Fire protection and oil containment

An oil-immersed power transformer holds thousands of litres of combustible oil next to the energised windings. A failure inside the tank can rupture it and set the oil alight, and the fire can spread to the next transformer, a building or the equipment around it. Fire protection limits that spread, and oil containment keeps the oil out of the soil and the water around the site. This topic explains the fire risk, the separation and firewalls between transformers, the soak pits and the oil collection, and the fire suppression systems. Each standards set's requirements are given from its own documents.

Before this topic: Roads, trenches and buildings · Power transformers

1Fire risk of an oil-filled transformer

Transformer fires are rare, but an uncontained fire can do a significant amount of damage and cause a prolonged, unscheduled outage (Bureau of Reclamation, FIST 3-32 §1). FIST 3-32 is written for the large mineral-oil-filled generator step-up transformers of the Bureau's powerplants, and it applies the same consideration to smaller transformers whose fire risk is unacceptable (§2). An arc inside the tank vaporises the oil around it and builds up pressure within milliseconds, and the pressure relief device may not relieve it before the tank ruptures (Power transformers, Parts of a power transformer). Industry statistics that FIST 3-32 cites show one transformer failure in 5 resulting in a fire (§3). An exploding transformer can throw oil beyond its containment, into nearby waterways, and the debris of a bushing or an arrester can strike the equipment nearby (FIST 3-32 §8, §12).

A transformer already on fire is generally lost. The aim of fire protection is to save the plant around it: the adjacent transformers, the buses and breakers, the buildings, and the supply that the other units carry (FIST 3-32 §8). Burning oil confined around the tank concentrates its heat there. So containment and fire protection work together: the oil is held on site, and the fire it feeds is kept from the rest of the yard (FIST 3-32 §3).

The first defence is to prevent the failure. Regular dissolved gas analysis of the oil detects the gases of an incipient fault before they become explosive (FIST 3-32 §9). The CEA standard specification for transformers and reactors names the bushing as a major cause of transformer failures, some of which led to fires. It specifies bushings of resin-impregnated paper or synthetic in place of oil-impregnated paper (Ch. 1 para 8). Where a utility asks for it, a flow-sensitive valve sits between the conservator and the Buchholz relay (Ch. 2 §20.12). It shuts off when the oil flows faster than in normal operation, so the conservator's oil does not feed a fire in the tank.

2The CEA Safety Regulations 2023

In the IEC + CEA / CBIP set, the CEA Safety Regulations 2023 set the fire measures of an installation where electricity above 650 V is supplied, transformed or used (Reg. 46(2)). For a substation or switching station with oil-filled apparatus holding more than 2000 l of oil, indoors or outdoors, the owner shall (Reg. 46(2)(vii)):

  1. provide separation walls or fire barrier walls between the apparatus (Reg. 46(2)(vii)(a)). A wall is also provided between the apparatus and an adjacent building whose wall is not rated for a fire withstand of 4 h. The walls take the thickness and dimensions of the relevant standards;
  2. provide a suitable oil soak pit (Reg. 46(2)(vii)(b)). Where one tank holds more than 9000 l, the owner provides for draining away or removing the oil that leaks or escapes, prevents the spread of a fire of the oil and provides for extinguishing it;
  3. keep no spare oil near the oil-filled equipment (Reg. 46(2)(vii)(c)).

Reg. 46(2) adds 2 measures that stand on their own, without the 2000 l condition. Without prejudice to the measures above, the owner undertakes adequate fire detection and protection arrangement for quenching a fire of the apparatus (Reg. 46(2)(viii)). Each transformer of 10 MVA and each reactor of 10 MVAr and above is provided with an automatic fire fighting system, to the relevant standards (Reg. 46(2)(ix)).

The same regulation keeps apparatus with more than 2000 l of oil out of a basement where proper oil draining cannot be provided (Reg. 46(2)(vi)). It requires the cable trenches of a substation to be filled with sand, pebbles or similar non-inflammable material, or covered with non-inflammable slabs (Reg. 46(2)(xiii)). Fire buckets of clean dry sand and suitable fire extinguishers are kept in enclosed substations (Reg. 29(1)).

The CEA specification leaves the fire fighting system to the utility. The utility ensures a fire protection system that includes the soak pits or oil collecting pits, the fire separation walls where required and a water hydrant system, in line with the Safety Regulations (Ch. 1 para 17). The regulation sets the measures by the quantity of oil and leaves the dimensions to the relevant standards, so the numbers of the next sections come from the CEA specification and from the utilities' specifications.

