Substations in the power system

Electricity is generated at power stations, carried over long distances at high voltage and delivered to consumers at low voltage. A substation is the place where the power system changes the voltage, switches its circuits and protects and measures them. This topic explains what a substation is, where it stands between generation and the consumers, and what a pooling substation of a generating plant does. It closes with the voltage levels of the grid in the IEC + CEA / CBIP set and in the ANSI / IEEE set, as SubstationLayout designs them.

1What a substation is

A substation is a station that transforms or converts electricity for its transmission or distribution. The Electricity Act 2003 of India defines it so in section 2(69). The same definition lists what a substation includes: transformers, converters, switchgear, capacitors, synchronous condensers, structures, cables and other equipment, with its buildings and its site.

The Occupational Safety and Health Administration (OSHA), the agency of the United States Department of Labor for safe and healthful working conditions, describes a substation as a high-voltage facility of the electric system. A substation switches generators, equipment and lines in and out of service, and it changes the voltage of alternating current. Its size ranges from a single transformer with a few switches to a large site with several transformers and dozens of switches (OSHA Electric Power eTool, Substations).

A substation is therefore a node of the network. Lines of the same or of different voltages meet at its buses, and the switching devices of each circuit connect it to them.

2The substation in the power system

The path from a power station to a consumer passes through several substations. The grid, in the words of the Electricity Act 2003, section 2(32), is the high-voltage backbone of interconnected transmission lines, substations and generating plants. The Energy Information Administration describes the grid in the same terms: substations, transformers and power lines that connect producers and consumers.

Figure 1 shows the path. A generating station delivers its power to a step-up substation, which raises the voltage for transmission. Transmission lines carry the power to switching points of the grid, where substations connect the lines with one another. A step-down substation lowers the transmission voltage to the sub-transmission voltage. A distribution substation near the consumers lowers it again, and distribution lines carry the power to them (OSHA Electric Power eTool, Substations).

Figure 1.The power system from generation to the consumers, with the substations between them. A renewable plant connects through its pooling substation, a generating station through its step-up substation. The drawing is schematic and not to scale.

The voltage rises for transmission because high-voltage transmission over long distances is more efficient and less expensive (Energy Information Administration, How electricity is delivered to consumers). The voltage falls again near the consumers, where lower voltages are used. The Electricity Act 2003 calls the wires and facilities between the delivery points on the transmission lines and the consumers' installations the distribution system (Electricity Act 2003, section 2(19)).

In India, the transmission network has 2 layers. The inter-State transmission system is the top layer of the national grid, and the intra-State transmission system lies below it (CEA Manual on Transmission Planning Criteria 2023 §2.1.1). The Central Transmission Utility (CTU) develops the inter-State system, and a State Transmission Utility (STU) develops the intra-State system of its State. The inter-State and intra-State systems together form the grid (CEA Manual on Transmission Planning Criteria 2023 §1.2.1).

3What a substation does

A substation performs some or all of the functions below. OSHA lists them for the substations of a utility, and states that not all substations perform all of them (OSHA Electric Power eTool, Substations):

  • change the voltage from one level to another
  • regulate the voltage against changes in the network
  • switch transmission and distribution circuits into and out of the grid
  • measure the voltages, currents and power in the circuits
  • protect the equipment against lightning and other surges
  • connect generating plants to the network
  • interconnect the networks of different utilities
  • control the reactive power supplied to the circuits

The equipment follows from these functions. Power transformers change the voltage. Circuit breakers switch the circuits, under load and under fault (Circuit breakers). Isolators (disconnectors, IEC 60050) open a circuit only after its breaker has interrupted the current, and isolate it for safe work (Isolators and earth switches). Instrument transformers measure the currents and voltages for the meters and the protection (Current transformers, Voltage transformers and CVTs). Surge arresters limit the overvoltages, and reactors and other reactive power equipment control the reactive power (Reactive power equipment).

4The pooling substation of a generating plant

The CEA Manual on Transmission Planning Criteria 2023 §5.2.1 divides substations into 2 categories. A load-serving substation is one where loads are connected. A generation pooling substation is one where generating stations connect, directly or through a dedicated transmission line, to evacuate their power. A substation where both generators and loads are connected counts as load-serving.

The International Finance Corporation (IFC) guide to utility-scale solar plants states that the inverters of a solar plant supply power at a low voltage, and that the grid connection is made at 11 kV and above (IFC §7.4.2.3). One or more transformers between the inverters and the point of connection step the voltage up. The main export transformers form a major element of the plant's main substation, which also holds the medium-voltage (MV) switchgear, the protection and the metering (IFC §7.4.2.3, §7.4.2.4).

