PLCC and fibre communication
A substation exchanges protection signals, operational data and speech with the substations at the other ends of its lines and with the load despatch centre. That traffic travels along a line over 2 media. Power line carrier communication (PLCC) sends it over the high-voltage line itself, and optical fibre carries it in a cable along the line. This topic explains the parts of a power line carrier link: the coupling capacitor or capacitor voltage transformer (CVT), the line trap, the coupling device and the carrier band. It then explains the optical fibre link and the optical ground wire (OPGW) that holds the fibres in the line's overhead earth wire. It closes with what the design states about both media.
Before this topic: Voltage transformers and CVTs · Bays and their equipment
1Services between substations
Communication between substations serves 3 purposes. Protective relaying uses it to initiate the tripping of circuit breakers. Supervisory control uses it to operate remote equipment and to send the status of equipment and the conditions of the power system. Operation and maintenance use it for speech (RUS Bulletin 1724E-300 §17.1).
Teleprotection is the exchange of signals between the ends of a line for its protection. Many relaying schemes need information from the terminals of a line to trip at high speed over 100 % of the line (RUS 1724E-300 §17.2.1). The information is in most cases simple two-state data, a trip or a block signal. The schemes that use it are explained with line protection (Line protection, Pilot schemes).
Supervisory control and data acquisition (SCADA) connects the substations to a control centre. A master station at the centre exchanges data with remote terminal units or intelligent electronic devices in the substations (RUS 1724E-300 §17.2.2; SCADA and substation automation (IEC 61850), SCADA and the remote terminal unit). The data include breaker status, tap changer positions, currents, voltages and active and reactive power. Speech connects the operators at fixed points and the maintenance crews (RUS 1724E-300 §17.2.4).
A plant connected to the grid provides the voice and data communication and the operational data that the load despatch centre prescribes (SCADA and substation automation (IEC 61850), SCADA and the remote terminal unit). The interface meters send their metered data to the load despatch centre over a secured and dedicated communication system (Tariff and revenue metering, Availability-based tariff and time blocks; CEA Meters Regulations, Reg. 14(1)(b)).
The CEA Communication Regulations 2020 set the technical standards of this communication. The communication system provides reliable data and voice communication and teleprotection (Reg. 4(1)). Cellular and radio-frequency communication are not considered for control and protection functions (Reg. 8(2)). The total outage of a node or a network is less than 16 hours in a month and less than 48 hours in a rolling 12 months (Reg. 7(1), 7(2)).
2Power line carrier
Power line carrier uses the conductors of the high-voltage line as its transmission path. The carrier signal frequencies range from 30 kHz to 500 kHz, far above the power frequency (RUS 1724E-300 §17.3.1). The CEA Communication Regulations 2020 set the band at 40 kHz to 500 kHz, with independent transmit and receive channels (Reg. 27(2)). The transmitter's power is low, 100 W or less and typically 10 W, so the signal does not radiate appreciably from the line. The regulations require PLCC between 2 consecutive substations, for speech, data and teleprotection (Reg. 27(1)).
Figure 1 shows the coupling path at both ends of a line, for one phase. Notice the order along the conductor at each end: the station bus, the line trap, and then the coupling point of the CVT on the line side.
Coupling capacitor and CVT
The signal reaches the line through a coupling capacitor, a device that frequently also serves as the voltage source for relaying or metering (RUS 1724E-300 §17.3.1). A CVT with carrier accessories does both jobs. Its capacitor stack has a low impedance at carrier frequencies and passes the signal to the line. The drain coil, the carrier blocking impedance and the terminal for the line tuner at its base are explained with the CVT (Voltage transformers and CVTs, Power line carrier coupling). At the far end, the signal is received through a coupling capacitor in the same way.
Line trap
The station bus and the transformers connected to it have a high capacitance. Without a barrier, that capacitance would short-circuit the carrier signal. A line trap on the station side of the coupling capacitor blocks the signal and confines it to the line section (RUS 1724E-300 §17.3.1). The line trap presents a high impedance at carrier frequencies (IEEE C93.3-2017, scope). It also isolates the carrier signal from changes of impedance behind its insertion point, caused by faults or switching.
