Shunt and series reactors

A reactor is an inductor built for a power network. Connected between a phase and the neutral, it is a shunt reactor, and it absorbs reactive power. Connected in series with a line or a feeder, it is a series reactor, and it adds impedance to the circuit. Shunt reactors hold down the voltage of long or lightly loaded lines and of the buses they feed. Series reactors limit fault currents and share the load between parallel circuits. This topic explains what each kind does, how reactors are built and rated, the neutral reactor of a line reactor, the duty of the breaker that switches a reactor, and the reactors of the design.

Before this topic: Active, reactive and apparent power · Lightning, switching and temporary overvoltages · Circuit breakers

1Reactors and reactive power

A reactor is a coil whose reactance sets its current at power frequency. Its losses are small beside its reactive power, so its current lags the voltage by nearly 90°. An inductance absorbs reactive power (Active, reactive and apparent power, Active, reactive and apparent power). A three-phase shunt reactor of reactance per phase, at the phase-to-phase voltage , absorbs

(1)
MIT 6.061 Notes Ch. 2 §7, derived from Eq. 62
where
reactive power the reactor absorbs, three-phaseMvar
phase-to-phase voltage at the reactorkV
current of a phasekA
reactance of a phase of the reactor, Ω
angular frequency, rad/s
inductance of a phase of the reactorH

The equation follows from per phase with at 90°, a phase current of , and 3 phases. The reactance is fixed by the coil, so the reactive power changes with the square of the voltage. At 90 % of its rated voltage a reactor absorbs 81 % of its rated reactive power. The rating of a shunt reactor is therefore always stated with its voltage.

A series reactor carries the circuit's current, not a current set by its own voltage. Its voltage drop is , and the reactive power it absorbs is . Its task is the impedance it adds in the path of the fault current and the load flow (Series reactors).

2Line charging and the voltage rise

An overhead line or a cable has capacitance between its conductors and to earth. At power frequency this capacitance draws a charging current that leads the voltage, and the line generates reactive power. With the capacitance of a phase to the neutral, the line generates , from Eq. (1) with the reactance . The charging power grows with the line's length and with the square of its voltage.

The series inductance of the line absorbs reactive power in proportion to the square of the load current. At heavy load the inductance absorbs more than the capacitance generates, and the voltage along the line falls. At light load the capacitance dominates, and the voltage rises along the line. At an open end the rise is the Ferranti effect (Lightning, switching and temporary overvoltages, Temporary overvoltages). Shunt reactors absorb part of the charging power and hold the voltage within its limits.

The Central Electricity Authority (CEA) Manual on Transmission Planning Criteria 2023 sets when reactors are planned. Bus reactors are provided at extra-high-voltage substations to keep the voltages within limits without switching off lines (CEA Manual on Transmission Planning Criteria 2023 §5.4.3.1). Line reactors are provided where a line cannot be charged without exceeding the maximum voltage (CEA Manual on Transmission Planning Criteria 2023 §5.4.3.3). Fixed line reactors may also be provided to control the temporary overvoltages at power frequency (CEA Manual on Transmission Planning Criteria 2023 §5.4.3.2). Line-connected shunt reactors typically compensate 70 % to 80 % of a long line's charging current (Chowdhury and others, 2024, §I).

3Bus reactors and line reactors

Shunt reactors stand at 3 places, which Figure 1 draws. A bus reactor connects to a substation bus through its own breaker. A line reactor connects to the end of a line, on the line side of the line's breaker, and is switched with the line. A tertiary reactor connects to the tertiary winding of a transformer. At 52 kV and above, shunt reactors connect to station buses or line terminations, with the neutral earthed directly or through a neutral reactor. Below 52 kV they are commonly connected to tertiary windings and are usually ungrounded (Cook and others, 2019, §I).

Figure 1.Shunt reactors on a bus and on a line, and a series reactor in a feeder. The line reactor's phase reactors meet at a star point earthed through a neutral reactor. The drawing is schematic and not to scale.

