Surge arresters
A surge arrester limits the overvoltages that reach the insulation of a substation's equipment. It is connected between a phase conductor and earth, beside the equipment it protects. At the operating voltage it behaves almost as an insulator. When a lightning or switching surge arrives, it conducts the surge current to earth and holds the voltage at its terminals to its protective level. This topic explains how a metal-oxide arrester works, the ratings that describe it, how it is housed, where it is placed and how it is monitored.
Before this topic: Lightning, switching and temporary overvoltages · Earthing of the neutral · Bays and their equipment
1The task of a surge arrester
The insulation of a transformer, a breaker or a bushing has a withstand voltage that a surge can exceed. A surge arrester sets a level of transient overvoltage above which it operates. When a surge appears at its location, the arrester conducts and discharges the surge to earth. Once the voltage has fallen, it stops conducting the power-frequency current, and the circuit returns to normal. RUS Bulletin 1724E-300 §5.8.1 calls the surge arrester the basic protective device against transient overvoltages in a substation. Its older name is lightning arrester (LA), and the abbreviation marks it on the design's yard plan and in its tags.
An arrester limits the switching and lightning overvoltages (Lightning, switching and temporary overvoltages, Overvoltages and their classes). It does not limit the temporary overvoltages at power frequency, which last from fractions of a second to hours. It is instead rated to withstand them without damage, as the other equipment of the network is. The arrester's protective level must be low enough to protect the insulation. The arrester must also stay stable at the voltages it meets in continuous and temporary operation. Its characteristic links these requirements, so one cannot be changed without the other.
2From gapped arresters to metal-oxide arresters
The earlier valve arresters used resistors of silicon carbide in series with spark gaps. The resistance of silicon carbide is not non-linear enough to stay connected at the operating voltage, so the gaps isolated the resistors until a surge sparked them over. The gaps then had to interrupt the power-frequency follow current. These gapped arresters were rated by their sparkover voltages as well as by their discharge voltages.
The metal-oxide arrester uses resistors made mainly of zinc oxide. Their voltage-current characteristic is far more non-linear than that of silicon carbide. The current at the operating voltage is small enough for the resistors to stay connected without gaps. The arrester has no sparkover and passes into conduction as the voltage rises, with lower discharge voltages than the earlier designs. Metal-oxide arrester technology was in its early years at the beginning of the 1980s, when a testing standard for these arresters was developed (Hinrichsen, Metal-Oxide Surge Arresters p. 99).
Most arresters installed today are gapless metal-oxide arresters, although many gapped silicon carbide arresters remain in service. Metal-oxide designs with shunt gaps or series gaps also exist. RUS 1724E-300 §5.8.1 prefers and recommends metal-oxide arresters for their protective characteristics.
3The voltage-current characteristic
The voltage-current characteristic of a metal-oxide arrester describes its behaviour from the operating voltage to the largest surge currents. Figure 1 draws it with the peak voltage on a linear scale and the peak current on a logarithmic scale. The figure shows how far the current changes for a small change of voltage. In the example of an arrester in a 420 kV system in Hinrichsen's handbook of metal-oxide arresters, the characteristic spans 9 decades of current, from 30 µA to 40 kA.
The leakage region. At the highest phase-to-earth voltage of the network, a leakage current flows through the arrester. It is mostly capacitive, with a much smaller resistive part. In the same example its peak is approximately 1.1 mA. The arrester behaves almost as an insulator there. The continuous operating voltage and the rated voltage lie in this region (Ratings and terms).
The discharge region. Above the power-frequency voltages, a small rise of voltage brings a large rise of current. This part of the characteristic is for switching and lightning surges, which last milliseconds and microseconds. The voltage across the arrester while a surge current flows is its residual voltage. A power-frequency voltage held in this region would destroy the arrester in a fraction of a second.
Thermal stability. The power loss of the resistors at the operating voltage rises steeply with their temperature. The heat the housing can give off rises with temperature too, but much less steeply. The curves cross at a stable operating point and at a higher limit of thermal stability. A surge adds energy and raises the temperature. If the temperature stays below the limit, the arrester cools back to its operating point. If it reaches the limit, the arrester heats without end until it fails. This is thermal runaway, and the energy ratings of an arrester guard against it.