A line trap is a parallel resonant circuit of an inductance and a capacitance. The inductance, the main coil, is in series with the coupled phase of the line, and the capacitance across it tunes the trap. Adjustment is available in the trap and in the line tuner (RUS 1724E-300 §17.3.1.2.1). The main coil carries the line's load current and its fault current. It is therefore rated to match the basic lightning impulse insulation level (BIL), the continuous current and the short-circuit withstand of the line's other major equipment, and it is physically large (RUS 1724E-300 §17.3.1). The main coil is a single-phase, air-cooled inductor of the dry type (IEEE C93.3-2017, scope).
Coupling device and terminal
A tuning network matches the output impedance of the transmitter to the impedance seen at the input of the coupling capacitor. This line tuner contains protective elements, such as a gap with a capacitor and an earthing switch. It is mounted in the base of the coupling capacitor or in a separate weatherproof cabinet (RUS 1724E-300 §17.3.1.1.1). The CEA regulations call it the coupling device: a line matching unit with its protective devices, between the CVT and the coaxial cable to the terminal (Reg. 27(9)).
The regulations set the coupling device's characteristics for phase-to-earth coupling. The nominal impedance on the equipment side is 150 Ω for a balanced circuit and 75 Ω for an unbalanced one. The maximum composite loss is 2 dB, the return loss is at least 12 dB, and the transmission band is 40 kHz to 500 kHz. The coupling device is mounted outdoors on a steel structure (Reg. 27(10)). A high-frequency coaxial cable connects it to the PLCC terminal indoors, and the regulations limit the cable's attenuation per kilometre by frequency (Reg. 27(11)).
A hybrid is a transformer that combines transmitters and receivers on one line tuner without mutual interference (RUS 1724E-300 §17.3.1.1.2). Each hybrid reduces the power level by 3 dB, so 2 stacked hybrids pass a quarter of the transmitter's power to the line tuner.
Tuning and channels
The line trap and the line tuner are tuned in 1 of 3 ways (RUS 1724E-300 §17.3.1.2). Single-frequency resonant tuning gives one sharp peak of response at the selected frequency, with the lowest transmission loss and the least room for added frequencies. Double-frequency resonant tuning gives 2 closely spaced peaks, at a somewhat greater loss. Wideband tuning passes a range of frequencies through one line tuner, at a greater attenuation. Wideband tuning suits a line that carries several relaying, control and data functions.
The signal carries information by on and off keying, by frequency-shift keying or by single sideband modulation (RUS 1724E-300 §17.3.1.3). On and off keying sends an unmodulated carrier as a blocking signal for directional or phase comparison relaying. Frequency-shift keying sends a guard signal continuously and shifts it to a trip signal when a trip is needed. The loss of the guard signal without a trip signal shows a failed channel, so the channel monitors itself. Single sideband modulation transmits 2 voice channels in the bandwidth that one channel occupies with both sidebands (RUS 1724E-300 §17.3.1.3.3).
A PLCC terminal of the CEA regulations works as an analogue, a digital or a mixed terminal (Reg. 27(3)). Its bandwidth is programmable from 4 kHz to 8 kHz in steps of 4 kHz. In 4 kHz it carries speech and at least 4 data channels of 1200 baud (Reg. 27(12)). The equipment of a PLCC link includes the coupling devices, the coaxial cable, the terminals, the teleprotection equipment, a 48 V direct current (DC) supply and the wave trap, another name of the line trap (Reg. 27(14)).
Fibre now displaces power line carrier in many applications. Power line carrier remains in use for relaying, for voice and for data of lower speed (RUS 1724E-300 §17.3.1).
3Optical fibre and OPGW
Optical fibre is the usual medium of substation communication. It is immune to electrical interference and noise, and its capacity far exceeds the needs of a substation (RUS 1724E-300 §17.3.5). The CEA Communication Regulations 2020 establish the wideband communication on fibre: underground fibre optic cable, OPGW or all-dielectric self-supporting cable (Reg. 26(1)).