A line reactor may be fixed, connected to the line without a breaker, or switchable through a breaker of its own. A shunt reactor can be permanently connected or switched by a breaker (Hitachi Energy, Shunt reactors). The CEA Manual on Transmission Planning Criteria 2023 specifies a switchable line reactor where the voltage without it stays within the limits for temporary overvoltages (§5.4.3.4). It specifies that a switchable line reactor be connected so that it can also serve as a bus reactor, with a bypass of its neutral reactor (CEA Manual on Transmission Planning Criteria 2023 §5.1.7).

Switching a bus reactor changes the bus voltage. The reactor draws its reactive power through the network's impedance, and the voltage at the bus falls by the drop it causes. For the network seen from the bus as a source behind a reactance , the power flow equation Active, reactive and apparent power, Eq. (6) at a small angle gives . The voltage step is then

(2)
MIT 6.061 Notes Ch. 2 §9
where
change of the bus voltage when the reactor is switchedkV
positive-sequence reactance of the network seen from the busΩ
, voltages of the source and of the buskV

The CEA Manual on Transmission Planning Criteria 2023 sizes bus reactors so that switching them on or off in the steady state does not change the voltage by more than 5 % (§5.4.3.1). Its standard sizes at 400 kV are three-phase units of 50, 63, 80, 125 and 250 Mvar rated at 420 kV. At 765 kV they are single-phase units of 80 and 110 Mvar.

4Construction

Reactors are built in 2 families of design: the gapped iron-core reactor, immersed in oil in a tank, and the air-core reactor, a dry-type coil in free air (Chowdhury and others, 2024, §I). The design determines a reactor's linearity, its zero-sequence reactance and its behaviour when it is energised.

Gapped iron core. An oil-immersed shunt reactor looks like a power transformer, with a core and windings in a tank of oil, bushings and radiators. Its core legs are divided by air gaps, which keep the core from saturating at the voltages of operation. The cores may be three-legged, five-legged or shell-type (Cook and others, 2019, §I). At 52 kV to 245 kV, reactors are commonly oil-filled with three-legged gapped cores. At 300 kV to 500 kV they are single-phase or three-phase units. At 735 kV and 765 kV they are almost exclusively banks of single-phase units.

Air core. A dry-type air-core reactor has no iron. Its winding is made of many insulated aluminium conductors in parallel, held in cylinders of epoxy-impregnated glass fibre (GE Vernova, Air core neutral grounding reactors). Spacers between the cylinders form ducts for cooling by natural convection. With no core, the reactor's impedance does not vary with current, and it has no magnetising inrush. Its magnetic field is not shielded, so the clearances to structures and metal parts around it must be specified (Cook and others, 2019, §I). Air-core shunt reactors are built up to 550 kV (Chowdhury and others, 2024, §I).

Linearity. A reactor is linear when its current rises in proportion to the voltage. Iron-core reactors can be designed linear up to 150 % of their rated voltage, or to a lower value such as 130 % to reduce cost (Chowdhury and others, 2024, §II). ADMIE, the Greek transmission operator, requires 400 kV reactors with a linear characteristic up to 120 % of the rated voltage (ADMIE TD-95/6 §VII.2). The air gap also limits the residual flux, so an iron-core reactor's inrush current in per unit is lower than a power transformer's.

Zero-sequence reactance. In a five-legged or shell-type core, the zero-sequence flux has a return path of low reluctance, and the zero-sequence reactance equals the positive-sequence reactance. In a three-legged core the zero-sequence flux returns through air, and the zero-sequence reactance can be 80 % to 90 % of the positive-sequence reactance (Cook and others, 2019, §I). ADMIE requires a ratio of 0.95 to 1.0 for its 400 kV reactors, with a five-legged gapped core (ADMIE TD-95/6 §VII.1, §VII.3).

5Ratings

A shunt reactor is rated by its reactive power at its rated voltage and frequency. The rated current follows from these values (ADMIE TD-95/6 §VII.1). The reactance per phase follows from Eq. (1) at the rated values. The reactor must carry a voltage above its rating continuously: ADMIE requires 105 % without exceeding the temperature rise limits (ADMIE TD-95/6 §VII.6). The losses are measured at rated current, and the specification limits the third harmonic of the current to below 3 % of the crest value of the fundamental (ADMIE TD-95/6 §VII.5).

