Transformer protection

A fault inside a power transformer can burn its windings, rupture its tank and set its oil on fire. Its protection must detect an internal fault fast and with high sensitivity. It must not trip for the currents that a healthy transformer draws, such as the magnetising current when it is energised. This topic explains the transformer's differential protection with its bias and its restraint against inrush. It then explains restricted earth fault protection, overcurrent backup, the protection devices mounted on the transformer and overfluxing protection. It closes with what the design specifies for the protection of its transformers.

Before this topic: Principles of protection · Power transformers · Neutral earthing resistors

1Protections of a transformer

A transformer's relay protection usually includes differential relays, sudden pressure relays, overcurrent or distance relays and earth overcurrent relays (RUS Bulletin 1724E-300 §12.4.4.1). In the practice of the bulletin, transformers of 5 MVA and below are almost always protected by fuses, and relay protection is most often used from 10 MVA. Each installation is evaluated for the protection it needs (RUS 1724E-300 §12.4.4.1). Figure 1 shows the protections of a two-winding transformer with a resistance-earthed lower-voltage winding, the arrangement of the design's interconnecting transformer (ICT).

Figure 1.The protections of a two-winding transformer: the differential zone between the current transformers (CTs) at its breakers, the restricted earth fault zone of the lower winding, and the devices on the tank. The drawing is schematic and not to scale.

2Differential protection

Differential protection is a main protection of a transformer against internal faults (RUS 1724E-300 §12.4.4.1). It compares the currents entering the transformer with the currents leaving it, by the principle of Principles of protection, The differential principle. A transformer, unlike a bus, changes the current's magnitude and often its phase angle, and a healthy transformer draws a current that does not leave it. The relay must allow for these sources of false operate current (Behrendt, Fischer and Labuschagne §II):

  • the ratio of the transformer, which the CT ratios on its 2 sides do not match
  • the tap changer, which changes the transformer's ratio over its range
  • the phase shift between the primary and secondary currents of a transformer with a delta winding
  • the magnetising inrush current when the transformer is energised (Magnetising inrush)
  • the high exciting current of an overexcited transformer (Overfluxing)

The relay corrects the magnitudes with a tap setting on each current input. The tap settings bring the currents of the 2 sides to a common base, by the transformer's voltage ratio and the CT ratios. The phase shift of the vector group (Transformer principles, Vector groups) is compensated by the connection of the CTs, or by its emulation in a digital relay. Older schemes used auxiliary CTs for the same purpose.

The remaining mismatch, from the tap changer's travel and the CTs' errors, grows with the current. A percentage restraint characteristic, the bias, solves it: the relay trips only when the operate current exceeds a percentage of the restraint current (Principles of protection, Figure 2). A minimum pickup secures the relay against the normal exciting current and against small CT differences at low load. A dual-slope characteristic, steeper at high currents, adds security against heavy CT saturation during an external fault (Behrendt, Fischer and Labuschagne §II). A transformer differential relay is device 87T, and it trips the breakers on all sides through a lockout relay, device 86. The lockout prevents the transformer from being energised again until the cause is found (RUS 1724E-300 §12.3.5).

3Magnetising inrush

A transformer draws a magnetising inrush current whenever its core flux is driven away from its steady-state value. The common cause is energisation, but the recovery of the voltage after an external fault and the energisation of a parallel transformer also cause it (Behrendt, Fischer and Labuschagne §III.A). The inrush current enters the transformer and does not leave it, so the differential relay measures it as operate current.

The flux in a core is the integral of the voltage applied to it. When a transformer is switched on at a voltage zero, the flux must change by its full swing in the first half cycle. Starting from zero, it reaches nearly twice its normal peak. The core is designed to work near saturation at the normal peak, so twice that flux saturates it, and the magnetising current rises steeply. It can exceed the transformer's rated full-load current. A residual flux in the core from an earlier operation, in the same direction, makes the inrush larger still.

The inrush current differs from a fault current in its waveform. It contains a direct current offset, odd harmonics and even harmonics. It is made of unipolar or bipolar pulses separated by intervals of low current. Its pulses decay slowly, much more slowly than the offset of a fault current (Behrendt, Fischer and Labuschagne §III.A).