3Separation and firewalls

A transformer fire endangers its neighbours by radiant heat and by flying debris. Distance protects them, because the heat a surface receives falls as it moves away from the fire. Where the distance is too short, a firewall between the units takes the heat and stops the debris. Figure 1 shows a firewall between 2 transformers and the extent it covers.

In the IEC + CEA / CBIP set's practice, a firewall stands between transformers or reactors whose free distance is less than 10 m. The same rule applies between transformers, reactors and auxiliary transformers (OPTCL Technical Specification E-6 §12.2, after the Tariff Advisory Committee's recommendations). The wall extends at least 2 m beyond each side of the units and at least 1 m above the conservator or the safety vent (OPTCL E-6 §12.5). A clearance of at least 2 m is kept between the units and the wall. A building wall that serves as a firewall extends at least 1 m above the roof.

The firewall is designed against radiant heat and flying debris. It may be of reinforced concrete, fire brick or concrete blocks (OPTCL E-6 §12.3, §12.6). Steel members that could twist the wall when overheated do not connect it to other structures (OPTCL E-6 §12.4). The OPTCL specification requires a fire resistance of at least 3 h (§12.3). The CEA specification requires separation or fire barrier walls of 4 h fire withstand rating between transformers and reactors, in line with the Safety Regulations (Annexure-P §3.0(m)). The 2 documents differ on the rating. The CEA specification ties its 4 h to the Safety Regulations, which use the same rating for a building wall.

In the ANSI / IEEE set, FIST 3-32 cites NFPA 851, the fire protection standard for hydroelectric generating plants, now part of NFPA 850 (FIST 3-32 §4, §12). Outdoor oil-filled transformers are separated from adjacent structures and from each other by firewalls, by spatial separation or by other means, to limit the damage and the spread of fire. This includes the phases of a bank of single-phase units. FIST 3-32 also gives the guidance of the Edison Electric Institute, which sets the protection by separation and oil volume (§4). At a separation of 7.6 m to 15.2 m (25 ft to 50 ft), a transformer with more than 1893 l (500 gal) of oil takes water spray. One with more than 18 927 l (5000 gal) takes water spray and a barrier wall. At 3.0 m to 7.6 m (10 ft to 25 ft), both take water spray and a barrier wall.

Industry standards and insurance requirements specify fire suppression and barrier walls for transformers with as little as 1893 l (500 gal) of oil (FIST 3-32 §4, citing IEEE 979). They apply where the separation from buildings and other equipment cannot be achieved. The barrier walls are of noncombustible materials, with a fire rating and the strength to withstand an exploding bushing or arrester (FIST 3-32 §12). RUS Bulletin 1724E-300 weighs physical separation, barrier walls and sprinkler systems against the safety concerns and the cost of fire insurance (§21.1).

Figure 1.The oil containment and the firewall of a transformer row. Each tank stands in a soak pit with a gravel layer on a grating, the pits drain to a common burnt-oil pit, and a firewall separates units that stand close together. The drawing is schematic and not to scale.

4Soak pits and the burnt-oil pit

A soak pit catches the oil that leaks or escapes from a transformer and keeps it from spreading a fire. The layer of stones over it matters for the fire. Burning oil that drains down between the stones is cut off from the air above, so the flames die in the layer. The OPTCL specification describes the gravel as an extinguisher for flaming oil (§11.2.2). The voids between the stones hold the oil: RUS 1724E-300 gives 25 % to 40 % of voids for stone of 5 cm to 9 cm (§8.4.1).

The CEA specification sets out the pit (Annexure-P §3.0):

  • Each transformer or reactor, with its conservator and cooler banks, stands in a pit surrounded by retaining walls of reinforced cement concrete, with no part of the unit outside the walls (item e). The walls rise 150 mm to 200 mm above the finished ground level, so surface water does not run in (item j).
  • The soak pit holds at least 150 % of the unit's oil, under a layer of gravel at least 300 mm thick, of stones of approximately 40 mm, on a steel grating with free space below it (item f).
  • Alternatively, the soak pit holds one-third of the unit's oil, and a common remote oil collecting pit serves a group of units. It holds at least the oil of the largest unit (item f).
  • The soak pit drains to the oil collecting pit, the burnt-oil pit, by 2 or more pipes of at least 150 mm diameter at a slope of at least 1 in 96. The burnt-oil pit is generally located away from the transformers (item f).
  • The pits have automatic pumping, so they stay empty for an emergency, and the oil is disposed of in an environmentally friendly manner (items h, i).