The pooling substation of a renewable plant therefore has an MV side and a high-voltage (HV) side. Its MV side collects the plant's feeders on MV buses. Its HV side connects the step-up transformers to the lines of the grid. Figure 1 draws this path from the solar or wind plant.

5Voltage levels of the grid

The CEA Manual on Transmission Planning Criteria 2023 applies to the inter-State and intra-State transmission systems and to dedicated lines down to the 66 kV level (CEA Manual on Transmission Planning Criteria 2023 §1.2.2). Its table of voltage limits for planning studies lists the nominal voltages 765 kV, 400 kV, 230 kV, 220 kV, 132 kV, 110 kV and 66 kV (CEA Manual on Transmission Planning Criteria 2023 §3.10.4). The manual treats the 110 kV system as part of the 132 kV system, and the 230 kV system as part of the 220 kV system.

OSHA describes a step-down transmission substation that lowers the transmission voltage to a sub-transmission voltage, usually 69 kV. A distribution substation then lowers the voltage to the levels the consumers use (OSHA Electric Power eTool, Substations).

SubstationLayout designs substations at these levels:

SetHV levelsPooling substationsMV (collector) levelsFrequency
IEC + CEA / CBIP33 kV, 66 kV, 132 kV, 220 kV, 400 kV and 765 kV33 kV to 400 kV11 kV and 33 kV50 Hz and 60 Hz
ANSI / IEEE69 kV, 115 kV, 138 kV, 161 kV, 230 kV and 345 kV69 kV to 345 kV34.5 kV60 Hz

In the IEC + CEA / CBIP set, the 765 kV level is designed as a switching substation only. The sets and their levels are described in The IEC + CEA / CBIP set, Voltage levels and system frequency and The ANSI / IEEE set, Voltage levels and system frequency.

6In the design

SubstationLayout designs the substation of a plant and the HV/HV switching substation. The input Substation type selects between them. A new project is a pooling substation of a 250 MW Solar PV plant at 220 kV, in the IEC + CEA / CBIP set at 50 Hz. A plant's capacity is its rated active power, stated in megawatts, and a transformer's rating is its apparent power, stated in megavolt-amperes (Active, reactive and apparent power).

In the default project, 17 plant feeders arrive on a 33 kV bus in 2 sections. The 2 transformers of 160 MVA, 220/33 kV, step the voltage up to the 220 kV switchyard, a double main bus. The number of line bays that connect the switchyard to the grid is 1. The single-line diagram (SLD) of the design draws this arrangement (Single-line diagram (SLD)).

Review questions
  1. Define a substation and name the equipment it includes.
    Answer 1

    A substation is a station for transforming or converting electricity for its transmission or distribution, with its transformers, converters, switchgear, capacitors, structures, cables, buildings and site (What a substation is).

  2. Trace the path of electricity from a generating station to a consumer.
    Answer 2

    A step-up substation raises the voltage for the transmission lines, switching points connect the lines, a step-down substation lowers the voltage to sub-transmission, and a distribution substation lowers it again for the distribution lines (The substation in the power system).

  3. List the functions of a substation.
    Answer 3

    It changes and regulates the voltage, switches circuits, measures the voltages, currents and power, protects against surges, connects generating plants, interconnects utilities and controls reactive power (What a substation does).

  4. Distinguish a load-serving substation from a generation pooling substation.
    Answer 4

    Loads connect at a load-serving substation, and generating stations connect at a generation pooling substation to evacuate their power (The pooling substation of a generating plant).

  5. Name the HV levels SubstationLayout designs in the IEC + CEA / CBIP set.
    Answer 5

    The levels are 33 kV, 66 kV, 132 kV, 220 kV, 400 kV and 765 kV, with pooling substations from 33 kV to 400 kV (Voltage levels of the grid).

Sources

[1]Electricity Act 2003, The Electricity Act, 2003.

[2]CEA Manual on Transmission Planning Criteria 2023, Manual on Transmission Planning Criteria.

[3]OSHA Electric Power eTool, Electric Power Generation, Transmission, and Distribution eTool.

[4]Energy Information Administration, Electricity explained: How electricity is delivered to consumers.

[5]IFC, Utility-Scale Solar Photovoltaic Power Plants: A Project Developer's Guide.

[6]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.