The losses of a reactor are small beside its reactive power. An air-core reactor has a ratio of reactance to resistance of 300 to 500, and an iron-core reactor approximately twice that (Chowdhury and others, 2024, §II). The direct-current component of the current after energising therefore decays slowly, with a time constant of approximately 1 s for an air-core reactor.

Example 1Bus reactor of a 400 kV project

Given: a new 400 kV project of the design, with its bus reactor of 125 Mvar rated at 420 kV. The short-circuit study gives the positive-sequence reactance of the network at the high-voltage (HV) bus, 5.84 Ω, in its minimum short-circuit case. The weakest network gives the largest voltage step.

Reactance of a phase at the rated voltage, by Eq. (1):

Rated current:

Reactive power at the nominal 400 kV: = 113.4 Mvar.

Voltage step at the HV bus by Eq. (2), for the reactive power at the nominal voltage:

Result: the reactor has a reactance of 1411.2 Ω and a rated current of 171.8 A. Switching it changes the bus voltage by approximately 0.41 %, within the 5 % of the CEA manual.

6The neutral reactor and single-pole reclosing

The line-to-earth fault is the most frequent fault (Faults and fault current, Fault types). In single-pole auto-reclosing, the protection opens only the faulted phase and closes it again after a dead time. Reclosing a single phase on a line-to-earth fault improves the network's transient stability and the line's availability (GE Vernova, Air core neutral grounding reactors).

When the faulted phase is open at both ends, the arc at the fault does not go out at once. The healthy phases still feed it through their capacitive coupling to the faulted phase. This current is the secondary arc current. In most cases it extinguishes on its own, but not always soon enough for the line to be reclosed.

A neutral reactor between the star point of a line reactor and earth speeds up the extinction of the secondary arc. It also controls the transient recovery voltages caused by switching the line. The reactors of the 3 phases with the neutral reactor form a four-reactor scheme. The neutral reactor adds 3 times its reactance to the zero-sequence reactance of the bank, as a neutral resistor adds 3 times its resistance (Earthing of the neutral, The neutral and the earth-fault current). In some applications a high zero-sequence reactance of the reactor is a distinct advantage (Cook and others, 2019, §I). Its parameters are found by transient studies with models of the arc (GE Vernova, Air core neutral grounding reactors).

A bus reactor is not switched with a line and serves no reclosing. Its neutral is typically earthed solidly (Chowdhury and others, 2024, §I). IEEE C37.015-2017 treats the switching of reactors with the neutral directly earthed, unearthed and earthed through a neutral reactor.

7Series reactors

A series reactor is connected in series with a line, a feeder or a bus section. It adds a reactance that the fault current and the load current both pass through. Current-limiting reactors reduce the fault current to a level the existing switchgear can interrupt. Power flow control reactors share the current between parallel circuits. Series reactors also limit the inrush current of capacitor banks and the current of arc furnaces and motor starting (GE Vernova, Reducing fault currents with air core series reactors, §1).

Most medium-voltage and high-voltage series reactors are dry-type air-core reactors, because their impedance does not change with core saturation during a fault. At the highest voltages and powers, current-limiting reactors may use oil-immersed iron cores. With the network's impedance and the reactor's taken as reactances in phase, the reactance that lowers the initial symmetrical fault current from to is

(3)
GE series reactor whitepaper §3, Fig. 4
where
reactance of a phase of the reactor, Ω
phase-to-phase voltage at the reactorkV
initial symmetrical fault current without the reactorkA
initial symmetrical fault current with the reactorkA

The reactor also causes a voltage drop in normal operation. That drop, and the voltage regulation with the reactor in service, are checked before the reactor is chosen. An air-core reactor needs magnetic and electrical clearances to other equipment, and footings suited to its field (GE series reactor whitepaper §3). The CEA Manual on Transmission Planning Criteria 2023 names series reactors among the measures to limit fault levels at existing substations (§5.1.5).

