Voltage transformers and CVTs
A voltage transformer (VT) gives the protection relays, the meters and the synchronising equipment a copy of a primary voltage at a level they can take, such as 110 V between lines. A substation uses 2 kinds. The inductive voltage transformer is a small transformer connected between a phase and earth. The capacitor voltage transformer (CVT) takes the voltage from a capacitor divider and transforms it in a small electromagnetic unit. This topic explains both principles, the carrier coupling that a CVT can provide, the accuracy classes and the risk of ferroresonance. It closes with the places of the voltage transformers in a switchyard and with the voltage transformers that the design specifies.
Before this topic: Transformer principles · Bus schemes · Current transformers
1Purpose
A voltage transformer is an instrument transformer whose secondary voltage is proportional to the primary voltage and in phase with it. Its primary is connected in shunt with the circuit whose voltage it measures, between a phase and earth or between 2 phases. The ANSI / IEEE set also calls it a potential transformer (PT).
The voltage transformers of a substation serve the protection, the synchronising and the metering of the circuits. A distance relay of a line takes the voltage from a voltage transformer and the current from a current transformer (CT). An energy meter needs the voltage and the current to measure the power (Active, reactive and apparent power). As for a CT, the voltage transformer insulates these circuits from the high voltage (Current transformers, Purpose).
2Inductive voltage transformers
An inductive voltage transformer is a two-winding transformer with a primary of many turns and a secondary of few turns (Transformer principles, The ideal transformer). Its secondary feeds relays and meters of high impedance, so it works close to an open-circuited transformer. Its voltage ratio is the turns ratio, corrected for the small voltage drops in its windings.
In a switchyard, the voltage transformer is a single-phase unit connected between a phase and earth. An earthed voltage transformer has one end of its primary connected directly to earth. An unearthed one has its whole primary insulated from earth to its rated insulation level, and is used between phases. At high voltages a cascade design divides the primary between several cores, each held at a fixed fraction of the line-to-earth voltage. The secondary is then on the core at the earthed end.
The burden of a secondary is stated in volt-amperes at the rated secondary voltage, or as an impedance. Both forms are tied by the secondary voltage:
| burden of a secondary | VA | |
| voltage across the burden, the secondary voltage | V | |
| impedance of the burden | Ω |
A voltage transformer may have a residual voltage winding in addition to its measuring and protective secondaries. The residual windings of the 3 phases, connected in series with one corner open, form an open delta winding. In normal operation the 3 voltages add to zero across the open corner. During an earth fault the sum is the residual voltage, which earth-fault protection uses.
3Capacitor voltage transformers
A CVT divides the line-to-earth voltage with capacitors before it transforms it. In the capacitor stack, the units form 2 capacitances in series, and (Figure 1). The point between them is brought out as the intermediate-voltage terminal. With no load on it, its voltage is the line-to-earth voltage divided in the ratio of the capacitances:
| intermediate voltage, across | V | |
| primary voltage, line to earth | V | |
| capacitance between the line terminal and the intermediate-voltage terminal | F | |
| capacitance between the intermediate-voltage terminal and earth | F |
The electromagnetic unit connects between the intermediate-voltage terminal and earth. It holds an intermediate transformer, which brings the intermediate voltage down to the secondary voltage. A load current drawn through the capacitive divider would change the intermediate voltage and its phase. The electromagnetic unit therefore holds a tuning reactor in series with the intermediate transformer, also called the series or compensating reactor. Seen from the intermediate-voltage terminal, the divider acts as and in parallel. The reactor's inductive reactance at power frequency approximately equals their capacitive reactance, so they cancel. With the reactor's inductance and the angular frequency, . The secondary voltage then stays in proportion to the line voltage and in phase with it over the range of the rated burden.
CVTs are commonly supplied as a more economical alternative to inductive voltage transformers, often without carrier accessories at voltages above 115 kV. They can have the same ratings and accuracy (RUS Bulletin 1724E-300 §5.11.3). IEC 61869-5 applies to CVTs connected between line and earth for system voltages of 72.5 kV and above.
A CVT stores energy in its capacitors and its reactor. When a fault makes the line voltage collapse, the secondary voltage does not follow at once. It shows a transient that decays, whose size depends on the capacitance of the divider and on the burden. IEC 61869-5 classes the transient response of a CVT as T1, T2 or T3, by the remaining secondary voltage at stated times after a primary short circuit. Class T1, for example, allows 10 % of the voltage before the fault at 20 ms or more after it. Specifications for protection require that a CVT transmit sudden drops of the primary voltage accurately.
