for the set's alloy. The alloy is 6101-T6 on the IEC + CEA / CBIP set. On the ANSI / IEEE set it is 6063-T6, the alloy of RUS 1724E-300's rating example, of 53 % IACS conductivity (Snohomish County PUD, S0301-3). The ambient temperature is the input Maximum ambient temperature, on the Site & soil page, 50 °C on the default project. The same input enters the earth conductor's sizing.
The other conditions of the rating are those of the project's standards set. On the IEC + CEA / CBIP set, they are the conditions of the bus calculation of an Indian 400 kV project to IEEE Std 605-2008 (GSECL Khavda substation, Amara Raja Infra, 2023). These are a conductor temperature of 95 °C, a wind of 0.61 m/s across the tube, 848 W/m² of sun, and an absorptivity and emissivity of 0.5. At that wind, the TB 601 form gives that calculation's tube a lower convective loss than its IEEE Std 605 formula, so the design's rating is the lower of the two. On the ANSI / IEEE set, the conditions are those of RUS Bulletin 1724E-300 (RUS 1724E-300 §4.10.4). These are a total conductor temperature of 70 °C, an emissivity of 0.5 for weathered aluminium, a wind of 0.61 m/s (2 ft/s) across the tube and no sun.
The main bus takes the smallest tube of its set's table, from the level's typical size up, whose ampacity meets the bus's rated current. The table of the IEC + CEA / CBIP set holds the tubes of the POWERGRID switchyard erection specification. The table of the ANSI / IEEE set holds the Schedule 40 sizes of RUS Bulletin 1724E-300 Table 4-14. On the default project the typical 4 inch EH tube carries 3124 A, below the main bus's 3150 A. The design therefore takes the 4.5" IPS EH tube, of 120.0 mm outside diameter with a 12.00 mm wall, rated 3804 A.
The bill of materials (BOM) names the tube by its size, wall and alloy, and states its rating beside the bus's rated current. Its line for the default project is "Aluminium tube, 4.5" IPS EH (OD 120 mm, wall 12 mm)". The lightning protection step and the 3D model take the same tube. The design calculates no ampacity of a strung conductor.
- Write the current a bare conductor carries at its limiting temperature.
Answer 1
, the heat balance solved for the current with the losses and the gain taken at the limiting temperature (Eq. (1)).
- Explain where the constant 17.8 of the radiation equation comes from.
Answer 2
It is , from the Stefan–Boltzmann law with the absolute temperatures written divided by 100 (Radiation).
- State how IEEE Std 738-2012, as linerate implements it, chooses between its convection equations.
Answer 3
It calculates both forced convection equations and the natural convection, and takes the larger as the convective loss (Convection).
- Explain why a rating is stated with its weather.
Answer 4
The wind, the sun and the ambient temperature change the losses and the gain, the wind and the sun most, so the same conductor has different ratings in different conditions (Effect of the conditions, the table).
- Name the reasons for a conductor's limiting temperature.
Answer 5
Above it, aluminium oxidises and anneals, the connected equipment can be damaged, and a strung conductor can sag below its clearance (The limiting temperature).
- Calculate the ampacity of a tube of the typical size of the default project's main bus in the example's conditions.
Answer 6
With = 98.2 W/m, the 4 inch tube carries 2261 A with the Schedule 40 wall and 2665 A with the Schedule 80 wall (Example 1).
[1]Abboud and others 2018, Using Computational Fluid Dynamics to Assess Dynamic Line Ratings in Southern Idaho. Eq. 7; Eq. 9, Eq. 10; Eq. 11.
[2]Energy Queensland STNW3014, Standard for Busbar Conductor Selection. Annex A, Eq. 1; Annex A.1.1.4; Annex A.1.1.2.
[3]Kanálik and others 2019, Temperature calculation of overhead power line conductors based on CIGRE Technical Brochure 601 in Slovakia. Eq. 3.
[4]Statnett linerate, linerate.
[5]RUS Bulletin 1724E-300, Design Guide for Rural Substations.
[6]IEEE Std 738, IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors.
[7]CIGRE TB 601, Guide for thermal rating calculations of overhead lines.
[8]IEEE Std 605, IEEE Guide for Bus Design in Air Insulated Substations.
[9]AFL, Seamless bus pipe, Seamless Bus Pipe.
[10]Snohomish County PUD, S0301-3, S0301-3 Aluminum Bus Conductor.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.