Insulators and bushings

An insulator holds a live conductor away from earthed parts and carries its mechanical loads. A bushing carries a live conductor through an earthed wall, such as the tank of a transformer or the enclosure of gas-insulated switchgear. Both must withstand the operating voltage and the overvoltages of their level, wet or dry, clean or polluted, over a long service life. This topic explains the types of insulator in a switchyard and their materials, the creepage distance that pollution requires, and how a condenser bushing grades its field. It closes with the insulators and bushings the design specifies.

Before this topic: Lightning, switching and temporary overvoltages · Bays and their equipment

1The duties of an insulator

An insulator has an electrical and a mechanical duty. Electrically, it holds the voltage between a live part and earth across 2 paths. One is the air around it. The other is its own surface, along which a current can leak when the surface is wet and dirty. Cahier Technique 151 calls these the air clearance and the creepage distance (p. 10; Creepage distance and pollution). Mechanically, it carries the weight of the conductor and of ice, the force of the wind, the tension of a strung conductor and the forces of a short circuit.

The insulator's withstand voltages are those of its level: the lightning impulse withstand, its basic lightning impulse insulation level (BIL), and at the higher levels the switching impulse withstand (Insulation levels, The ratings of a level). RUS Bulletin 1724E-300 lists apparatus insulators by BIL and notes that a higher BIL may suit an area of extreme contamination (§4.8.1.2). The withstand of the air falls with altitude, and above 1000 m the bulletin reduces the BIL by a correction factor (Insulation levels, Altitude).

Insulation is coordinated so that a flashover, if it occurs, goes to earth and not between phases. The quantity of suspension insulators in a string is chosen on this basis: too few cause needless flashovers, and too many can move a flashover to the phase-to-phase path (RUS 1724E-300 §4.8.2.2, §4.9).

2Post insulators

Apparatus insulators support rigid buses and the live parts of equipment above earth. RUS 1724E-300 describes 2 types, cap-and-pin and post (§4.8.1). The cap-and-pin type was the original insulator of substation construction. The post type is the one most used today and the one the bulletin recommends for new construction.

A porcelain post insulator is one piece of electrical-grade wet-process porcelain with a number of sheds, the skirts that lengthen its surface. Metal end caps for mounting are cemented to it. The sheds of a post are short, so a flashover seldom damages them. If some sheds break, the dry arcing distance through the air from cap to cap changes little and the insulation usually holds (RUS 1724E-300 §4.8.1.4). The bulletin uses single, non-stacking posts up to 69 kV (BIL 350 kVp), and stacking units from 115 kV (BIL 550 kVp) upwards.

Figure 1 shows a stacked post on the left. Its creepage path runs over the sheds, and its arcing distance runs straight from cap to cap.

Figure 1.The types of insulator in a switchyard: a stacked station post, a cap-and-pin disc string and a composite long rod. The creepage path follows the surface over the sheds, and the arcing distance runs through the air. The drawing is schematic and not to scale.

Mechanical rating. The cantilever strength, the force at the top square to the axis, is the most important mechanical rating of a post insulator. Tensile, compressive and torsional strength matter in some uses (RUS 1724E-300 §4.8.1.6). Posts are rated equally upright and underhung. Mounted horizontally, they carry their own weight, the bus and the fittings as a bending load, and some manufacturers reduce the allowable loads. The strength needed follows from the bus loads and above all from the short-circuit forces (RUS 1724E-300 §4.11.1.6).

Polymer posts. Post insulators are also made of polymer. RUS 1724E-300 notes that a polymer post is less rigid than a porcelain one and does not recommend it for switch supports (§4.8.1.4).

3Suspension insulators

Suspension insulators insulate and support the strung buses of a substation (Busbars and conductors, Strung buses and flexible conductors). The conventional unit is a cap-and-pin disc, 25.4 cm in diameter and 14.6 cm long, with a clevis or a ball-and-socket connection (RUS 1724E-300 §4.8.2.1). Each disc carries a metal cap on its top and a metal pin below it, and the units hang in series to form a string (Figure 1). The discs are made of porcelain, glass or polymer. IEC 60305 gives the characteristics of ceramic and glass cap-and-pin units for overhead lines.