8Switching a shunt reactor

A shunt reactor is switched often, in some networks daily, as the reactive power the network needs changes (Cook and others, 2019, §I). The breaker that disconnects it interrupts a small inductive current, of the order of the reactor's rated current. Breakers have been damaged by severe overvoltages, particularly when reactors were disconnected (Cook and others, 2019, §I). The interruption of a reactor current remains a difficult duty for a breaker (Brunke, IEEE Circuit Breaker Tutorial, 2008, p. 33).

Current chopping. At a small current the arc in the breaker is cooled strongly, becomes unstable and can be extinguished before the current's natural zero. The current at that instant is the chopped current . The reactor's inductance then holds the energy . That energy oscillates into the capacitance on the reactor side of the breaker, and the peak voltage follows from the balance of the energies:

(4)
Cahier Technique 151 §1
where
instantaneous current at which the breaker chopsA
inductance of a phase of the reactorH
capacitance on the reactor side of the breaker, stray and connectedF
peak of the overvoltage on the reactor sideV

The inductance of a reactor is large and the stray capacitance small, so a small chopped current can give a high voltage.

Re-ignitions. The voltage across the opening contacts can exceed their dielectric withstand, and the arc strikes again. Repeated re-strikes send trains of high-frequency waves of rising amplitude into the windings on both sides of the breaker (Cahier Technique 151 §1). They stress the reactor's insulation and the breaker.

The overvoltages depend on the reactor's connection and neutral earthing, its rating and construction, its connection to the network and the breaker (Cook and others, 2019, §I). Modern breakers, controlled switching and metal-oxide surge arresters are among the means available against them (Brunke, p. 50). IEEE C37.015-2017 is the guide for applying breakers to this duty. Energising a reactor causes an inrush current smaller than a transformer's, which is not generally considered a problem (Brunke, p. 36).

9Standards for reactors

IEC 60076-6:2007 covers reactors in the series of power transformer standards. Its scope includes shunt reactors, series reactors (current-limiting, neutral-earthing, power flow control, motor-starting and arc-furnace reactors), filter reactors, earthing transformers, arc-suppression reactors and smoothing reactors. IEEE C57.21-2021 covers liquid-immersed and dry-type shunt reactors rated over 500 kVA, including the thyristor-controlled reactors of static var compensators. IEEE C57.16-2025 covers dry-type air-core series-connected reactors. IEEE C37.015-2017 guides the application of breakers to reactor switching. IEEE C57.32 covers neutral grounding devices, the neutral reactors among them (Neutral earthing resistors, Standards).

10In the design

The design offers a bus reactor at any HV level and line reactors at 765 kV, and lists them in its bill of materials (BOM). Their positions in the bus schemes and their footprints in the yard are explained in Reactive power equipment, The bus reactor and Reactive power equipment, The line reactor.

Bus reactor. The Define input Bus reactor, its range and its default at each level are explained in Reactive power equipment, The bus reactor. The BOM line "Shunt (bus) reactor, 3-phase, oil immersed" of a new 400 kV project specifies 125 Mvar, 420 kV, neutral solidly earthed, ONAN, quantity 1. The reactor is rated at the level's highest voltage for equipment, as Example 1 calculates. The single-line diagram (SLD) designates it −L1. The earth mat places 1 electrode at its solidly earthed neutral.

Line reactors. The Define input Line reactor sets the rating per line, at the levels Reactive power equipment, The line reactor names. A new 765 kV switching substation has 2 lines with line reactors of 240 Mvar each. The BOM line "Line reactor, single-phase, oil immersed" specifies 80.0 Mvar, 765/√3 kV, ONAN, quantity 6, for 2 lines × 3 units, switchable by their own CB. Each line reactor's neutral reactor is the BOM line "Neutral reactor of the line reactor", specified to suit single-pole auto-reclosing (secondary arc), per line, quantity 2. The design adds 2 breakers for the line reactors. The earth mat places 2 electrodes at the neutral reactors.