4Ratings and terms
The ratings of an arrester are defined in its test standard. IEC 60099-4:2014 covers gapless metal-oxide arresters for alternating current (AC) systems. IEEE C62.11 covers metal-oxide arresters with and without gaps. These standards use different terms for some ratings, and the table sets them side by side.
| Rating | IEC term | IEEE term |
|---|---|---|
| Highest power-frequency voltage applied without limit of time | Continuous operating voltage | Maximum continuous operating voltage (MCOV) |
| Power-frequency voltage for the temporary overvoltages | Rated voltage , held for 10 s | Duty-cycle voltage rating |
| Current that classifies the arrester | Nominal discharge current | Classifying current of the arrester's class |
| Residual voltage at a lightning current impulse of 8/20 µs | Lightning impulse protective level at | Discharge voltage at the stated current |
| Residual voltage at a switching current impulse of 30/60 µs | Switching impulse protective level | Switching surge protective level |
Continuous operating voltage. The continuous operating voltage is the root-mean-square value (RMS) of the power-frequency voltage that may be applied to the arrester continuously. IEEE C62.11 calls it the maximum continuous operating voltage (MCOV). It must lie above the highest continuous phase-to-earth voltage of the network, with an allowance for harmonics. In a solidly earthed system the minimum is
| minimum continuous operating voltage of the arrester, RMS | kV | |
| highest voltage of the network, phase to phase, RMS | kV |
RUS 1724E-300 §5.8.3.4 and §5.8.7.3.1 (Eq. 5-7) set the minimum MCOV of a solidly grounded system at the maximum line-to-ground voltage, the nominal voltage raised by 5 %. In an isolated or resonant earthed system, an earth fault raises the sound phases to the phase-to-phase voltage for long periods. There, is at least (Hinrichsen, Metal-Oxide Surge Arresters p. 42; Earthing of the neutral, The neutral and the earth-fault current).
Rated voltage. The rated voltage is not a voltage the arrester can hold without limit of time. It describes the arrester's capability against temporary overvoltages. The arrester holds its rated voltage for 10 s after it has absorbed its rated energy. For most metal-oxide arresters is 1.25 times , a ratio found by test rather than derived. The minimum rated voltage from the continuous voltage is therefore
The temporary overvoltages give a second minimum. A manufacturer publishes the arrester's power-frequency voltage versus time characteristic: the higher the voltage above , the shorter the time the arrester holds it. The factor read from it for the duration of a temporary overvoltage gives
| minimum rated voltage from the continuous operating voltage, RMS | kV | |
| minimum rated voltage from a temporary overvoltage, RMS | kV | |
| temporary overvoltage at the arrester, phase to earth, RMS | kV | |
| ratio of the voltage the arrester holds for the overvoltage's duration to its rated voltage |
The rated voltage chosen is the higher of and , raised to a standard step. The temporary overvoltage of a solidly earthed system follows from its earth fault factor, and its duration is the time the protection takes to clear the fault (Lightning, switching and temporary overvoltages, Temporary overvoltages). Without that information, Hinrichsen takes an earth fault factor of 1.4 for 10 s.
In a system earthed through a resistor, the protection clears an earth fault, so the raised voltage of the sound phases is a temporary overvoltage. A voltage counts as continuous when it is applied for more than 60 minutes (Hinrichsen, Metal-Oxide Surge Arresters p. 41). The earth fault factor of such a system can exceed the 1.4 of solid earthing, because the resistor makes the zero-sequence resistance larger than the positive-sequence reactance, outside the condition of effective earthing (Lightning, switching and temporary overvoltages, Temporary overvoltages). For isolated and resonant earthed systems, where the sound phases rise to the phase-to-phase voltage, Hinrichsen gives a factor of 1.73 or more (Metal-Oxide Surge Arresters p. 111). The overvoltage of the resistance-earthed system, with its clearing time, gives by Eq. (3) (Hinrichsen, Metal-Oxide Surge Arresters pp. 43 to 44). A rated voltage above the minimum makes the arrester more stable in service, as long as its protective level stays low enough. In the ANSI / IEEE set, the duty-cycle voltage rating takes the place of the rated voltage, and the MCOV is listed with it.