4Power line carrier coupling
A CVT can also couple the signal of power line carrier communication (PLCC) to the high-voltage line. PLCC carries protection signalling, speech and data between the substations at the ends of a line over the line's own conductors, at carrier frequencies far above the power frequency (PLCC and fibre communication, Power line carrier gives the band). A capacitor stack has a low impedance at these frequencies, so it passes the carrier signal to the line.
For carrier coupling the low-voltage end of the stack is not earthed directly. A drain coil connects it to earth, with a low impedance at power frequency and a high impedance at carrier frequency. The carrier equipment connects at the low-voltage terminal through a line tuner. A choke coil, the carrier blocking impedance, keeps the carrier frequencies out of the electromagnetic unit. Line traps in the line conductors complete the carrier coupling at the line entry. An earth switch on the base bypasses the drain coil for maintenance. A stack used for carrier coupling alone, with no electromagnetic unit, is a coupling capacitor.
5Accuracy classes
An accuracy class states the limits of the voltage error and the phase displacement of a secondary at its rated burden. A measuring secondary must keep them near the rated voltage. A protective secondary must keep them over a wider range of voltage, down to the low voltages of a fault.
IEC 61869-3 and IEC 61869-5 give limits for measuring voltage transformers and CVTs, such as classes 0.2, 0.5 and 1.0, and separate limits for protective ones. The protective classes carry the letter P, such as class 3P. A utility specification for a 220 kV CVT requires secondaries of class 3P for protection and class 0.2 for metering (KSEB CVT specification §3).
The ANSI / IEEE set gives voltage transformers the metering classes 0.3, 0.6 and 1.2 at standard burdens named by letters. The burdens W, X, M, Y, Z and ZZ are 12.5, 25, 35, 75, 200 and 400 VA at stated power factors. An accuracy rating such as 0.3W and X, 0.6Y, 1.2Z gives the class at each burden. Higher accuracy classes, such as 0.15, are available (RUS 1724E-300 §5.10.3.1). A coupling capacitor voltage transformer (CCVT) for relaying is assigned class 1.2R, with further limits at low voltage and varying frequency. A CVT of extra-high capacitance is the type suitable for revenue metering, with class 0.3 (RUS 1724E-300 §5.11.5.4).
6Ferroresonance
Ferroresonance is a resonance between a capacitance and a saturable iron-cored inductance, which a transient can push into a state of high voltage (Lightning, switching and temporary overvoltages, Temporary overvoltages). In a voltage transformer, that state has high, distorted overvoltages and currents that can destroy the transformer (Cahier Technique 190 §1).
Voltage transformers are a common case, since a VT is an iron-cored inductance and a switchyard has many capacitances. A VT on a bus can be energised through the grading capacitors of an open circuit breaker and fall into a sustained oscillation. VTs connected between phase and earth on a network with an isolated neutral are the case most exposed to ferroresonance. The ratings of the ANSI / IEEE voltage transformers note that their overvoltage capability does not preclude ferroresonance.
The remedies add losses or keep the core away from saturation. A damping resistor across the open delta of the residual windings adds losses only under unbalanced voltages, and does not disturb the measurement in normal operation. A core designed for a low flux density leaves a margin to saturation. A CVT contains both a capacitance and an iron core, and its electromagnetic unit includes a damping device for this reason (Figure 1). A utility specification requires it to make ferroresonant oscillations practically zero (KSEB CVT specification §4.28). IEC 61869-5 includes ferroresonance tests of CVTs.
7Where voltage transformers sit
The voltage transformers sit near the circuit entrance positions or next to the buses, depending on the bus configuration and the relaying scheme. They stand on individual or three-position stands. A means of disconnecting them is usually provided, such as disconnectable clamps on the bus connections. At a circuit position they can be placed so that opening the circuit breaker and the line disconnect switches de-energises them (RUS 1724E-300 §4.4.5).
A CVT at a line entry can also serve the carrier equipment of the line, on a stand of its own near the line trap or on a common structure with it (RUS 1724E-300 §4.4.4).
A ring bus has no main buses. Each circuit therefore needs its own potential source for its relaying, so each line and each transformer position has its own voltage transformer (RUS 1724E-300 §4.6.4.2).
8In the design
The design specifies the high-voltage (HV) voltage transformers of the switchyard and the PT panels of the medium-voltage (MV) switchgear: the ratio, the secondaries with their classes and the rated burden. It prints them on the single-line diagram (SLD) and in the bill of materials. SubstationLayout sets no relay settings and makes no ferroresonance study.