Number of units. The voltage a string withstands grows with its number of units. RUS 1724E-300 gives a minimum quantity of standard units per system voltage and BIL, for example 14 at 230 kV with a BIL of 1050 kVp (Table 4-6). More units are added above 1000 m, in areas of high contamination, for a dead-end on a steel structure and for a string far from vertical.

Mechanical rating. A suspension insulator is rated by its combined mechanical and electrical strength, an ultimate strength. Its proof test load is half that rating. The bulletin limits the working load of a porcelain string to 40 % of its rating (RUS 1724E-300 §4.8.2.3, §4.12.1.5).

Long rod insulators. A long rod insulator is one long insulating body in place of a string of discs. IEC 60433 covers the ceramic long rod. A composite long rod has a rod of glass-fibre reinforced plastic, which carries the tension, inside a housing of silicone rubber with sheds. Metal end fittings are crimped onto the rod (Siemens High-Voltage Products, pp. 98 to 100). It serves as a suspension or a tension insulator.

4Porcelain, glass and composite

Porcelain is the traditional material of apparatus insulators and bushings. It is fired and glazed, and the metal fittings are cemented to it (RUS 1724E-300 §4.8.1.4). Purchase specifications require homogeneous, fully vitrified porcelain, impervious to moisture, with a uniform glaze (BHEL specification TB-316-369-012, §3.18.2, §3.18.3).

Glass is used for cap-and-pin suspension discs, with porcelain and polymer (RUS 1724E-300 §4.8.2.1).

Composite insulators share the duties between 2 materials. A fibre-reinforced plastic core carries the load, and a polymer housing, usually silicone rubber, gives the insulating surface and the sheds. Silicone rubber is water repellent, so no continuous conductive layer forms on it even when it is polluted, and this improves its behaviour in polluted conditions (Hinrichsen, Metal-Oxide Surge Arresters p. 33). The property can be lost under constant moisture over a long period, so a silicone housing is normally given the creepage distance of a porcelain one (Hinrichsen, Metal-Oxide Surge Arresters p. 58). A composite insulator is lighter than a porcelain one. The same construction houses surge arresters and bushings (Surge arresters, Housings, Bushings).

5Creepage distance and pollution

The creepage distance of an insulator is the shortest path between its metal ends along its outer surface. Clean and dry, an insulator's surface withstands about as much as the air beside it. Rain, and above all wet pollution, reduce that withstand considerably (Cahier Technique 151 p. 11). Salt fog near the coast and dust in industrial areas are typical sources of such pollution (Siemens High-Voltage Products p. 99). In areas of high contamination, RUS 1724E-300 uses insulators with longer creepage distances or higher BILs to prevent electrical breakdown from surface contamination (§4.8.1.5). The sheds of an insulator are there to increase its creepage distance (IEC TS 60815-1:2025, 3.1.3).

The IEC TS 60815 series guides the selection and the dimensions of high-voltage insulators for polluted conditions. Part 1 (IEC TS 60815-1:2025) gives the definitions, the methods for evaluating the site pollution severity and the principles of selection. Parts 2, 3 and 4 cover ceramic and glass insulators for alternating current, polymer insulators for alternating current, and insulators for direct current. The method classes the site's pollution severity and takes a reference creepage distance for the class. It then corrects that distance for the candidate insulator's profile and diameter, the altitude and the type of network. The series does not deal with ice and snow.

Unified specific creepage distance. The creepage distance needed grows with the voltage. It is therefore stated per kV, as the unified specific creepage distance (USCD):

(1)
Hinrichsen, Metal-Oxide Surge Arresters p. 150
where
unified specific creepage distancemm/kV
creepage distance of the insulatormm
highest voltage for equipment, phase to phase, root-mean-square valuekV

The USCD takes the phase-to-earth voltage as its reference. The first edition of the series, of 1986, used the specific creepage distance (SCD), which takes the phase-to-phase . The SCD and the USCD differ by the factor . An insulator with a creepage distance of 10 500 mm at 420 kV has an SCD of 25 mm/kV and a USCD of 43.3 mm/kV (Hinrichsen, Metal-Oxide Surge Arresters pp. 141 and 150).

the table gives the classes of site pollution severity of the 2008 edition of IEC TS 60815-1 and the USCD recommended for each, as Hinrichsen lists them (p. 129). The edition of 2025 adds a class f, extremely heavy, for sites where class e is not enough, and specifies no reference value for it.