An OPGW is a conductor that serves both as the line's overhead earth wire and as a fibre optic cable. It holds optical fibres, typically 6 to 48, inside the conductor (RUS 1724E-300 §17.3.5.1). The earth wire runs at the top of the towers, above the phase conductors. The OPGW therefore avoids the ground clearance problems of a communication cable hung below the energised line. On a new line, the cost of the conventional earth wire that the OPGW replaces offsets part of its cost. The suspension and termination hardware of the OPGW is special to it.
An all-dielectric self-supporting cable contains no metal. It can enter a substation from outside the earth mat without bringing in a hazard of earth potential rise (GPR). For the same reason, fibre links isolate the metallic communication circuits that enter a substation from its GPR (RUS 1724E-300 §17.3.5.1, §17.3.5.2).
Figure 2 shows the path of the fibres from the line into the control building. Notice the splice enclosure at the gantry, where the OPGW's fibres pass to the approach cable, and the distribution panel where the approach cable ends.
The CEA regulations set the fibre and its fittings (Reg. 26). The cable holds 12, 24 or 48 single-mode or multimode fibres. The approach cable from the OPGW's termination to the fibre optic distribution panel has as many fibres as the OPGW. The splices sit in enclosures of ingress protection class 66 or better, with at most 12 fibres per splice tray. An OPGW of a line of 220 kV and above withstands a short-circuit current of 6.32 kA for 1 s (Reg. 26(13)).
The attenuation of the optical path from end to end is limited by the length of the fibre and the number of its splices and connectors. At a wavelength of 1550 nm the limit is:
| maximum attenuation of the optical path at 1550 nm | dB | |
| length of the fibre path | km | |
| number of splices | ||
| number of connectors | ||
| maintenance margin, where a standard specifies one | dB |
The constants are in dB per kilometre, per splice and per connector. At 1310 nm the coefficient of length is 0.35 dB per kilometre, and the other terms are the same (Reg. 26(9)(b)).
The wideband network that the fibre carries meets the timing of protection. Its absolute channel delay is less than 25 ms, and the asymmetry of the delay between the 2 directions is less than 0.1 ms (Reg. 25(1)). On the failure of one path, it switches over to the alternate path in less than 50 ms (Reg. 25(2)). Its interfaces include voice, low-speed data, Ethernet and a teleprotection interface for lines (Reg. 25(6)).
4PLCC and fibre compared
The 2 media differ in their path, their capacity and their outdoor equipment, as the table shows.
| Feature | Power line carrier | Optical fibre |
|---|---|---|
| Path | The phase conductors of the line | Fibres in the OPGW, in an all-dielectric cable or in an underground cable |
| Signal | Carrier of 30 kHz to 500 kHz, 40 kHz to 500 kHz in the CEA regulations | Digital, time-division multiplexed |
| Capacity | A 4 kHz or 8 kHz channel: speech and low-speed data | Far greater than a substation needs |
| Outdoor equipment | Line trap, CVT or coupling capacitor, coupling device, coaxial cable | OPGW and its hardware, splice enclosure, approach cable |
| Services | Relaying, SCADA, speech and telemetering, at lower data rates | Relaying, SCADA, speech and telemetering |
5In the design
The design draws the line bay of the IEC + CEA / CBIP set with a line trap between the line isolator (disconnector, IEC 60050) and the CVT, the station side of the coupling point (Bays and their equipment, Line bay). The CVT is the line's voltage source for protection and metering and the coupling capacitor of the PLCC (Voltage transformers and CVTs, In the design). The single-line diagram (SLD) states the communication path in its note 4, which reads, in full, “PLCC per line through line traps (WT) on 2 phases (phase to phase), coupled through the CVTs. OPGW for the wideband network.”
