Short-circuit forces on busbars

Parallel conductors that carry current exert a force on each other. At the load current the force is small. During a short circuit the current rises to many times its rated value, and the force rises with its square. The force then bends the tubes of a rigid bus, loads the post insulators that hold them, and swings the spans of a strung bus. This topic derives the force from the peak short-circuit current, follows it into the stress of a tube and the load on its supports, and explains why the span's natural frequency matters. It closes with the forces on flexible conductors, in outline, and with what the design specifies for the bus.

Before this topic: Busbars and conductors · Peak current and thermal equivalent current

1Force between parallel conductors

A current in a long straight conductor sets up a magnetic field around it. By Ampère's circuital law, the flux density at a distance from the conductor is , where is the permeability of free space. A second conductor at that distance carries . Each metre of it feels the force on a current-carrying conductor in a magnetic field, , square to both the conductor and the field. That is the Lorentz force, which Cahier Technique 162 states as Laplace's law (Cahier Technique 162 §2). The force per metre between the 2 conductors is therefore

(1)
Cahier Technique 162 §2
where
force per metre of conductorN/m
permeability of free space, , so that H/m
, instantaneous currents in the 2 conductorsA
centre-line distance between the conductorsm

Currents in the same direction attract and currents in opposite directions repel. The equation holds for conductors reduced to a line of current. Cahier Technique 162 accepts that for conductors of any section when their distance is much larger than their largest transverse dimension, for example 10 times. It also holds for conductors that are long compared with their distance, 15 to 20 times (Cahier Technique 162 §2). The default 220 kV project has its phases 4.5 m apart, on tubes of 120.0 mm, a ratio of 38. Its main buses run 72 m along the yard, 16 times the phase spacing. Bars close together, as in switchgear, need a correction for their shape, and short conductors a correction for their length.

2The force on a three-phase bus

In a three-phase bus laid flat, each conductor feels the forces of the other 2. The currents of the 3 phases are displaced by a third of a cycle and each carries a direct-current (DC) component that decays (Faults and fault current, The fault current and its components). The force on each conductor is the sum of its interactions with the others, and it varies with time. Cahier Technique 162 finds its maximum by setting the derivative of the force with respect to time to zero. The largest force acts on the central conductor, and it is reached with the peak short-circuit current :

(2)
Cahier Technique 162 §3
where
peak force per metre on the central conductor during a three-phase short circuitN/m
peak short-circuit currentkA

The constant 0.2 is of Eq. (1) times , since is in kA as the short-circuit study gives it. The factor applies to the central conductor and 0.808 to an outer one. The peak current is , with the peak factor of IEC 60909-0 (Peak current and thermal equivalent current, Eq. (1)). STNW3014 calculates the short-circuit load on its busbars in the same form, times the square of the peak current in amperes over the phase spacing (Energy Queensland STNW3014 Annex B.3.3.3).

A line-to-line short circuit drives one current through 2 conductors in opposite directions. Its force is , without the factor 0.866. Its current is of the three-phase current at the same point, so its force is smaller. Cahier Technique 162 finds the three-phase force 1.15 times the line-to-line force (Cahier Technique 162 §3). Figure 1 shows the force on the central conductor of a flat bus.

Figure 1.The force on the central conductor of a flat three-phase bus at one instant. The currents of phase L1 and phase L2 flow the same way and attract, and the current of phase L3 flows the other way and repels, so phase L2 is pushed towards phase L1. The force is spread along each span and is carried by the bus post insulators at its ends. Its direction and size change with time. The drawing is schematic and not to scale.

