SVC and STATCOM
A static compensator supplies or absorbs reactive power and changes its output within a fraction of a second. It holds the voltage of a bus during load changes and disturbances, where a switched capacitor bank or reactor acts too slowly or in steps. The static var compensator (SVC) does this with reactors and capacitors switched or controlled by thyristors. The static synchronous compensator (STATCOM) does it with a voltage-source converter. This topic explains how the SVC and the STATCOM work, how they behave when the voltage falls, and where they are used. It closes with the design's static var generator (SVG), a compensator of the STATCOM type.
Before this topic: Capacitor banks and harmonic filters · Active, reactive and apparent power
1Switched and dynamic compensation
Voltage stability is the ability of a network to keep acceptable voltages at its buses in all conditions. A network can lose it after a disturbance, a rise of the load or a change of its state. The voltage then falls progressively and cannot be controlled, mainly because the sources of reactive power reach their limits. Adequate reactive power compensation, shunt or series, is one of the means of avoiding this (CEA, Studies for Dynamic Compensation §2.0). That document is a POWERGRID study for the standing committees on power system planning, published by the Central Electricity Authority (CEA).
A mechanically switched capacitor bank or reactor supplies or absorbs a fixed amount of reactive power, switched in or out by a breaker (Capacitor banks and harmonic filters, The task of a shunt capacitor bank). It serves the slow changes of the steady state. A dynamic compensator varies its output continuously and fast, and it supports the voltage during a fault and its recovery. Switched and dynamic compensation can be combined. The POWERGRID study proposed STATCOMs with mechanically switched reactors and capacitors under the STATCOM's controller. The STATCOM provides the dynamic compensation, and the switched reactors and capacitors the compensation of the steady state (CEA, Studies for Dynamic Compensation §1.0, §4.0).
2The static var compensator
An SVC is a shunt combination of controlled reactors and capacitors that regulates the voltage of the bus where it is installed (CEA, Studies for Dynamic Compensation §2.1). Its main parts are:
- Thyristor-controlled reactor (TCR). A reactor in series with thyristors. The firing of the thyristors controls the effective admittance of the reactor at the fundamental frequency, and so the reactive power it absorbs.
- Thyristor-switched capacitor (TSC). A capacitor bank switched in or out by thyristors, in steps.
- Fixed capacitors and harmonic filters. Capacitor banks connected permanently, and filters for the harmonics of the network and of the SVC itself (Cahier Technique 142 §1; Harmonics).
- Coupling transformer. It connects the SVC's branches to the network bus (Masood and others 2010, Fig. 1).
With the TCR turned off, the SVC is a shunt capacitor and supplies reactive power. As the TCR conducts more, it absorbs more reactive power and offsets the capacitors. The SVC's output therefore varies continuously from capacitive to inductive (CEA, Studies for Dynamic Compensation §2.1). A combination of a TCR and a TSC behaves at full output as a fixed capacitive admittance (Masood and others 2010 §4). Figure 1 compares the parts of an SVC with those of a STATCOM.
3The STATCOM
A STATCOM is a voltage-source converter (VSC) with its voltage source behind a reactor (CEA, Studies for Dynamic Compensation §2.2). A coupling transformer connects it to the network bus (Masood and others 2010, Fig. 2). The converter makes an alternating current (AC) voltage from the voltage of a direct current (DC) capacitor. Because its only source of energy is that capacitor, a STATCOM has little active power capability. It controls its reactive power through the amplitude of its AC voltage:
- If the converter's voltage is above the network voltage at the point of connection, the STATCOM supplies reactive power.
- If it is below, the STATCOM absorbs reactive power.
The relation follows from the reactive power sent through a reactance (Active, reactive and apparent power, Eq. (6)). With the converter's voltage in phase with the network's, and :
| reactive power sent from the converter into the reactance | var | |
| voltage of the converter, magnitude | V | |
| voltage of the network at the point of connection, magnitude | V | |
| reactance between the converter and the network | Ω |
The POWERGRID study notes that a modern STATCOM needs only a small blocking filter, with minimal or no filtering. It creates no resonance point, because it needs no capacitor banks or reactors to produce its reactive power (CEA, Studies for Dynamic Compensation §2.3).
4Voltage-current characteristics
The difference between the SVC and the STATCOM shows when the voltage falls. The figure Figure 2 draws the voltage at the point of connection against the compensator's current, capacitive to the left and inductive to the right. In its control range, each compensator regulates the voltage near its reference. The difference lies at the limits of its output.