Voltage transformers by level and scheme
The design places a CVT set at the entry of each line, and one set on each main bus or bus section for the bus voltage. At a 33 kV HV level the voltage transformers are inductive units to IEC 61869-3, in place of each CVT. The design calls them PTs, as it calls the inductive voltage transformers of the MV switchgear. From the 66 kV level, whose highest voltage for equipment is 72.5 kV, the voltage transformers are CVTs, within the scope of IEC 61869-5.
| Level | Voltage transformer |
|---|---|
| 33 kV | PT |
| 66 kV | CVT |
| 132 kV | CVT |
| 220 kV | CVT |
| 400 kV | CVT |
The default 220 kV project has a double main bus and 2 bus voltage transformer sets. A ring bus has no main buses and no bus voltage transformer. Each circuit has its own potential source, so each line and each transformer has its voltage transformer. A 138 kV ring bus of the ANSI / IEEE set with 1 line and 2 transformers has 0 bus sets and 3 CVT sets, 9 single-phase units.
In a yard of gas-insulated switchgear (GIS), the bus voltage transformers are inductive units inside the GIS, and the CVT stays outdoors at each line exit (Gas-insulated switchgear (GIS), Exits and links). The MV bus has one PT panel per section.
Ratio, secondaries and burden
The ratio is the level's voltage over √3 to the secondary, 220/√3 : 110/√3 V at 220 kV. The secondary is 110/√3 V by default, the secondary of a 220 kV CVT in the KSEB CVT specification §1. An entered value, such as 100/√3 V, prints in its place. The voltage transformer has 3 secondaries: 0.2, 3P, open delta. That is a measuring secondary of class 0.2, a protective secondary of class 3P and an open delta winding. The rated burden is 50 VA, one of the rated outputs of IEC 61869-5.
Given: the default 220 kV project, a double main bus with 1 line bay and 2 buses.
CVT sets: one at the line and one on each of the 2 buses, 3 sets, 9 single-phase units.
Each unit: 220/√3 : 110/√3 V, with secondaries 0.2, 3P, open delta and 50 VA.
MV PT panels: 2, one per MV section.
Result: the switchyard has 3 CVT sets of 220/√3 : 110/√3 V.
Given: a secondary of 110/√3 V, that is 63.5 V, rated 50 VA.
Burden impedance by Eq. (1): = 80.7 Ω.
Result: the rated burden of 50 VA is a load of 80.7 Ω at the rated secondary voltage. A burden of higher impedance draws less than the rated output.
The ANSI / IEEE set
The voltage transformers of the ANSI / IEEE set are 230/√3 : 115/√3 V, 115 V between lines, 66.4 V to the neutral. Their secondaries are 0.15, 0.3, 1.2R, for revenue metering, metering and relaying, at 50 VA. The bill of materials calls the CVT a CCVT.
Given: a new 230 kV pooling project of the ANSI / IEEE set, a one-and-a-half breaker at 60 Hz.
Voltage transformers: 230/√3 : 115/√3 V, secondaries 0.15, 0.3, 1.2R, 50 VA.
Result: the CCVTs are 230/√3 : 115/√3 V.
The inputs
The design's values are defaults, each an input with Auto on the Define page. The voltage transformer inputs are the secondary voltage, the secondaries, their classes and the burden. A value entered there prints on the SLD and in the bill of materials in place of the default.
- Explain why an inductive voltage transformer works close to an open-circuited transformer.
Answer 1
Its secondary feeds relays and meters of high impedance, so it carries little current and its voltage ratio is close to the turns ratio (Inductive voltage transformers).
- Give the intermediate voltage of a capacitor divider with no load on it.
Answer 2
It is the line-to-earth voltage times , by Eq. (2).
- Explain the purpose of the tuning reactor of a CVT.
Answer 3
Its inductive reactance at power frequency cancels the capacitive reactance of the divider, so the secondary voltage stays in proportion to the line voltage and in phase with it over the rated burden (Capacitor voltage transformers).
- Name the remedies against ferroresonance of a voltage transformer.
Answer 4
A damping resistor across the open delta of the residual windings, a core designed for a low flux density, and the damping device in the electromagnetic unit of a CVT (Ferroresonance).
- Give the reason why a ring bus has no bus voltage transformer.
Answer 5
A ring bus has no main buses, so each circuit needs its own potential source, and each line and transformer position has its voltage transformer (Where voltage transformers sit, In the design).
- Calculate the burden in ohms of the default CVT secondary.
[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations. §5.10.4, Eq. 5-10.
[2]Cahier Technique 190, Cahier Technique no. 190: Ferroresonance.
[3]Probst and others 2023, Modeling of a Capacitive Voltage Transformer for Evaluation of Transient Response in Conformity with the IEC 61869-5 Standard. §II, Eq. 2.
[4]KSEB CVT specification, Technical Specification: 220 kV & 110 kV Capacitor Voltage Transformer.
[5]IEC 61869-2, Instrument transformers.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.