ClassSite pollution severityUSCDSCD
aVery light22.0 mm/kV12.7 mm/kV
bLight27.8 mm/kV16 mm/kV
cMedium34.7 mm/kV20 mm/kV
dHeavy43.3 mm/kV25 mm/kV
eVery heavy53.7 mm/kV31 mm/kV

Indian utility specifications can state the creepage distance in the older form. One requires at least 25 mm/kV of , 6125 mm at 245 kV (KSEB current transformer specification, Technical Particulars). Another requires 10 500 mm at 420 kV and 6125 mm at 245 kV for a heavily polluted site (BHEL specification TB-316-369-012, §3.1.1). These are the SCD of class d.

Creepage is one remedy among several. RUS 1724E-300 also names a higher BIL and, in contaminated locations, clearances one step above the usual (§4.8.1.5, §4.9). Composite housings resist pollution through their water-repellent surface (Porcelain, glass and composite). The edition of 2025 of IEC TS 60815-1 recognises a reduced creepage distance for insulators of a hydrophobicity transfer material.

6Bushings

A bushing insulates a high-voltage conductor that passes through a metal enclosure or a building wall. Transformers, buildings, gas-insulated switchgear (GIS) and generators need them. The sides of a bushing can be oil and air, oil and gas, oil and oil, SF6 and air, or air and air (Siemens High-Voltage Products p. 78).

The condenser core. At the flange, the conductor at full voltage passes close to the earthed wall. A condenser bushing grades the field between them with a core of insulating paper or synthetic fabric, wound on the conductor or on a central tube. Conductive foils, usually aluminium, are wound into the core at calculated distances. They divide the insulation into coaxial capacitors in series and control the field radially and axially (Siemens High-Voltage Products p. 79). The voltage along the bushing's surface becomes nearly linear, which keeps the stress on the surrounding air low (Siemens High-Voltage Products p. 82). Figure 2 shows the foils in section.

Figure 2.A condenser bushing on a transformer. The foil layers of the condenser core grade the voltage from the conductor to the earthed flange, both radially and along the bushing. The air side carries sheds of porcelain or silicone, and the oil side lies in the tank. The drawing is schematic and not to scale.

Oil-impregnated paper (OIP). The core is wound of paper with aluminium foil layers and impregnated with insulating mineral oil. The bushing is sealed and filled with oil, and its insulators are usually porcelain (Siemens High-Voltage Products p. 79; Hitachi Energy, bushing technologies).

Resin-impregnated paper (RIP). The core is wound of crepe paper and impregnated with a curable resin under vacuum, so the bushing is dry and holds no oil. Its outer insulation is a composite insulator with silicone sheds, or porcelain. Resin-impregnated synthetic (RIS) replaces the paper by a synthetic fabric. It does not absorb water and is easier to keep in storage (Hitachi Energy, bushing technologies).

Test tap. The mounting flange carries an integrated test tap (Siemens High-Voltage Products p. 79). Monitoring of a condenser bushing in service reports its capacitance and its dissipation factor, tan δ (Hitachi Energy, bushing technologies).

GIS bushings. A bushing connects GIS to an overhead line, with SF6 inside and air outside. Up to 245 kV such bushings can be of an electrode design, and above 245 kV of a condenser design. Composite housings are increasingly used, especially at the higher voltages and in polluted areas (Siemens High-Voltage Products p. 83). An oil-to-gas bushing connects a transformer directly to GIS (Siemens High-Voltage Products p. 81).

7In the design

Bus post insulators. The design supports the tubes of the high-voltage (HV) main buses on bus post insulators (BPI) (Busbars and conductors, In the design). For the default 220 kV project, the bill of materials (BOM) line "Bus post insulator" specifies 245 kV, solid core, 8 kN. Its quantity is 54, for 6 tubes × 72 m at 9 m spans, with 6 spares, 10 % of the quantity. Each BPI stands on a "Bus post insulator support", galvanised, 6.7 m.