Nominal discharge current. The nominal discharge current is the peak of the lightning current impulse that classifies an arrester. IEC 60099-4:2014 uses 20 kA and 10 kA for station class arresters, and 10 kA, 5 kA and 2.5 kA for distribution class arresters (Hinrichsen, Metal-Oxide Surge Arresters pp. 10, 18). A 10 kA arrester can carry larger lightning currents without damage. The value matters because the lightning impulse protective level is stated at .
Protective levels. The lightning impulse protective level is the highest residual voltage while the nominal discharge current flows, as an impulse of 8 µs front and 20 µs to half value. The switching impulse protective level is the residual voltage at a switching current impulse, from 0.5 kA to 2 kA by the arrester's class. At the highest system voltages, the switching impulse protective level determines the arrester's protection. Both levels follow from the rated voltage, because the characteristic fixes the ratio of the residual voltages to for a given type of resistor.
Energy ratings. Up to its edition 2.2, IEC 60099-4 described the energy capability of a high-voltage arrester by a line discharge class, from 1 to 5. The class named the parameters of a test that discharged a charged line into the arrester. The edition of 2014 replaced it by a charge rating and an energy rating. The repetitive charge transfer rating describes the charge the resistors take in one event without damage. The thermal energy rating , in kJ per kV of rated voltage, describes the energy after which a station arrester still cools back to its operating point. Station class arresters are designated SH, SM or SL, for high, medium and low duty. Distribution class arresters are DH, DM or DL. The edition of 2014 converts the former classes to values of and , and class 3 converts to the minimum ratings of class SM. Hinrichsen notes that the conversion holds for an arrester of low protective level.
5Housings
The housing protects the resistor column from the weather, gives it the creepage distance that pollution requires and carries the mechanical loads. Arresters for high voltages are housed in porcelain or in polymer, and gas-insulated switchgear has metal-enclosed arresters filled with sulphur hexafluoride.
Porcelain. The resistor column sits in a porcelain housing closed by aluminium flanges, cemented to its ends. A sealing system at both ends keeps moisture out for the arrester's service life. A leaking seal is the failure most often reported for arresters. If an arrester is overloaded, an arc forms inside the housing and the pressure rises. A pressure relief device opens within milliseconds, and the gases vent so that the arc moves outside the housing.
Polymer. In the directly moulded design, the resistors are held in a cage of fibreglass-reinforced plastic rods, and silicone rubber is moulded directly onto them. No gas space remains inside, so an overload arc tears the housing open without a build-up of pressure. In the tube design, a composite hollow insulator of a fibreglass tube with silicone sheds replaces the porcelain. Silicone rubber is water repellent, and this improves its behaviour in polluted conditions. Polymer housings are lighter than porcelain, and at medium voltages they have almost replaced it.
Height and grading. An arrester for a high system voltage is too long for one housing, and its units are stacked in series. From a length of approximately 2 m, a grading ring at the top evens out the voltage along the column. Without it, the resistors near the high-voltage end would carry more than their share and could become thermally unstable.
6Placement and the separation distance
An arrester protects the equipment close to it, because a surge travels along the conductors and is reflected where the impedance changes (Lightning, switching and temporary overvoltages, Lightning overvoltages). A transformer winding acts on a steep surge almost as an open line end. A surge reaching it is reflected, and the voltage at the transformer rises towards twice the incoming wave. The arrester limits that rise only after its own reflection travels back to the transformer. Figure 2 shows the usual positions of the arresters, at the line entry and at the transformer.
At the transformer. Power transformers are sensitive to overvoltages, and RUS 1724E-300 §4.4.3 places arresters on each phase of both their primary and secondary sides. The highest protection comes from arresters as close as possible to the equipment. Transformers can be supplied with brackets for the arresters beside their bushings.