The OPTCL specification sizes its pits differently. Its retaining wall stands 20 % of the transformer's height or 0.8 m from the unit, whichever is greater. The pit holds the usual 30 % of the oil under 100 mm of gravel (OPTCL E-6 §11.2.2). The common sump pit holds 150 % of the largest unit's oil, with the water of a fixed fire fighting system and the rain. The sizes are a utility's choice within the regulation's "suitable oil soakpit", so a project follows the specification its owner names.

5Oil retention in the ANSI / IEEE set

In the ANSI / IEEE set the oil containment answers the oil pollution regulations of 40 CFR Parts 110 and 112, as RUS 1724E-300 and FIST 3-32 name them, as well as the fire. Where an oil spill could reach navigable waters, the station needs containment and a spill prevention, control and countermeasure plan (RUS 1724E-300 §8.4, §2.3.1.6). The aim is that the oil within the substation remains on site (RUS 1724E-300 §8.4.3). RUS 1724E-300 describes 2 systems:

  • Basic retention system. An impervious, lined sump around the transformer, open or filled with stone, drains through a perforated pipe to an underground tank (RUS 1724E-300 §8.4.1). A sump pump removes the rainwater. A low-oil-level alarm of the transformer stops the pump, and at least 15 cm (6 in) of water stays in the tank at cut-off, so a slow leak floats on it. The tank holds the oil of one transformer.
  • Oil separator tank. The collected oil and water flow to a tank that passes the water and keeps the oil, which floats on the water (RUS 1724E-300 §8.4.2). It contains the oil of one transformer after a major rupture, and it needs a gradient for gravity discharge.

A fire adds water to the oil. FIST 3-32 sizes the containment for the oil that might spill, the expected fire suppression water and the rain or snowmelt. It takes the spill of the largest transformer plus at least 20 min of suppression water at maximum discharge (FIST 3-32 §12). It advises against metallic berms, which fail in the heat of a fire. IEEE 980 is the ANSI / IEEE set's guide for the containment and control of oil spills in substations.

6Fire suppression

A fixed suppression system puts water or another agent on a burning transformer, so the fire is controlled before it spreads. In the IEC + CEA / CBIP set, the Safety Regulations require an automatic system on each transformer of 10 MVA and each reactor of 10 MVAr and above, whatever its oil quantity (Reg. 46(2)(ix)). The CEA specification provides a pedestal for the fire fighting system on the transformer's foundation (Annexure-P §3.0(d)), and the OPTCL specification a pylon support for it (§11.1). The OPTCL civil works include a fire water tank for the suppression water (§22.0).

FIST 3-32 compares the systems for the transformers of the Bureau's powerplants (§12):

  • Water deluge. Open nozzles discharge a high volume of water at low pressure from several angles. It is effective, but its volume can overtop the containment and wash oil into a waterway.
  • Water mist. A low volume of water at high pressure. Its smaller discharge reduces the risk to the waterways, and the containment may need little change.
  • Foam, gas and dry chemicals. Not recommended at this time for the existing Reclamation facilities: foam leaves a residue and does not cool, gases are not effective in the open, and dry chemicals do not work well on large fires.

How a suppression system starts matters as much as its agent. Heat-sensing detectors near or on the transformer and a manual discharge start the suppression, and 2 sensors may be required to agree. FIST 3-32 does not use the differential relay, the sudden pressure relay, the Buchholz relay or the temperature detectors to start it, because their false operation would wet the bushings and flush spilled oil away (§12).

The suppression system de-energises the transformer before water reaches it, and stops the fans and oil pumps that could feed the fire (FIST 3-32 §11, §12). It also blocks the drains and the sump pumps, so oily water stays in the containment. The pipes and nozzles stand clear of the fire, so they do not melt before the water flows. Each suppression system is tested annually, from the detector to the nozzles and the drain valves (FIST 3-32 §10).

A transformer filled with a less flammable liquid needs less of this protection. FIST 3-32 describes ester-based fluids as an alternative that reduces the need for suppression, barrier walls and containment (§18). The liquid's class, set by its fire point, is in Power transformers, Cooling.