The force in RUS Bulletin 1724E-300. This bulletin, a design guide of the ANSI / IEEE set, writes the force on the central conductor from the root-mean-square value (RMS) of the symmetrical current, with a reduction factor. The bulletin writes the current in amperes and the spacing in centimetres. Written with in kA and in metres, its equation reads

(3)
RUS Bulletin 1724E-300 §4.11.2.3, Eq. 4-4
where
maximum short-circuit force on the central conductor of a flat three-phase busN/m
short-circuit force reduction factor, 0.5 to 1.0, 0.67 recommended
initial symmetrical three-phase short-circuit current, RMSkA

The constant follows from Eq. (1) and the factor 0.866 of Eq. (2), with a peak of times the RMS current, the full offset of . In amperes and metres the factor is , which is with the spacing in centimetres. The bulletin's example of a 161 kV bus with 24 000 A at a spacing of 274 cm and = 0.67 gives 195.8 N/m (RUS 1724E-300 §4.11.3.3).

3Stress in a tube

The force per metre loads each span of a tube as a beam. The span bends between its supports, and the largest bending moment sets the largest stress in the wall. For a span of length resting on simple supports at both ends, the largest moment is at midspan. The stress at the outer fibre of the tube is the moment divided by the section modulus:

(4)
Energy Queensland STNW3014 Annex B.3.1, Eq. 6
where
bending stress at the outer fibre of the tubePa
span between supportsm
section modulus of the tube, m³
second moment of area of the tube, m⁴
, outside and inside diameter of the tubem

STNW3014 writes the equation for the longest span that keeps the stress within the allowable stress, , with the total load . With , that is Eq. (4) solved for . RUS Bulletin 1724E-300 writes the same limit as . Its factor of 0.090 for a single span on simple supports is , the 8 of Eq. (4) with the kilopascals and cubic centimetres of its units (RUS 1724E-300 Eq. 4-8, Table 4-12). A span fixed at both ends has a smaller moment and takes 0.110. RUS Bulletin 1724E-300 writes and IEC 60865-1 writes for the section modulus.

The short-circuit force acts with the other loads. RUS Bulletin 1724E-300 adds the horizontal loads, the short-circuit force and the wind, and the vertical loads, the weight of the tube and of the ice. It takes the total as their vector sum, and notes that IEEE Std 605 applies the wind and the ice separately (RUS 1724E-300 §4.11.2.4, Eq. 4-7). The stress is compared with an allowable stress below the alloy's yield. RUS Bulletin 1724E-300 allows 1.38 × 10⁵ kPa for 6063-T6, with a safety factor of 1.25 (RUS 1724E-300 Eq. 4-8). STNW3014 divides the 0.2 % proof stress by 1.65 (STNW3014 §8.5). A weld lowers the strength of the alloy near it, from a minimum yield of 172 MPa to 76 MPa for 6063-T6 and 6101-T6 (STNW3014 Table 8). Couplers are therefore placed where the bending moment is smallest (Busbars and conductors, Rigid buses).

The stress grows with the square of the span and with the square of the peak current, and is inversely proportional to the phase spacing. Shorter spans, a wider spacing and a larger tube lower it.

4Load on the supports

The force on a span is carried by the supports at its ends. For spans on simple supports, a support between 2 equal spans takes half of each span's load, the force on one span length in all. STNW3014 makes the same division for the weight of the bus (STNW3014 §8.1.1). A tube continuous over the support carries more to it: by beam theory, the inner reaction of a beam continuous over 2 equal spans is 1.25 times the load of one span. IEC 60865-1 expresses the support arrangement through its factor for the force on a support (IEC 60865-1:2011, terms and symbols). The force acts at the top of the post insulator, so it bends the insulator as a cantilever. RUS Bulletin 1724E-300 requires a cantilever strength of 2.5 times the support's share of the short-circuit and wind loads. The working load is then 40 % of the insulator's rated cantilever strength (RUS 1724E-300 §4.11.2.7, Eq. 4-10). STNW3014 uses a factor of 2 for the dynamic nature of the short-circuit load on its insulators (STNW3014 §8.6). If no insulator is strong enough, the designer widens the phase spacing or shortens the spans (RUS 1724E-300 §4.11.2.7).