The SVC at its limit. At full capacitive output the SVC is a fixed capacitive susceptance . Its current falls in proportion to the voltage, and its reactive power with the square of the voltage. The capacitive reactive power therefore decreases when the network needs it most (CEA, Studies for Dynamic Compensation §2.3; Masood and others 2010 §4).
The STATCOM at its limit. The STATCOM's current is set by its converter, not by an admittance. When the voltage falls far enough to drive the STATCOM to its maximum current, that current does not depend on the voltage. Its reactive power falls only in proportion to the voltage (CEA, Studies for Dynamic Compensation §2.2, §2.3). In per unit of the rating at rated voltage:
| , | largest capacitive reactive power at the voltage | Mvar |
| capacitive rating at rated voltage | Mvar | |
| voltage at the point of connection, per unit | pu | |
| susceptance of the SVC at full capacitive output | pu | |
| largest current of the STATCOM | pu |
Given: one unit of the default project's SVG, rated ±58.00 Mvar, and a voltage dip to 0.5 pu at its terminals.
As an SVC at its capacitive limit, by Eq. (2):
As a STATCOM at its maximum current:
Result: at 50 % voltage, a compensator of the STATCOM type supplies 29.00 Mvar, 50 % of its rating. An SVC of the same rating supplies 14.50 Mvar, 25 % of its rating.
The POWERGRID study concluded that a STATCOM may be rated at 75 % of an SVC's rating for the same performance after a line fault (CEA, Studies for Dynamic Compensation §2.3). The ratings have 2 limits that work the other way. A TCR fully conducting has no current limit when the voltage rises, while a STATCOM must be designed for the largest temporary overvoltage of the network. The study also notes that a STATCOM's capacitive rating may be approximately 10 % below its inductive rating, because its devices are stressed more in the capacitive direction. Masood and others draw both characteristics with a transient rating, for less than 1 s, beyond the continuous limits, and state that a STATCOM's transient rating depends on its power semiconductors (Masood and others 2010 §4).
5Response time
A STATCOM responds faster than an SVC, mainly because of the fast switching of the insulated-gate bipolar transistors (IGBTs) of its converter (CEA, Studies for Dynamic Compensation §2.2). The study gives a step response of 8 ms to 30 ms for a STATCOM (CEA, Studies for Dynamic Compensation §2.3). The study also found the STATCOM's control loop to be more robust than an SVC's to a change of the network's strength, for example the loss of a parallel line.
6Harmonics
The power electronics of an SVC generate harmonics of their own (Cahier Technique 142 §1). An SVC with a TCR therefore needs harmonic filters, at least for the 5th and 7th, the 11th and 13th, and a high-pass filter (Capacitor banks and harmonic filters, Harmonic filters). The POWERGRID study gives the filters' capacitive rating as 30 % to 50 % of the TCR's rating (CEA, Studies for Dynamic Compensation §2.3). The filters are not switched, so the SVC's range is offset by that amount in the capacitive direction. Low-order filters can resonate with the network, depending on its impedance, and may need changes in the field. A thyristor-switched reactor, switched fully on or off, needs no filter. It does not damp oscillations of the network as well as a TCR, so a TCR is still included.
A STATCOM's converter is itself a source of harmonics (Harmonics and voltage unbalance, Sources of harmonics). A modern STATCOM needs only a small blocking filter (The STATCOM), and the harmonic study of a plant includes the compensator among its sources.
7Uses
Voltage control and stability. An SVC or a STATCOM controls the voltage in the steady state and during disturbances. It limits temporary overvoltages, improves transient stability and damps power oscillations (CEA, Studies for Dynamic Compensation §2.1). A STATCOM can also balance the voltages of the 3 phases, that is, reduce the negative-sequence voltage (CEA, Studies for Dynamic Compensation §2.3).
Reactive power at a plant's connection. A grid code requires a solar or wind plant to supply and absorb reactive power over a range of power factor at its point of interconnection (Reactive power equipment, The reactive power range at the interconnection). The plant's inverters supply part of that range. A compensator on the plant's collector buses supplies the rest, and its fast response supports the voltage during a fault.
Flicker. A load that varies fast and widely makes the voltage fluctuate and causes flicker. Dynamic compensation combining capacitors, filters and thyristor-controlled reactors was developed for industries with such loads (Cahier Technique 142 §1). A STATCOM serves the same purpose: Masood and others list the reduction of rapid voltage fluctuations, flicker control, among its applications (Masood and others 2010 §7).
Space. A STATCOM needs less space than an SVC, because it needs no large capacitors or reactors to produce its reactive power and little or no filtering. Modular STATCOMs can be supplied in containers, and units in parallel form a larger compensator (CEA, Studies for Dynamic Compensation §2.3).