POWERGRID's PLCC specification sets the coupling of a line by its voltage and circuits (cl. 5.7). Lines of 765 kV and 400 kV, and single-circuit lines of 220 kV, take phase-to-phase coupling. Double-circuit lines of 220 kV and 132 kV take inter-circuit coupling, and single-circuit lines of 132 kV phase-to-earth coupling. Phase-to-phase coupling uses 2 phase-to-earth coupling devices joined by a balancing transformer (cl. 7.3). The design treats a line bay as one circuit. It draws line traps on 2 phases at 220 kV and above and on 1 phase at 66 kV and 132 kV, and the PLCC study of the line confirms the coupled phases (cl. 5.7). Each line trap is rated for the bay's rated current and the level's short-time current, and its inductance follows the frequency plan (cl. 6.7). It stands on a pedestal on the conductor's run, between the line isolator and the CVT (cl. 6.12). A 33 kV line bay has an inductive voltage transformer and no coupling capacitor, so the design draws no PLCC there. Its SLD note reads “No wave trap: protection and SCADA over OPGW.” The ANSI / IEEE set's line bay has no line trap and the same note.
The bill of materials lists a line trap and a coupling device per coupled phase and a PLCC terminal per line. The CEA / Indian checklist's PLCC item, Reg. 27(1), passes by design and reads “PLCC on 1 line at 220 kV with line traps on 2 phases per line, 2 line traps in all, coupled through the CVTs, a PLCC terminal per line. OPGW for the wideband network”.
The design's auxiliary load list holds the communication loads. The 48 V DC telecom / PLCC charger is a continuous load of 2 kW, and the SCADA, RTU, SAS servers and network a continuous load of 3 kW (AC auxiliary supply, The load list). The telecom supplier provides the 48 V DC telecom battery and its charger (DC system, The DC system).
The CEA / Indian checklist's SCADA item is answered by the user (SCADA and substation automation (IEC 61850), In the design).
SubstationLayout does not design the communication links: it selects no carrier frequency, line trap inductance, coupling mode of a double-circuit line, OPGW, fibre count or terminal channel plan.
- Name the services that communication between substations carries.
Answer 1
Protective relaying, supervisory control and data acquisition, and speech for operation and maintenance (Services between substations).
- Explain why a line trap sits on the station side of the coupling capacitor.
Answer 2
The station bus and its transformers have a high capacitance that would short-circuit the carrier signal, so the trap blocks the signal there and confines it to the line (Power line carrier).
- State the characteristics of a coupling device in the CEA communication regulations.
Answer 3
A nominal impedance of 150 Ω balanced or 75 Ω unbalanced, a composite loss of at most 2 dB, a return loss of at least 12 dB and a band of 40 kHz to 500 kHz (Power line carrier).
- Calculate the attenuation limit at 1550 nm of a fibre path of 40 km with 10 splices and 2 connectors, without a margin.
Answer 4
By Eq. (1) the limit is 0.21 × 40 + 0.05 × 10 + 0.5 × 2 = 9.9 dB.
- Describe the path of the fibres of an OPGW into the control building.
Answer 5
The fibres pass from the OPGW to an approach cable in a splice enclosure at the gantry, and the approach cable ends at the fibre optic distribution panel (Optical fibre and OPGW).
- State what the design draws for the communication of a 220 kV line bay of the IEC + CEA / CBIP set.
Answer 6
It draws a line trap between the line isolator and the CVT, with the note “PLCC per line through line traps (WT) on 2 phases (phase to phase), coupled through the CVTs. OPGW for the wideband network.” (In the design).
[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.
[2]CEA Communication Regulations 2020, Central Electricity Authority (Technical Standards for Communication System in Power System Operations) Regulations, 2020. Reg. 26(9).
[3]POWERGRID PLCC specification, Technical Specification, Section: PLCC.
[4]IEEE C93.3-2017, IEEE Standard Requirements for Power-Line Carrier Line Traps (30 kHz to 500 kHz).
[5]CEA Meters Regulations, Central Electricity Authority (Installation and Operation of Meters) Regulations, 2006.
[6]IEC 60050-321, International Electrotechnical Vocabulary, Part 321: Instrument transformers.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.