A bus fixed at more than one support in a section is also pushed along its length. Its thermal expansion during the short circuit loads the fixed supports, and its lateral bending pulls them inwards. STNW3014 avoids both with one fixed support per section and slip supports elsewhere (STNW3014 §8.1.1, §8.1.2).

5Dynamic response and natural frequency

The force of a short circuit is not a steady load. While the DC component lasts, it has a component at the network frequency, and it has a component at twice the network frequency and its multiples (Cahier Technique 162 §3). A tube is elastic, so it vibrates in response. Near its natural frequency, the stresses can be far greater than those of the peak force applied statically. Cahier Technique 162 calls the ratio of the dynamic to the static stress the stress factor (Cahier Technique 162 §3).

The natural frequency of a span depends on its supports, its length, its mass and its stiffness:

(5)
Energy Queensland STNW3014 Annex C.1
where
first natural frequency of a spanHz
constant of the end supports, 1.00 for simple supports at both ends, 1.25 for simple and fixed, 1.51 for fixed at both ends
modulus of elasticity of the conductor materialPa
mass per metre of the conductorkg/m

The frequency falls with the square of the span. A long span of a large tube has a natural frequency of a few hertz, far below twice the network frequency.

IEC 60865-1:2011 calculates the stresses of rigid conductors with this response in mind. It multiplies the static stress and the support force by ratios of the dynamic to the static value, and . It finds them from the relevant natural frequency of the span, and adds factors for the support arrangement: for the force on a support, for the conductor's stress, and for estimating the natural frequency. It has further factors for unsuccessful three-phase automatic reclosing (IEC 60865-1:2011, terms and symbols). A factor of plasticity accepts a slight permanent deformation, so the permitted stress is times the yield stress (Cahier Technique 162 §4). The standard calculates only the stresses caused by the short-circuit currents, with simplifications that err on the safe side. The combination with the dead load, wind, ice or earthquakes is left to an agreement or to other codes, and its results are design loads without a further partial safety factor (IEC 60865-1:2011, scope).

The span's natural frequency also governs its response to wind. A steady light wind sheds eddies alternately from each side of a tube, at a frequency , with the Strouhal number = 0.19 for a cylinder. STNW3014, after IEEE Std 605, accepts a span whose ratio lies outside 0.5 to , and otherwise adds a damping conductor inside the tube (STNW3014 Annex C, §8.3). This is the aeolian vibration of Busbars and conductors, Rigid buses.

6Flexible conductors

A strung bus or a slack connection moves under the force, instead of bending. During the short circuit, the spans of 2 phases are pushed apart or drawn together and swing out. IEC 60865-1:2011 defines the tensile forces this sets up in a flexible conductor (terms and definitions):

  • the short-circuit tensile force , the largest tension caused by the swing out during the short circuit
  • the drop force , the largest tension when the span falls back after the swing out
  • the pinch force , the tension in a bundle when its subconductors are drawn together

The standard also calculates the horizontal displacement of a span and the minimum air clearance that remains during the swing, and the effects on droppers (IEC 60865-1:2011, contents). The tensile forces include the dead load and pass to the insulator strings, the gantries and their foundations. They are the reason a strung bus needs larger clearances than a rigid one (Busbars and conductors, Strung buses and flexible conductors).

Example 1Force and stress on the main bus of the default 220 kV project

Given: the default 220 kV project at 50 Hz. The peak current is the short-circuit study's at the high-voltage (HV) bus (Peak current and thermal equivalent current, Example 1). The tube is the design's main-bus tube, 4.5" IPS EH of alloy 6101-T6, of 120.0 mm outside diameter with a 12.00 mm wall (Ampacity of conductors, In the design). Its second moment of area and section modulus are computed from that geometry, as Eq. (4) defines them. Its weight is that of the POWERGRID switchyard erection specification for the size, and the alloy's properties are those of STNW3014 Table 8.

