Harmonics and voltage unbalance

The voltage and current of a power network are meant to be sine waves at the network frequency, equal in the 3 phases. Converters and some other loads draw currents that are not sinusoidal. Unequal loads on the phases make the phase voltages differ. This topic explains harmonics, how they are measured and limited, and how filters remove them. It then explains voltage unbalance, and what the design provides for both.

Before this topic: Voltage, current and impedance in AC circuits · Active, reactive and apparent power

1What harmonics are

A periodic wave that is not a pure sine wave can be written as the sum of sine waves. One is at the network frequency, called the fundamental. The others are at whole multiples of it, called harmonics. The ratio of a harmonic's frequency to the fundamental's is its order:

(1)
Cahier Technique 152 §1
where
harmonic order
frequency of the harmonic of order Hz
frequency of the fundamental, the network frequencyHz

At 50 Hz, the 5th harmonic is at 250 Hz and the 7th at 350 Hz. A harmonic's size is given as its ratio to the fundamental, in percent. The distribution of these ratios over the orders is the wave's spectrum. Harmonic amplitudes generally fall as the order rises.

Figure 1 shows a current with a 5th harmonic of 20 % and a 7th of 14.3 %. These are the ratios of an ideal six-pulse rectifier bridge. The sum is no longer a sine wave.

−1.2−0.8−0.40.00.40.81.205101520Time (ms)Current per unit of the fundamental's peakWith the 5th and 7th harmonicsFundamental
Figure 1.One period of a sinusoidal current and of the same current with a 5th harmonic of 20 % and a 7th harmonic of 14.3 % added, per unit of the fundamental's peak. Its total harmonic distortion by Eq. (2) is 24.6 %.

2Total harmonic distortion

The total harmonic distortion (THD) measures the harmonics of a wave as one number. It is the root-mean-square value (RMS) of the harmonics over the RMS value of the fundamental, in percent. The Central Electricity Authority (CEA) Grid Standards Regulations 2010 define the voltage THD over the orders 2 to 40:

(2)
CEA Grid Standards Regulations 2010 Reg. 3(2)
where
total harmonic distortion of the voltage%
RMS voltage of the harmonic of order V
RMS voltage of the fundamentalV

The same form applied to the currents gives the current THD. The current in Figure 1 has a THD of 24.6 %. IEEE 519 states the current limits as a total demand distortion (TDD) instead. The TDD divides the harmonic current by the maximum demand current, not by the current at the moment. A lightly loaded converter can therefore have a high THD and a low TDD.

3Sources of harmonics

A load or a source whose current is not proportional to its voltage draws or injects harmonic currents. Static converters are the main source. A rectifier bridge of pulses produces the orders , with = 1, 2, 3 and so on. A six-pulse bridge therefore produces the 5th, 7th, 11th and 13th harmonics, and a twelve-pulse bridge the 11th, 13th, 23rd and 25th. Arc furnaces, discharge lighting and transformers driven into saturation are other sources.

A photovoltaic (PV) plant's inverters convert the panels' direct current to alternating current by switching at a high frequency. Measurements at a 1 MW PV installation found the 5th and 7th harmonic currents the largest of the low orders. They also found emission at higher frequencies, from 2 kHz to 150 kHz.

A static var generator (SVG) or static synchronous compensator (STATCOM) is also a converter, of the voltage-sourced type. Its harmonics depend on its converter design.

4Effects of harmonics

The main long-term effect of harmonics is heating. A harmonic current raises the RMS current for the same power, and adds losses in transformers, cables and machines. Capacitors are sensitive to them, since their losses rise with the square of the RMS current. Harmonic currents also cause vibration and noise in transformers and reactors. They interfere with communication and control circuits run beside the power cables, and they add errors to some meters.

The largest risk is resonance. A capacitor bank or a filter forms a parallel resonant circuit with the inductance of the network. At the resonance frequency, a small harmonic current produces a large harmonic voltage. The short-circuit power at a point of the network is , times the line voltage at the point times its fault level (Cahier Technique 158 §2.3). The order of this resonance follows from the short-circuit power at the bank and the bank's reactive power:

(3)
Cahier Technique 152 §5.2
where
order of the parallel resonance
short-circuit power at the capacitor bank's terminalsMVA
line voltage at the bankkV
three-phase fault current at the bankkA
reactive power of the capacitor bankMvar

If is at or near the order of an injected harmonic, the harmonic is amplified. The short-circuit power of the grid varies with its operating state, so the resonance moves with it.

5Limits at the grid connection

Harmonic limits apply at the point where a plant or a user connects to the grid. The CEA Connectivity Regulations 2007 require a wind or inverter-based generating station to keep its harmonic current injections within the limits of IEEE 519. The same clause limits its direct current (DC) injection to 0.5 % of its full rated output. Its flicker is limited by IEC 61000. The harmonics, the DC injection and the flicker are measured at least once a year.

The CEA Grid Standards Regulations limit the voltage distortion in the grid. The voltage THD and the largest individual harmonic may not exceed:

  • 1.5 % and 1.0 % at 765 kV
  • 2.0 % and 1.5 % at 400 kV
  • 2.5 % and 2.0 % at 220 kV
  • 5.0 % and 3.0 % from 33 kV to 132 kV

IEEE 519 sets its limits at the point of common coupling (PCC), the point on the public network nearest to the user where another user could be served. Its voltage limits, a THD and an individual harmonic, fall as the voltage at the PCC rises. Its current limits depend on the ratio of the short-circuit current to the maximum demand current at the PCC. A stronger network admits a larger harmonic current. A harmonic study shows whether a plant meets these limits.

