Current transformers

A current transformer (CT) gives the meters and the protection relays a copy of a primary current at a level they can take, 1 A or 5 A. It also insulates the secondary circuits from the high-voltage conductor. This topic explains the principle of the CT and the burden it supplies. It then explains the accuracy classes for metering and for protection, the saturation of the core and its effect on the relays, and the danger of an open secondary. It closes with the cores, the ratios and the place of the CTs in a bay, and with the CTs that the design specifies.

Before this topic: Transformer principles · Faults and fault current · Bays and their equipment

1Purpose

An instrument transformer reproduces in its secondary circuit the current or the voltage of its primary circuit, in a known proportion and with the phase relation kept. The current transformer does this for a current. Its primary is connected in series with the conductor whose current it measures. The voltage transformer, the other kind, does it for a voltage (Voltage transformers and CVTs).

A CT serves 2 purposes. It brings the current down from hundreds or thousands of amperes to 1 A or 5 A, so meters and relays can be built for one standard input. It also insulates the secondary circuit from the primary conductor. This simplifies the construction of the meters and relays and keeps the personnel who use them away from the high voltage. One terminal of the secondary circuit is earthed.

Metering needs accuracy around the normal load current. Protection needs a faithful copy of the current during a fault, at many times the rated current. A CT therefore carries separate cores for metering and for protection (Cores and ratios).

2Principle

A CT is a transformer whose primary current is set by the network (Transformer principles, The ideal transformer). The secondary winding is connected to the burden, the relays, the meters and their leads, a low impedance. The CT therefore works close to a transformer with a short-circuited secondary (Figure 1). The ampere-turns of the primary and secondary windings balance, so the secondary current is the primary current divided by the turns ratio.

In the common high-voltage CT the primary is a single turn. A bar-type CT has a fixed straight conductor, a bar, rod or tube, that passes once through the core. A bushing-type CT is a ring core with its secondary winding, placed over a bushing of a circuit breaker or a transformer, whose conductor is the primary. A wound-type CT has a primary winding of one or more turns around the core. With a single primary turn, the nominal number of secondary turns equals the ratio, 1600 for a 1600/1 A CT.

The burden does not change the primary current, so a CT behaves as a current source that injects the ratio current into the burden. A small part of that current, the exciting current, magnetises the core and does not reach the burden. That part is the error of the CT.

Figure 1.The principle of a current transformer. The primary conductor passes once through the core, and the secondary winding of turns feeds the burden. The ampere-turns balance, . The drawing is schematic and not to scale.

3Burden

The burden is the load on the secondary: the relays, the meters and the leads between them and the CT. It is stated either as an impedance in ohms or as the apparent power in volt-amperes at the rated secondary current. Both forms are tied by the rated current:

(1)
Cahier Technique 194 §3.1
where
rated output (accuracy power) of a coreVA
rated burden, at which the accuracy is statedΩ
rated secondary currentA

The same output in volt-amperes is a much larger impedance at 1 A than at 5 A. A 1 A secondary therefore allows longer leads to the control building for the same output. The burden sets the voltage that the CT must produce at its secondary terminals. That voltage drives the secondary current through the winding's own resistance and the burden:

(2)
Cahier Technique 194 §3.1
where
internal voltage of the secondary windingV
secondary currentA
resistance of the secondary windingΩ
burden, the relays, meters and leadsΩ

A higher current or a higher burden needs a higher voltage, and a higher voltage needs more flux in the core. The flux of the core has a limit (Saturation and its effect on protection). The burdens of the connected devices are taken from their makers' data and added. Where the total approaches the rating, they are added as phasors with their power factors (RUS Bulletin 1724E-300 §5.10.4).

4Accuracy classes

An accuracy class states the errors that a core keeps within at its rated burden. The ratio error, or current error, is the difference between the actual and the marked ratio. The phase displacement is the angle between the primary and the secondary current. The classes differ for metering and for protection, and the IEC and the ANSI / IEEE sets name them differently.