Transformer differential relays detect the inrush by its harmonics, the second above all. A relay with harmonic restraint adds the harmonic currents to the restraint quantity, which raises its slope line during inrush (Behrendt, Fischer and Labuschagne §IV.A). A relay with harmonic blocking blocks its trip when a selected harmonic exceeds a set percentage of the operate current (Behrendt, Fischer and Labuschagne §IV.B). Early work found the second harmonic of the inrush current never below 16 % to 17 % of the fundamental. Energisation at reduced voltage, and some points on the voltage wave, give inrush currents with considerably less than 10 % (Behrendt, Fischer and Labuschagne §III.A). Modern relays therefore combine the harmonic methods, or add a recognition of the waveform's shape.

4Restricted earth fault protection

An earth fault in a star winding near its neutral may change the currents at the line terminals little, while the current in the neutral connection is large. In a winding earthed through a resistance, the fault current is limited further by the resistor (Neutral earthing resistors). The differential relay, set above the magnetising current and the mismatch, may not detect such a fault (Chowdhury and others, 2022, §I).

Restricted earth fault protection (REF) detects it. It compares the residual current of the winding's line terminals, 3 times the zero-sequence current, with the current in the winding's neutral connection, measured by a CT in the neutral. For an external earth fault, the 2 currents balance. For an earth fault in the winding, the neutral current has no matching residual current, or a residual current of opposite direction. The CTs restrict the zone to the winding between them, so the protection is selective for the faulted winding (Chowdhury and others, 2022, §I, §II). It is most valuable where the winding has low-resistance earthing (Neutral earthing resistors, Low-resistance and high-resistance earthing), where the differential protection is least sensitive to earth faults.

The protection must stay stable for an external fault that saturates one of its CTs. The element is therefore made directional, and its CTs are chosen and set for the maximum external fault (Chowdhury and others, 2022, §II, §V). It is device 87N, a differential relay in the neutral circuit (Principles of protection, Device function numbers).

5Backup protection

Overcurrent relays on the primary winding back up the differential protection (RUS 1724E-300 §12.4.4.1). Where they cannot be coordinated with the secondary main and feeder relays, a directional phase distance relay may replace them. An earth overcurrent relay is normally applied for its higher sensitivity to earth faults. A negative-sequence relay can be set sensitively as a further backup to the differential relay, since it does not respond to the load current (RUS 1724E-300 §12.4.4.1).

6The transformer's own devices

An oil-immersed transformer carries protection devices of its own, which detect what the relays cannot measure from outside. Power transformers, Parts of a power transformer describes them as parts of the transformer. Their protective role:

  • Buchholz relay. The relay in the pipe to the conservator gives an alarm on gas from a slow fault, and trips the transformer on the surge of oil from an arc.
  • Sudden pressure relay. It responds to the sudden rise of pressure in the tank from an internal fault, and not to slow changes of pressure (RUS 1724E-300 §12.3.12). Many engineers consider it the primary relay protection of a transformer (RUS 1724E-300 §12.4.4.1). It is a pressure switch, device 63.
  • Pressure relief device. It opens to relieve the pressure of an arc before the tank ruptures.
  • Oil and winding temperature indicators. The oil temperature indicator (OTI) reads the top oil temperature. The winding temperature indicator (WTI) reads the hot spot temperature of a winding, through an image coil and, where needed, auxiliary CTs. Each has adjustable alarm and trip contacts, besides the contacts that control the cooling (CEA standard specification for transformers and reactors, Ch. 2 §11.10, §11.11). A thermal relay of a transformer winding is device 49.

The Buchholz relay and the sudden pressure relay act on the mechanical effects of a fault in the tank. The thermal devices act on the heating of an overload, which the differential relay does not detect (RUS 1724E-300 §12.4.4.1).

7Overfluxing

The flux in a transformer's core is proportional to the applied voltage and inversely proportional to the frequency (Behrendt, Fischer and Labuschagne §III.B). Overvoltage, underfrequency or both raise the flux and can saturate the core. In per unit of the rated values:

(1)
Behrendt, Fischer and Labuschagne §III.B
where
peak flux in the coreWb
peak flux at the rated voltage and frequencyWb
applied voltagekV
rated voltage of the windingkV
frequencyHz
rated frequencyHz

An overexcited transformer heats, and its exciting current, noise and vibration rise. A severely overexcited transformer should be disconnected. The withstand depends on the time. A transformer of the CEA specification withstands overfluxing of 110 % continuously, 125 % for 1 min and 140 % for 5 s (CEA standard specification for transformers and reactors, Ch. 2 §5.1.11).