At the line entry. Arresters at the line entrance limit a surge as it enters the substation. On the line side of the circuit breaker, they also protect the breaker's open contacts (RUS 1724E-300 §4.4.3). A steep surge reaching an open breaker or isolator (disconnector, IEC 60050) is reflected at nearly twice its rate of rise (RUS 1724E-300 §5.8.9).
Separation distance. The separation distance runs from the arrester's connection on the line to the transformer bushing (RUS 1724E-300 §5.8.8.2.2). With the arrester close to the transformer, the reflections cancel almost at once. As grows, the cancellation comes later, and the voltage at the transformer can approach twice the arrester's discharge voltage. An arrester in a high-voltage substation protects a zone of up to approximately 60 m, and in a distribution system a few metres. The zone shrinks as the surge front grows steeper.
Lead length. The lead length is the conductor from the junction with the line to earth, without the arrester itself (RUS 1724E-300 §5.8.8.2.3). The surge current through it causes an inductive voltage drop that adds to the arrester's residual voltage:
| inductive voltage drop along the arrester's leads | kV | |
| inductance of the leads, approximately 1 µH per metre of a conductor clear of other parts | µH | |
| rate of rise of the surge current | kA/µs |
With 10 m of lead and a current rising at 10 kA/µs, the drop is 100 kV. The leads are therefore kept short, and the arrester is connected directly to the conductor that feeds the equipment. Its earth lead joins the earth mat, which bonds it to the frames of the protected equipment.
7Protective margin
The protective margin compares the withstand of the equipment's insulation with the voltage the arrester lets through. For lightning it is the ratio of the equipment's lightning impulse withstand, its basic lightning impulse insulation level (BIL) (Insulation levels, The ratings of a level), to the arrester's lightning impulse protective level. For switching surges it compares the switching impulse withstand with the switching impulse protective level.
RUS 1724E-300 §5.8.7.6 states the accepted practice as a ratio of 1.20 (a margin of 20 %) between the BIL and the arrester's lightning protective level. It states a ratio of 1.15 (15 %) between the switching impulse withstand and the switching protective level. Hinrichsen cites the safety factor of 1.15 of IEC 60071-2 for non-self-restoring insulation, applied to the overvoltage at the equipment's terminals, not at the arrester's. Hinrichsen states that, where the arrester is close to the equipment, a lightning impulse protective level below the equipment's withstand divided by 1.4 is normally adequate. A long separation distance, a steep front or an unusual arrangement calls for a calculation in the insulation coordination study (Overvoltage protection by surge arresters, Protective margin).
A lower rated voltage gives a lower protective level and a larger margin. It also stresses the arrester more at the operating and temporary voltages. The choice of an arrester balances protection against stability in service (The task of a surge arrester).
8Monitoring
The seal of an arrester's housing must keep moisture out over the arrester's intended life of 25 to 30 years (Hinrichsen, Metal-Oxide Surge Arresters p. 26). Overloads still occur, and monitoring devices record the arrester's operations and condition. A station arrester for monitoring stands on insulating feet, and its earth connection runs through the monitoring device.
Surge counter. A surge counter in the earth connection records the number of discharges with an electromechanical or electronic register.
Leakage current. A leakage current meter shows the current through the arrester at the operating voltage, and it is often combined with a surge counter in one housing. The total leakage current is mostly capacitive. A rise of its small resistive part can indicate ageing of the resistors, and recent monitors estimate that part from the third harmonic of the current. Hinrichsen notes that poor sealing of the housing is a greater risk to arresters than electrical ageing.
9Standards for arresters
IEC 60099-4:2014 is the test standard for gapless metal-oxide arresters in AC systems. IEC 60099-5:2018 gives recommendations for the selection and application of arresters in three-phase systems above 1 kV. In the ANSI / IEEE set, IEEE C62.11 is the test standard for metal-oxide arresters. IEEE C62.22 is the application guide for metal-oxide arresters protecting equipment of 1000 V and above. It covers substation equipment, distribution systems, overhead lines and large machines. Arresters are selected within the insulation coordination of IEC 60071-1 and IEC 60071-2.