Bus reactor and breakers of the switching substation. Its bus reactor, 330 Mvar, is the BOM line "Shunt (bus) reactor, 3 × single-phase, oil immersed", 110.0 Mvar per unit, 765/√3 kV, neutral solidly earthed, ONAN, quantity 3. Its single-phase units, bus and line reactors alike, are rated at the phase voltage, as the single-phase units of the interconnecting transformers (ICTs) are. The HV breakers are specified 800 kV, BIL 2100 kVp, 63 kA 1 s, 3150 A, spring operated, pre-insertion resistors 450 Ω on line CBs, controlled switching on ICT and reactor CBs.

The design sizes no reactor from a study of line charging or voltage, specifies no series reactor, and calculates no switching overvoltage, neutral reactor rating or reactor protection.

Review questions
  1. Calculate the reactance and the rated current of the 400 kV bus reactor of the design.
    Answer 1

    By Eq. (1) the reactance is = 1411.2 Ω, and the rated current is = 171.8 A (Example 1).

  2. Explain why a lightly loaded line raises the voltage and how a shunt reactor counters it.
    Answer 2

    The line's capacitance generates more reactive power than its inductance absorbs at light load, so the voltage rises, and the reactor absorbs part of the charging power (Line charging and the voltage rise).

  3. Find the voltage step when the 400 kV bus reactor is switched.
    Answer 3

    By Eq. (2) it is approximately = 0.41 %, within the 5 % of the CEA manual (Example 1).

  4. Compare the zero-sequence reactance of three-legged and five-legged gapped-core reactors.
    Answer 4

    A five-legged core gives a zero-sequence reactance equal to the positive-sequence reactance, and a three-legged core 80 % to 90 % of it (Construction).

  5. Explain the task of the neutral reactor of a line reactor.
    Answer 5

    It speeds up the extinction of the secondary arc that the healthy phases feed through their capacitance, so that single-pole auto-reclosing can succeed (The neutral reactor and single-pole reclosing).

  6. Derive the overvoltage of a chopped reactor current.
    Answer 6

    The energy left in the reactor passes into the capacitance , so (Eq. (4)).

Sources

[1]CEA Manual on Transmission Planning Criteria 2023, Manual on Transmission Planning Criteria.

[2]Cook and others, 2019, SDG&E Relay Standards: Updating Tertiary Bus and Reactor Protection.

[3]Chowdhury and others, 2024, A Fresh Look at Practical Shunt Reactor Protection.

[4]ADMIE TD-95/6, Technical Description TD-95/6: 400 kV, 30 MVAR to 100 MVAR Shunt Reactors.

[5]GE Vernova, Air core neutral grounding reactors, Air Core Neutral Grounding Reactors: The Optimum Solution for Ground-fault Arc Suppression.

[6]GE Vernova, Reducing fault currents with air core series reactors, Reducing Fault Currents in Power Systems with Air Core Series Reactors. §3, Fig. 4.

[7]Hitachi Energy, Shunt reactors, Shunt reactors.

[8]Brunke, IEEE Circuit Breaker Tutorial, Capacitor and Reactor Switching.

[9]MIT 6.061 Notes Ch. 2, 6.061 Introduction to Power Systems, Class Notes Chapter 2: AC Power Flow in Linear Networks. §7, derived from Eq. 62; §9.

[10]Cahier Technique 151, Cahier Technique no. 151: Overvoltages and insulation coordination in MV and HV. §1.

[11]IEC 60076-6:2007, Power transformers, Part 6: Reactors.

[12]IEEE C57.21-2021, IEEE Standard Requirements, Terminology, and Test Code for Shunt Reactors Rated Over 500 kVA.

[13]IEEE C57.16-2025, IEEE Standard for Requirements, Terminology, and Test Code for Dry-Type Air-Core Series-Connected Reactors.

[14]IEEE C37.015-2017, IEEE Guide for the Application of Shunt Reactor Switching.

[15]IEEE C57.32-2015, IEEE Standard for Requirements, Terminology, and Test Procedures for Neutral Grounding Devices.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.