Insulation levels. The BPI's specification names the level's highest voltage for equipment. The equipment of the default level is rated 245 kV with a BIL of 1050 kVp (Insulation levels, the table). The yard keeps the bottom of the insulators at least 2.5 m above ground, the value of the Central Electricity Authority (Yard layout, Bay width, phase spacing and heights). In the ANSI / IEEE set this is 2.60 m, by the National Electrical Safety Code (NESC) 2007 Rule 124A3 (Clearances of the ANSI / IEEE set, The NESC 2007 clearances).

SF6/air bushings. A gas-insulated HV yard leaves the hall through SF6/air bushings at its line and reactor exits (Gas-insulated switchgear (GIS), Exits and links). The single-line diagram marks each exit as an SF6/air bushing, a gas-insulated bus duct (GIB) or a cable end. The default project in GIS has the BOM line "SF6/air bushing, outdoor", 245 kV, 1600 A, silicone housing. Its quantity is 3, for 1 line and reactor exit × 3. The GIS yard's BOM has no bus post insulator line, since its main buses are inside the hall, against 54 BPIs for the same project in air-insulated switchgear (AIS).

Transformer bushings. The transformer's bushings are part of the transformer and have no BOM line of their own. The HV connection runs from the bay's surge arresters to the HV bushings (Surge arresters, Placement and the separation distance). The lightning protection step takes the bushing tops, at 7.5 m for the default level, as a protected level (Direct stroke shielding by the rolling sphere, Spheres of the protected levels).

The design takes no site pollution severity and specifies no creepage distance for its insulators and bushings. It calculates no cantilever load on a BPI and specifies no suspension insulator string.

Review questions
  1. Name the 2 paths across which an insulator holds its voltage.
    Answer 1

    The air clearance through the air beside it and the creepage distance along its surface, which wet pollution weakens (The duties of an insulator, Creepage distance and pollution).

  2. Explain why insulator strings are coordinated with the phase spacing.
    Answer 2

    Too few units cause needless flashovers, and too many can move a flashover from the path to earth to the path between phases (The duties of an insulator).

  3. Calculate the unified specific creepage distance of an insulator with 10 500 mm of creepage at 420 kV.
    Answer 3

    By Eq. (1) it is 10 500 mm divided by kV, 43.3 mm/kV, the value of class d (the table).

  4. Describe how a condenser bushing controls its electric field.
    Answer 4

    Conductive foils wound into its paper or fabric core divide the insulation into coaxial capacitors in series, which grade the field radially and along the bushing (Bushings).

  5. Compare OIP and RIP bushings.
    Answer 5

    An OIP core is paper impregnated with mineral oil in a sealed, oil-filled bushing, while an RIP core is paper impregnated with a cured resin, so the bushing is dry (Bushings).

  6. State the BOM line of the bus post insulators of the default project.
    Answer 6

    The line "Bus post insulator" specifies 245 kV, solid core, 8 kN, with a quantity of 54 and 6 spares (In the design).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[2]Cahier Technique 151, Cahier Technique no. 151: Overvoltages and insulation coordination in MV and HV.

[3]Hinrichsen, Metal-Oxide Surge Arresters, Metal-Oxide Surge Arresters: Fundamentals. p. 150.

[4]Siemens High-Voltage Products, High-Voltage Products.

[5]Hitachi Energy, bushing technologies, Transformer bushings: technologies.

[6]IEC TS 60815-1:2025, Selection and dimensioning of high-voltage insulators intended for use in polluted conditions, Part 1: Definitions, information and general principles.

[7]KSEB CT specification, Technical Specification: 220 kV & 110 kV Current Transformers (Live / Dead Tank Type) of Various Ratings and Supporting Structures.

[8]BHEL specification TB-XXX-316-019, Technical Specification for ACSR (Moose / Bersimis / Zebra) & AAC (Bull) Conductor.

[9]IEC 60305, Insulators for overhead lines with a nominal voltage above 1000 V: Ceramic or glass insulator units for a.c. systems, Characteristics of insulator units of the cap and pin type.

[10]IEC 60433, Insulators for overhead lines with a nominal voltage above 1000 V: Ceramic insulators for a.c. systems, Characteristics of insulator units of the long rod type.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Insulators and bushings, revision 4, 9 Nov 2026, https://substation.solarlayout.app/library/reference/insulators-and-bushings