8Standards
IEEE 1031-2011 is the guide to the functional specification of transmission static var compensators. It serves as a base specification, with an informative annex to adapt its clauses to a particular application. IEEE lists it as an inactive-reserved standard since 2022. IEC 61954:2021 sets the type, production and optional tests of the thyristor valves of SVCs: those of thyristor-controlled reactors, thyristor-switched reactors and thyristor-switched capacitors.
9In the design
The design's reactive power device is a static var generator (SVG) on the medium-voltage (MV) buses, and in the ANSI / IEEE set a STATCOM (Reactive power equipment, The SVG of the IEC + CEA / CBIP set, Reactive power equipment, The STATCOM of the ANSI / IEEE set). Its bill of materials (BOM) item names the SVG as a STATCOM, a converter-based compensator.
Rating. On Auto, the default project's SVG for a plant of 250 MW is rated ±116.0 Mvar. The rating is the reactive power that the reactive power study requires at the MV buses, each unit up to a whole Mvar (Reactive power equipment, The SVG of the IEC + CEA / CBIP set). The design shares it over the 2 MV sections, ±58.00 Mvar per unit. A 250 MW plant of the ANSI / IEEE set has a STATCOM of ±83 Mvar.
Bill of materials. The BOM line "Static var generator (STATCOM)" specifies ±58 Mvar, 33 kV, with coupling transformer / reactor, with a quantity of 2, one per MV section. The coupling transformer or reactor of Figure 1 is part of the unit.
Single-line diagram. The single-line diagram (SLD) draws each unit as a box with its name on its own MV feeder panel, labelled with its rating. The SLD's note on the current transformers (CT) rates the panel at 1015 A, the unit's current at 33 kV.
Auxiliary supply. The auxiliary load list carries the units' cooling and auxiliaries, 17.4 kW per unit for 2 units, as a continuous load.
Yard. The units stand in a fenced area of the yard, 10 m deep, whose length follows from the total rating at 6.4 m²/Mvar. The default project's area is 74 m long (Reactive power equipment, The reactive power area).
Checklist. The checklist item on the reactive power capability at the interconnection point states "SVG ±116 Mvar in total, the reactive power study requires ±114.9 Mvar (Grid studies)", the rating that the reactive power study sets on Auto (Reactive power equipment, The checklist items).
When the design has none. A thermal plant or another plant with synchronous generators has no SVG, and its rating reads 0 Mvar. Its checklist item states the generators' power factor instead. A switching substation connects no plant and has none.
SubstationLayout does not model the compensator's control, its voltage-current characteristic or its response, and does not choose between an SVC and a STATCOM. Its harmonic study leaves the SVG out of the network (Harmonics and voltage unbalance, In the design).
- Explain how a STATCOM supplies or absorbs reactive power.
Answer 1
Its converter makes an AC voltage behind a reactor, and it supplies reactive power when that voltage is above the network's and absorbs it when below (The STATCOM, Eq. (1)).
- Name the parts of an SVC.
Answer 2
A thyristor-controlled reactor, thyristor-switched capacitors, fixed capacitors and harmonic filters, and a coupling transformer (The static var compensator).
- Compare the capacitive output of an SVC and a STATCOM at a low voltage.
Answer 3
The SVC's falls with the square of the voltage and the STATCOM's in proportion to it, against (Eq. (2)).
- Calculate the output of one SVG unit of the default project at a voltage of 0.5 pu, as a STATCOM and as an SVC.
Answer 4
As a STATCOM it supplies 29.00 Mvar, and as an SVC 14.50 Mvar (Example 1).
- Explain why an SVC with a TCR needs harmonic filters.
Answer 5
The thyristor control of the TCR generates harmonics, and filters for the 5th, 7th, 11th and 13th harmonics and a high-pass filter take them (Harmonics).
- State when the design includes no SVG.
Answer 6
A plant with synchronous generators, a thermal plant for example, and a switching substation have none (In the design).
[1]CEA, Studies for Dynamic Compensation, Proposal for Dynamic Compensations in Northern Region, Eastern Region, Western Region and Southern Region. §2.3.
[2]Masood and others 2010, STATCOM Model against SVC Control Model Performance Analyses Technique by Matlab.
[3]Cahier Technique 142, Cahier Technique no. 142: Control equipment for MV capacitor banks.
[4]MIT 6.061 Notes Ch. 2, 6.061 Introduction to Power Systems, Class Notes Chapter 2: AC Power Flow in Linear Networks. §9.
[5]IEEE 1031-2011, IEEE Guide for the Functional Specification of Transmission Static Var Compensators.
[6]IEC 61954:2021, Static VAR compensators (SVC), Testing of thyristor valves.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.