6Harmonic filters

A harmonic filter gives the harmonic currents a path of low impedance, so that they flow in the filter and not into the grid. The resonant shunt filter is a reactor in series with a capacitor bank:

(4)
Cahier Technique 152 §7.1
where
tuning frequency of the filterHz
inductance of the filter reactorH
capacitance of the filter, per phaseF

At its tuning frequency , the filter's impedance falls to the resistance of its reactor, and it absorbs most of the harmonic current of that order. One branch is tuned to each harmonic to be removed, for example the 5th, 7th, 11th and 13th. Below its tuning frequency, the branch behaves as a capacitor and supplies reactive power at the fundamental.

Each tuned branch forms a parallel resonance with the network at a frequency below its own tuning. These resonances must fall between the harmonics present (Effects of harmonics). A damped filter adds a resistor across the reactor. It absorbs a wide band of harmonics and damps the resonances, at the cost of higher losses. An active filter injects a current equal and opposite to the harmonics.

7Voltage unbalance

In a balanced network the 3 phase voltages are equal. Unequal loads on the phases make them differ. The CEA Grid Standards Regulations define the voltage unbalance as the largest deviation of a phase voltage from the average, over the average:

(5)
CEA Grid Standards Regulations 2010 Reg. 2(1)(n)
where
voltage unbalance%
voltage of phase V
average of the 3 phase voltagesV

The regulations limit it to 1.5 % at 765 kV and 400 kV, 2 % at 220 kV and 3 % from 33 kV to 132 kV. They require bulk consumers and distribution licensees to avoid unbalanced loads. An unbalance can be described as a negative-sequence component of the voltages (Symmetrical components, Balanced sequence systems).

8In the design

Figure 2 shows the arrangement the design provides on a medium-voltage (MV) section. The harmonic study has a filter when you enter a rating, or when a limit is not met and it gives one. The design then places a harmonic filter bank on each MV section with that rating and tuning, with or without an SVG. When the study has no filter and the input Harmonic filter is on, its default, the design keeps a filter bay on each MV section beside the SVG, named reserved. The default project has 2 sections, each with an SVG of ±58 Mvar. Its harmonics are within the limits without a filter, so the bill of materials (BOM) specifies each reserved bay as 33 kV, rating per harmonic study (Reactive power equipment, The harmonic filters).

Figure 2.The plant's feeders inject harmonic currents into an MV section, where the tuned filter branch takes them, so that less reaches the transformer and the grid. The drawing is schematic and not to scale.

In the IEC + CEA / CBIP set, the design's harmonic study takes the inverters as harmonic current sources at the MV sections, with the inverter maker's spectrum or a typical one. It solves the network at each harmonic order, its reactances and susceptances at that order, with the grid at its maximum and at its minimum fault level. It compares the current into the grid with the IEEE 519 limits for harmonic current injection that the CEA Connectivity Regulations name, at the row for generation whatever the ratio of the short-circuit current to the load current. It compares the voltage there with the IEEE 519 voltage limits, and reports the CEA Grid Standards limits beside them. When a limit is not met, the study gives the smallest single-tuned filter, tuned below the lowest order over its limit, that meets them.

In the ANSI / IEEE set, the checklist item is answered from a harmonic study at the PCC. SubstationLayout calculates no voltage unbalance.

Review questions
  1. Define the order of a harmonic, and find the frequency of the 7th harmonic at 50 Hz.
    Answer 1

    The order is the ratio of the harmonic's frequency to the fundamental's, so the 7th harmonic is at 350 Hz (What harmonics are, Eq. (1)).

  2. Calculate the total harmonic distortion of a current with a 5th harmonic of 20 % and a 7th of 14.3 %.
    Answer 2

    By Eq. (2), the RMS of the 2 ratios gives a THD of 24.6 % (Total harmonic distortion).

  3. Name the harmonic orders a six-pulse rectifier bridge produces.
    Answer 3

    A bridge of pulses produces the orders , so a six-pulse bridge produces the 5th, 7th, 11th and 13th harmonics (Sources of harmonics).

  4. Explain why a capacitor bank can amplify a harmonic.
    Answer 4

    The bank forms a parallel resonance with the network's inductance at the order , where a small harmonic current produces a large harmonic voltage (Effects of harmonics, Eq. (3)).

  5. State the CEA limits on a plant's harmonic currents and on the voltage distortion at 220 kV.
    Answer 5

    A plant's harmonic current injections are held within IEEE 519, and the voltage at 220 kV is held to 2.5 % THD and 2.0 % for one harmonic (Limits at the grid connection).

  6. Explain how a tuned harmonic filter removes a harmonic.
    Answer 6

    Its reactor and capacitor resonate at the tuning frequency, where its impedance falls to the reactor's resistance, so it absorbs most of that harmonic's current (Harmonic filters, Eq. (4)).

Sources

[1]Cahier Technique 152, Cahier Technique no. 152: Harmonic disturbances in networks, and their treatment. §1; §5.2; §7.1.

[2]Cahier Technique 158, Cahier Technique no. 158: Calculation of short-circuit currents.

[3]CEA Grid Standards Regulations 2010, Central Electricity Authority (Grid Standards) Regulations, 2010. Reg. 3(2); Reg. 2(1)(n).

[4]CEA Connectivity Regulations 2007, Central Electricity Authority (Technical Standards for Connectivity to the Grid) Regulations, 2007.

[5]Mirus white paper on IEEE Std 519-2014, A Practical and Effective Way of Applying IEEE Std 519-2014 Harmonic Limits.

[6]Power Monitors white paper on IEEE 519-2014, Updates and Changes Made to the IEEE 519 in the 2014 Release.

[7]Varatharajan and others 2014, Harmonic Emission of Large PV Installations: Case Study of a 1 MW Solar Campus.

[8]IEC 61000, Electromagnetic compatibility (EMC).

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.