Metering classes

A measuring CT must be accurate over the range of the load current, from a small fraction of the rated current to a little above it. IEC 61869-2, which replaced the earlier IEC standard for CTs in 2012, has the measuring classes 0.1 to 1, the classes 0.2S and 0.5S, and the classes 3 and 5. A utility specification for a 220 kV CT requires a class 0.2S metering core (KSEB CT specification).

A metering core has a small core with a small exciting current. It is accurate at the load current, but it saturates at currents slightly above the rated current. That early saturation protects the meters from the fault current. The instrument security factor (FS) is the ratio of the rated instrument limit primary current to the rated primary current (IEC 60050-321, IEV 321-02-28). The rated instrument limit primary current is the smallest primary current at which the composite error is 10 % or more, at the rated burden (IEC 60050-321, IEV 321-02-27). A metering core has a low FS for this reason (Cahier Technique 194 §3.1). The KSEB CT specification limits it to 5 or less for a 220 kV CT.

The ANSI / IEEE set defines the metering classes 0.3, 0.6 and 1.2 by the limits of the transformer correction factor, for metered loads of 0.6 to 1.0 power factor lagging. Class 0.3 keeps the factor between 0.997 and 1.003 at rated current. A class applies at a named standard burden: 0.3B-0.2 is class 0.3 at the burden B-0.2. The standard metering burdens are B-0.1, B-0.2, B-0.5, B-0.9 and B-1.8, where the number is the impedance in ohms at 5 A. Higher accuracy, such as class 0.15, is available from some makers (RUS 1724E-300 §5.10.3.1).

Protection classes

A protective CT must reproduce a fault current many times its rating, so that the relay measures it correctly. Its core is larger than a metering core. In the classes 5P and 10P of that earlier standard, as Cahier Technique 194 §3.1 gives them, the number before P is the limit of the composite error in percent at the accuracy limit current. The accuracy limit factor (ALF) is that current as a multiple of the rated current. A 5P20 core keeps its composite error within 5 % at 20 times its rated current, at its rated burden.

ClassCurrent error at rated currentPhase displacement at rated currentComposite error at the accuracy limit current
5P±1 %±60 minutes5 %
10P±3 %not specified10 %

A core loaded below its rated burden reaches its limit at a higher current. The actual accuracy limit factor follows from the rated one through the resistances of the winding and the burden:

(3)
Cahier Technique 194 §3.1
where
rated accuracy limit factor, at the rated burden
actual accuracy limit factor, at the actual burden
rated burden, at which the accuracy is statedΩ
actual burden, relays and leadsΩ
resistance of the secondary windingΩ

Differential protection is most often fed from a core defined by its magnetic characteristic instead. Class PX of the IEC instrument transformer standards, class X of the British standard BS 3938, sets a minimum knee point voltage and a maximum winding resistance. It may also set a maximum exciting current at the knee point voltage. The KSEB CT specification names such a core class PS and gives the same quantities. For a 1600-800/1 A CT of 220 kV it requires a knee point voltage of at least 900 V and a winding resistance under 6 Ω. It also limits the exciting current to 30 mA at half the knee point voltage.

The ANSI / IEEE set rates a relaying core by a letter and a secondary terminal voltage. Class C (or K) means that the ratio can be calculated from the excitation curve, and class T that it is found by test. The voltage is the one the CT delivers to a standard burden at 20 times the rated secondary current without exceeding 10 % ratio error:

(4)
RUS Bulletin 1724E-300 §5.10.6.2.5
where
secondary terminal voltage rating of the classV
rated secondary current, 5 AA
standard relaying burden B-1, B-2, B-4 or B-8Ω

A C400 CT keeps the ratio error within 10 % up to 20 times the rated current into 4.0 Ω, since 20 × 5 A × 4.0 Ω is 400 V. The standard voltages are 10, 20, 50, 100, 200, 400 and 800 V, and C800 is the highest class (RUS 1724E-300 §5.10.6.2.5).

5Saturation and its effect on protection

The flux in the core rises with the time integral of the secondary voltage. A core has a saturation flux beyond which it cannot rise further. While the flux is below it, the core takes a small exciting current and the secondary current follows the primary. When the flux reaches saturation, the exciting current rises steeply and takes most of the ratio current. The secondary current collapses for the rest of the half cycle, and its waveform is distorted.