The differential relay is not the right protection for overfluxing, because the tolerable time is difficult to control through it (Behrendt, Fischer and Labuschagne §III.B). The overexcitation current is rich in odd harmonics, of which the fifth passes through the delta compensation of the relay. A fifth-harmonic restraint or blocking keeps the differential relay stable during a tolerable overexcitation. A separate volts per hertz relay, device 24, measures the ratio of voltage to frequency, with instantaneous or time-delayed characteristics (IEEE C37.2 as RUS 1724E-300 Appendix F reprints it). Its delays are chosen within the transformer's withstand. RUS 1724E-300 §12.4.4.1 names overvoltage relays for the same purpose.

8In the design

SubstationLayout sets no transformer protection and specifies none of its relays. It specifies the transformer and its earthing, which determine the protections the transformer needs.

The ICT. The default project has 2 ICTs of 160 MVA, 220/33 kV, vector group YNyn0, with an on-load tap changer of ±10 % (Power transformers). Its high-voltage (HV) neutral is solidly earthed, and its medium-voltage (MV) neutral is earthed through a neutral earthing resistor (NGR) rated 1000 A. The rated MV current of an ICT is 2799 A. An earth fault in the MV winding near its neutral is therefore limited well below the rated current, which is the case for which restricted earth fault protection is applied (Restricted earth fault protection).

CTs. The ICT's HV CTs stand in its transformer bay, and its MV CTs in its MV incomer panel, 3150/1 A. These 2 sets bound the zone of a differential protection of the ICT. The design specifies no CT in the NGR's connection, which the restricted earth fault protection needs (Neutral earthing resistors, In the design).

Fittings. The bill of materials (BOM) line of the ICT names its rating, ratio, vector group, impedance, tap changer and cooling. It leaves the fittings, among them the Buchholz relay, the pressure relief devices and the temperature indicators, to the transformer's specification.

Review questions
  1. Name the sources of false operate current in a transformer differential relay.
    Answer 1

    The ratio mismatch, the tap changer, the phase shift of the vector group, the magnetising inrush and the exciting current of an overexcited transformer (Differential protection).

  2. Explain why energising a transformer at a voltage zero gives a large inrush current.
    Answer 2

    The flux must change by its full swing in the first half cycle and reaches nearly twice its normal peak, which saturates the core (Magnetising inrush).

  3. Explain why harmonic restraint alone may not secure a differential relay against inrush.
    Answer 3

    Energisation at reduced voltage and some points on the wave give inrush currents whose second harmonic is well below 10 % of the fundamental (Magnetising inrush).

  4. Describe how restricted earth fault protection detects a fault near the neutral of a star winding.
    Answer 4

    It compares the neutral current with the residual current of the line terminals, which balance for an external fault and do not for a fault in the winding (Restricted earth fault protection).

  5. Calculate the flux, in per unit, of a transformer at 1.1 per unit voltage and 0.95 per unit frequency.
    Answer 5

    By Eq. (1) the flux is 1.1 divided by 0.95, 1.16 per unit, above the 110 % that a transformer of the CEA specification withstands continuously.

  6. Give the reason the differential relay is not used to trip a transformer for overfluxing.
    Answer 6

    The tolerable time of overexcitation is difficult to control through it, so a separate volts per hertz relay trips with delays chosen within the withstand (Overfluxing).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[2]Behrendt, Fischer and Labuschagne, Considerations for Using Harmonic Blocking and Harmonic Restraint Techniques on Transformer Differential Relays. §III.B.

[3]Chowdhury and others, 2022, Restricted Earth Fault Protection in Low-Impedance Grounded Systems With Inverter-Based Resources.

[4]CEA standard specification for transformers and reactors, Standard Specifications and Technical Parameters for Transformers and Reactors (66 kV & above voltage class).

[5]IEEE C37.2-1996, Standard Electrical Power System Device Function Numbers.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Transformer protection, revision 2, 9 Nov 2026, https://substation.solarlayout.app/library/reference/transformer-protection