10In the design
The design takes one arrester rating per voltage level from its level table and does not calculate it (Insulation levels, the table). At the default 220 kV high-voltage (HV) level, the equipment is rated 245 kV and 1050 kVp. The HV arresters are rated 216 kV, and the arresters at the transformers' 33 kV terminals 36 kV. In the ANSI / IEEE set, the level table gives a duty-cycle rating per level, 180 kV at 230 kV (Insulation levels, the table).
Placement. The design places HV arresters in the line bays and the transformer bays (Bays and their equipment). The default project has 1 line bay and 2 transformers. In the default line bay the arrester is the first device from the line, 4.0 m inside the line gantry. In a transformer bay it is the last device before the transformer, 9.0 m from the face of the tank, and its conductor runs on to the HV bushings. The single-line diagram (SLD) draws the arrester on a branch to earth, designated −F1 in the IEC + CEA / CBIP set (Graphical symbols, Symbols and designations).
Bill of materials. The bill of materials (BOM) line "Surge arrester, station class, with counter" specifies 216 kV rated, 10 kA, class 3. Its quantity is 9, for 3 line / ICT / reactor positions × 3, with 3 spares. Class 3 in that specification is the line discharge class of the earlier edition of IEC 60099-4 (Ratings and terms). The line "Surge arrester at ICT LV terminals" specifies 36 kV rated, 10 kA, with a quantity of 6.
Checklist. The rated voltage depends on the temporary overvoltage at the arrester, which the neutral earthing study gives (Earthing of the neutral, The HV system: solid earthing). The checklist item "Arrester rated voltage against temporary overvoltage" cites IEC 60099-4:2014 §5.1, Table 2 and §6.12. For the default project it reads Needs your review, to be answered from that study. In the ANSI / IEEE set, the checklist item for IEEE C62.11 and IEEE C62.22 is answered with the arresters' ratings and their application.
SubstationLayout calculates no protective levels, energy ratings, separation distances or protective margins, and performs no insulation coordination study.
- Explain why a metal-oxide arrester needs no series gaps.
Answer 1
Its characteristic is non-linear enough that only a small, mostly capacitive leakage current flows at the operating voltage, so the resistors stay connected (From gapped arresters to metal-oxide arresters, The voltage-current characteristic).
- State the difference between the continuous operating voltage and the rated voltage of an arrester.
Answer 2
The continuous operating voltage may be applied without limit of time, while the rated voltage is held for 10 s after the rated energy and describes the capability against temporary overvoltages (Ratings and terms).
- Find the minimum continuous operating voltage of an arrester in a solidly earthed system.
- Explain why the voltage at a transformer can exceed the arrester's residual voltage.
Answer 4
A surge reflected at the transformer raises its voltage until the arrester's reflection returns across the separation distance, and the lead inductance adds (Placement and the separation distance, Eq. (4)).
- Describe how a protective margin is formed.
Answer 5
It is the ratio of the equipment's impulse withstand to the arrester's protective level, with a ratio of 1.20 for lightning and 1.15 for switching surges in the practice of RUS 1724E-300 §5.8.7.6 (Protective margin).
- Name the checklist item on the arrester rating and the study that answers it.
Answer 6
The item "Arrester rated voltage against temporary overvoltage" reads Needs your review, and the neutral earthing study answers it (In the design).
[1]Hinrichsen, Metal-Oxide Surge Arresters, Metal-Oxide Surge Arresters: Fundamentals. p. 42; p. 44; p. 14.
[2]RUS Bulletin 1724E-300, Design Guide for Rural Substations.
[3]Siemens High-voltage surge arresters Product guide, High-voltage surge arresters: Product guide.
[4]ABB High Voltage Surge Arresters Buyer's Guide, High Voltage Surge Arresters Buyer's Guide.
[5]Hitachi Energy High-voltage surge arresters, High-voltage surge arresters.
[6]IEC 60099-5:2018, Surge arresters, Part 5: Selection and application recommendations.
[7]IEEE C62.11, IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits (> 1 kV).
[8]IEEE C62.22-2009, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems.
[9]IEC 60099-4:2014, Surge arresters.
[10]IEC 60071-1:2019, Insulation co-ordination.
[11]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.