The excitation curve shows this behaviour (Figure 2). It plots the secondary voltage against the exciting current, measured at the secondary terminals, usually on logarithmic scales. The knee point marks the change from the steep to the flat part of the curve. The ANSI / IEEE practice defines it where a 45° tangent touches the curve, the point of the core's maximum permeability, which is not yet the point of saturation. The IEC and British practice defines it where a 10 % rise in voltage causes a 50 % rise in exciting current.

Figure 2.The excitation curve of a current transformer, drawn without values. Below the knee point the core takes a small exciting current. Above it a small rise in voltage needs a large rise in exciting current. The drawing is schematic and not to scale.

A fault current has a decaying direct current (DC) component, whose size depends on the X/R ratio of the faulted circuit (Faults and fault current). The DC component drives the flux in one direction, cycle after cycle. A CT that carries a symmetrical fault current without saturation can therefore saturate during the offset. For a CT of the ANSI / IEEE set, saturation is avoided when the fault current and the burden, each in per unit of the CT's rating, satisfy this criterion:

(5)
Benmouyal, Roberts and Zocholl §IV, Eq. 5
where
maximum fault current, per unit of the CT's rated current
burden, per unit of the standard burden of the CT's class
ratio of reactance to resistance of the faulted primary circuit

A high X/R ratio makes the criterion hard to meet, so a degree of transient saturation is accepted in many relay applications. Saturation affects the relays in different ways. An overcurrent relay may operate late, by up to the time constant of the DC component. A differential relay compares the currents of 2 or more CTs. If one CT saturates during an external fault, the difference appears as a false operating current. A core can also keep a remanent flux after a fault, and the delay of a relay depends on it. Class PR of IEC 61869-2 limits the remanent flux. A utility specification requires low-remanence cores for distance protection (KSEB CT specification §7.1).

6The open secondary

A CT secondary circuit must never be opened while the primary carries current. With the secondary open, no secondary ampere-turns oppose the primary ampere-turns. The whole primary current then magnetises the core and drives it far into saturation in each half cycle. The rapid change of flux at each reversal induces voltage peaks across the open terminals. These voltages are dangerous to personnel and can break down the insulation of the secondary circuit (RUS 1724E-300 §5.10.6.3).

A secondary winding that is not in use is short-circuited. CT secondary terminals have short-circuiting arrangements for this purpose. A relay or meter is disconnected only after its CT circuit is short-circuited at the terminals.

7Cores and ratios

A high-voltage CT usually carries several secondary cores around one primary. Each core has its own magnetic circuit and secondary winding, excited by the same primary current. Each core can therefore have its own class, burden and ratio, and a metering core and a protection core can each be designed for its own duty. The 220 kV CT of the KSEB CT specification has 5 cores: one class 0.2S metering core and 4 class PS protection cores. The cores feed the relays of the distance, differential, overcurrent and busbar protection (KSEB CT specification §7.1).

A CT may have more than one ratio. A dual-ratio CT has a primary in 2 sections, reconnected in series or in parallel, or a tapped secondary winding. A multi-ratio current transformer has a secondary winding with several taps, from which a range of ratios is selected. The accuracy class applies to the full secondary winding unless stated otherwise. On a lower tap the turns in use are fewer and the knee point voltage is lower in proportion, so the use of the lower taps is avoided where possible (RUS 1724E-300 §5.10.6.2.6).

8Where CTs sit in a bay

A CT sits in series with the circuit it measures, in each phase of the bay. In the design's yard of air-insulated switchgear (AIS) of the IEC + CEA / CBIP set, the CTs are free-standing units, 3 per bay, between the circuit breaker and the line or transformer isolator (disconnector, IEC 60050), as Bays and their equipment, Line bay shows. In the ANSI / IEEE practice the relaying and metering CTs are usually bushing CTs inside the circuit breakers and power transformers, multi-ratio and with no mounting of their own. Separate CTs on their own stands are used where needed, for revenue metering for example (RUS 1724E-300 §4.4.6).