7Fire protection of the control building

The control building holds the relays, the batteries and the cables, and a fire there can disable the protection of the whole station. The Safety Regulations require fire buckets of dry sand and fire extinguishers in an enclosed substation (Reg. 29(1)). In RUS 1724E-300 the control house is of fire-resistant, low-maintenance materials, with fire-extinguishing equipment located and marked inside it (§16.2.3). Its ventilation louvers carry fusible links that close them in a fire (RUS 1724E-300 §16.3.7).

8In the design

The design places the oil containment and the firewalls of the transformer row, and checks them against the CEA Safety Regulations 2023 on the IEC + CEA / CBIP set. It does not calculate a pit's volume, a firewall's construction or a suppression system. Each transformer and bus reactor stands in a soak pit 1.5 m beyond its tank, and the pits drain to a common burnt-oil pit 5 m square, in a column of the transformer row that has no transformer (Yard layout, The transformer row).

A firewall 0.3 m thick stands between transformers side by side whose clear gap is below 10 m. That gap follows OPTCL Technical Specification E-6 §12.2 (Separation and firewalls), and the design applies it on the ANSI / IEEE set as its own choice. The firewall extends 0.6 m beyond the tanks and above the conservator, the design's own size, smaller than the 2 m beyond and 1 m above of OPTCL §12.5. The design keeps OPTCL's 2 m as the distance from each tank to the firewall, so 2 tanks with a firewall between them stand at least 4.3 m apart (Yard layout, The transformer row). The default project's tanks are 24 m apart, so its row has no firewall (Yard layout, Example 1).

The compliance checklist of the IEC + CEA / CBIP set evaluates 2 items: the firewalls (Reg. 46(2)(vii)(a)) and the soak pits with the burnt-oil pit (Reg. 46(2)(vii)(b)). It lists 2 further items for the user to answer, cited to Reg. 46(2)(ix) and Reg. 46(2)(viii). The checklist of the ANSI / IEEE set names IEEE 980 for the oil containment: the design provides the pits, and the item is answered from the civil design. It names IEEE 979 for the fire protection of the substation.

The station service loads include the fire fighting system. The default project's load list has a main electric fire-water pump of 37 kW on standby, a jockey pump of 5.5 kW and a fire detection and alarm panel of 1 kW (AC auxiliary supply, The load list).

Review questions
  1. Explain why fire protection aims to save the plant around a burning transformer.
    Answer 1

    A transformer already on fire is generally lost, so the protection limits the damage to the adjacent transformers, buildings and equipment and the outages they would cause (Fire risk of an oil-filled transformer).

  2. State the measures the CEA Safety Regulations 2023 require for oil-filled apparatus holding more than 2000 l.
    Answer 2

    Separation or fire barrier walls, a suitable oil soak pit, a drain-away above 9000 l in one tank and no spare oil nearby (Reg. 46(2)(vii), The CEA Safety Regulations 2023).

  3. Describe the extent of a firewall between 2 transformers in the IEC + CEA / CBIP set's practice.
    Answer 3

    It extends at least 2 m beyond each side of the units and at least 1 m above the conservator or the safety vent, with 2 m clear between the units and the wall (Separation and firewalls).

  4. Calculate the capacity of the soak pit of a unit holding 30 000 l of oil by the 2 rules of the CEA specification.
    Answer 4

    At 150 % the pit holds  l; with a common oil collecting pit it holds one-third,  l, and the collecting pit at least the largest unit's oil (Soak pits and the burnt-oil pit).

  5. Explain how the gravel layer of a soak pit stops a fire of the oil.
    Answer 5

    The burning oil drains down between the stones and is cut off from the air above, so the flames die in the layer (Soak pits and the burnt-oil pit).

  6. Give the reason why a transformer's differential or Buchholz relay does not start its suppression system.
    Answer 6

    A false operation of those relays would wet the transformer and its bushings and flush spilled oil away, so heat detectors and a manual discharge start it (Fire suppression).

Sources

[1]CEA Safety Regulations 2023, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.

[2]CEA standard specification for transformers and reactors, Standard Specifications and Technical Parameters for Transformers and Reactors (66 kV & above voltage class).

[3]OPTCL Technical Specification E-6, Technical Specification E-6, Civil Works.

[4]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[5]FIST 3-32, Facilities Instructions, Standards, and Techniques, Volume 3-32: Transformer Fire Protection.

[6]IEEE 979, IEEE Guide for Substation Fire Protection.

[7]IEEE Std 980-2013, IEEE Guide for Containment and Control of Oil Spills in Substations.

[8]NFPA 851, Fire Protection for Hydroelectric Generating Plants.

[9]NFPA 850, Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.