QuantityValue
Initial symmetrical current , peak factor 22.95 kA, 2.000
Peak short-circuit current 64.90 kA
Phase spacing of the main buses4.5 m
Span between bus post insulators9 m
Outside diameter and wall of the tube120.0 mm, 12.00 mm
Section modulus and second moment of area 100.2 cm³, 601.0 cm⁴
Weight of the tube108.2 N/m
Modulus of elasticity , minimum yield strength 70 GPa, 172 MPa

Force on the central conductor by Eq. (2):

On one span of 9 m the force is 1459 N. On simple supports, a bus post insulator between 2 spans carries the same 1459 N. If the tube is continuous over 2 equal spans, the inner support carries 1824 N.

Stress by Eq. (4), for a span on simple supports:

That is 10 % of the minimum yield strength of 172 MPa, before the factors of the dynamic response.

Natural frequency by Eq. (5), with simple supports ( = 1) and a mass of 11.03 kg/m:

The force oscillates at 50 Hz and 100 Hz, far above . A wind of 2.4 m/s sheds eddies from the tube at .

Result: the peak force on the central tube is 162.1 N/m, and the static stress of a span is 16.4 MPa, 10 % of the alloy's minimum yield strength. On simple supports, each inner support carries 1459 N.

7In the design

The design calculates the peak short-circuit current at the HV and medium-voltage (MV) buses and checks it against the rated making current of the switchgear (Peak current and thermal equivalent current, The switchgear rating checks). It specifies the quantities that set the forces on the main buses: the phase spacing of the yard, 4.5 m at 220 kV, the main-bus tube, and bus post insulators at spans of at most 9 m. It sizes the tube to the bus's rated current (Ampacity of conductors, In the design). Its bus post insulator for the default project is "245 kV, solid core, 8 kN" (Insulators and bushings, In the design).

The design does not calculate the short-circuit forces on a bus, the stress of a tube, the load on its supports, a span's natural frequency, or the tensile forces of a strung conductor.

Review questions
  1. Derive the force per metre between 2 parallel conductors.
    Answer 1

    The first current sets up at the second conductor, which feels per metre, so (Eq. (1)).

  2. State which conductor of a flat three-phase bus carries the largest force, and its value.
    Answer 2

    The central conductor, with in kA, at the peak short-circuit current (Eq. (2)).

  3. Show where the constant of RUS Bulletin 1724E-300 Eq. 4-4 comes from.
    Answer 3

    It is with the spacing in centimetres, the central conductor's force at a full offset (The force on a three-phase bus).

  4. Explain how the span and the phase spacing change the stress of a tube.
    Answer 4

    The stress grows with the square of the span and is inversely proportional to the phase spacing, so shorter spans and a wider spacing lower it (Stress in a tube).

  5. Explain why the natural frequency of a span matters.
    Answer 5

    The force oscillates at the network frequency and twice it, and near the natural frequency the dynamic stress can far exceed the static one (Dynamic response and natural frequency).

  6. Calculate the static stress of a main-bus span of the default project.
    Answer 6

    With = 162.1 N/m on a span of 9 m and = 100.2 cm³, the stress is 16.4 MPa (Example 1).

Sources

[1]Cahier Technique 162, Cahier Technique no. 162: Electrodynamic forces on busbars in LV systems. §2; §3.

[2]Energy Queensland STNW3014, Standard for Busbar Conductor Selection. Annex B.3.1, Eq. 6; Annex C.1.

[3]RUS Bulletin 1724E-300, Design Guide for Rural Substations. §4.11.2.3, Eq. 4-4.

[4]IEC 60865-1:2011, Short-circuit currents, Calculation of effects, Part 1: Definitions and calculation methods.

[5]IEEE Std 605, IEEE Guide for Bus Design in Air Insulated Substations.

[6]IEC 60909-0:2016, Short-circuit currents in three-phase AC systems, Part 0: Calculation of currents.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Short-circuit forces on busbars, revision 3, 9 Nov 2026, https://substation.solarlayout.app/library/reference/short-circuit-forces-on-busbars