In a gas-insulated switchgear (GIS) the CTs are part of the bay's enclosed modules, with the circuit breaker and the disconnectors (Gas-insulated switchgear (GIS)).

9In the design

The design specifies the high-voltage (HV) CTs of the switchyard and the CTs of the medium-voltage (MV) switchgear: the ratio, the number of secondary cores, the accuracy class of each core and the rated burden. It prints them on the single-line diagram (SLD) and in the bill of materials. SubstationLayout sizes no protection settings and does not check the cores against saturation. These checks belong to the protection design, with the design's fault levels and the relays chosen.

CT ratio

The HV CT is a single-phase unit, 3 per bay. Its primary follows the bay's rated current. The design takes the bay rated current of the level as the higher primary, unless the user enters another value.

The CT has a dual ratio, from a primary winding reconnected in series or in parallel. The lower primary is the current nearest half of the higher one in the design's series of CT primaries, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000 and 6300 A. A higher primary below 200 A has a half under that series, and the CT then has one ratio. The ratio prints as the higher primary, the lower primary and the secondary, for example 1600-800/1 A at 220 kV.

LevelHV CT ratio
33 kV800-400/1 A
66 kV800-400/1 A
132 kV1250-630/1 A
220 kV1600-800/1 A
400 kV3150-1600/1 A

The MV switchgear's CTs take the panel's rated current, rounded up on the same series. An incomer CT follows the incomer's rating and a feeder CT the feeder's. The MV CTs have the same cores as the HV CTs.

Cores, classes and burden

The design's CT has 5 cores, connected in the order 0.2S, 0.2S, 5P20, 5P20, PS. The 2 measuring cores of class 0.2S feed the main and check meters of the grid connection (Bays and their equipment, Line bay). The 2 protective cores of class 5P20 and the class PS core feed the protection relays. The rated burden is 15 VA, one of the rated outputs of IEC 61869-2, and the secondary is 1 A by default. By Eq. (1), 15 VA at 1 A is a burden of 15 Ω.

The design's fault level at 220 kV is 50 kA. That current is 31.25 times the higher primary and 62.5 times the lower one. A 5P20 core at its rated burden is accurate to 20 times its rated current. Its accuracy at the design fault level depends on the actual burden by Eq. (3), and on the DC component (Saturation and its effect on protection). These are checks of the protection design, which SubstationLayout does not make.

Example 1CTs of the default 220 kV project

Given: the default 220 kV project, a double main bus with bays of 1600 A and a 33 kV bus with incomers of 3150 A and feeders of 1250 A.

HV CT primary: the bay rated current, 1600 A. Half of it is 800 A, a current of the series, so the ratio is 1600-800/1 A.

HV CT cores: 5 cores, 0.2S, 0.2S, 5P20, 5P20, PS, 15 VA each. The yard has 4 bays with CTs, so 12 single-phase units.

MV CTs: incomers 3150/1 A, feeders 1250/1 A.

Result: the HV CTs are 1600-800/1 A with 5 cores. The bill of materials adds 3 spare CT units, one set of 3 per rating.

Example 2Secondary currents of the default 220 kV CT

Given: the CT of the default project, 1600-800/1 A, and one interconnecting transformer (ICT) of 160 MVA at 220 kV, whose rated HV current is 420 A. The design fault level is 50 kA.

At the ICT's rated current: on the higher ratio of 1600 to one, the secondary current is 0.262 A. On the lower ratio of 800 to one, it is 0.525 A.

At the design fault level: the secondary current is 31.25 A on the higher ratio and 62.5 A on the lower ratio, 31.25 and 62.5 times the rated secondary current.

Result: the lower ratio doubles the secondary current at load and during a fault. It raises the current in the meters at load, and the multiple of rated current the protection cores carry during a fault.

The ANSI / IEEE set

The ANSI / IEEE set takes its instrument transformers from IEEE C57.13-1993 as RUS 1724E-300 reprints it. A new project's CT secondary is 5 A. The HV CT is a multi-ratio current transformer (MR) whose full ratio is the bay current, from the standard multi-ratio CTs 600:5, 1200:5, 2000:5, 3000:5, 4000:5 and 5000:5 A. A primary outside that list prints as one ratio.

The CT has 5 cores: 0.15B-1.8, 0.15B-1.8, C800, C800, C800. The 2 class 0.15 metering cores feed the line bay's 2 revenue meters at the B-1.8 burden, 45 VA at 5 A, which is 1.8 Ω by Eq. (1). The 3 C800 cores feed the relays. A CT rated other than 5 A keeps the standard burden's volt-amperes at its rated current, with the resistance and inductance multiplied by the square of 5 divided by its rated current (RUS 1724E-300 Table 5-72, its note). The design therefore gives a CT with a 1 A secondary the same 45 VA. Such a CT prints no MR, because the standard multi-ratio CTs are 5 A ratings.

The MV CT is the standard multi-ratio CT at or above the panel's current, and 600:5 A MR is the smallest the design takes. That is the design's value for switchgear CTs, which carry the relaying cores and the bus's short-time current.

Example 3CTs of a 230 kV project in the ANSI / IEEE set

Given: a new 230 kV pooling project of the ANSI / IEEE set, with bays of 2000 A, MV incomers of 3000 A and feeders of 1200 A.

HV CT: the bay current is a standard multi-ratio CT, so the CT is 2000:5 A MR, with cores 0.15B-1.8, 0.15B-1.8, C800, C800, C800 and 45 VA.

MV CTs: incomers 3000:5 A MR, feeders 1200:5 A MR.

Result: the HV CTs are 2000:5 A MR, with class 0.15 metering cores and C800 relaying cores.

The inputs

The design's values are defaults, each an input with Auto on the Define page. The CT inputs are the primary, the secondary, the cores, their classes and the burden. A value entered there prints on the SLD and in the bill of materials in place of the default. Enter the core classes in the order the cores are connected.

Review questions
  1. Explain why a CT works close to a transformer with a short-circuited secondary.
    Answer 1

    Its secondary feeds a burden of low impedance, and its primary current is set by the network, so the ampere-turns balance and the CT acts as a current source (Principle).

  2. Calculate the burden in ohms of a core rated 15 VA at 1 A.
    Answer 2

    By Eq. (1) the burden is the rated output divided by the square of the rated current, 15 Ω.

  3. State what the class 5P20 means.
    Answer 3

    The core keeps its composite error within 5 % up to 20 times its rated current at its rated burden, its accuracy limit factor (Accuracy classes).

  4. Explain how the DC component of a fault current saturates a CT.
    Answer 4

    The DC component drives the flux in one direction, so the flux can reach saturation although the symmetrical current alone would not, and the secondary current collapses for part of the cycle (Saturation and its effect on protection).

  5. Give the reason why a CT secondary is never opened under load.
    Answer 5

    Without secondary ampere-turns the primary current saturates the core, and the flux reversals induce dangerous voltage peaks at the open terminals (The open secondary).

  6. Find the HV CT ratio of the default 220 kV project.
    Answer 6

    The bay rated current 1600 A is the higher primary, and its half 800 A is a current of the series, so the ratio is 1600-800/1 A (Example 1).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations. §5.10.6.2.5.

[2]Cahier Technique 194, Cahier Technique no. 194: Current transformers: how to specify them. §3.1.

[3]ABB application note 1MRS 755322, Current Transformer Requirements for Non-Directional Overcurrent Protection.

[4]Zocholl and Smaha, Current Transformer Concepts.

[5]Benmouyal, Roberts and Zocholl, Selecting CTs to Optimize Relay Performance. §IV, Eq. 5.

[6]KSEB CT specification, Technical Specification: 220 kV & 110 kV Current Transformers (Live / Dead Tank Type) of Various Ratings and Supporting Structures.

[7]IEC 61869-2, Instrument transformers.

[8]IEC 60050-321, International Electrotechnical Vocabulary, Part 321: Instrument transformers.

[9]IEEE C57.13-1993, IEEE Standard Requirements for Instrument Transformers.

[10]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.

[11]BS 3938, the British standard that defines class X of current transformers, as Cahier Technique 194 §3.1 names it.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.