Power cables and terminations

A power cable carries a circuit underground or through a building, where an overhead conductor cannot run. In a substation it connects a gas-insulated switchgear (GIS) to its transformers or lines, the medium-voltage (MV) switchgear to the plant's feeders, and the auxiliary supply to its loads. This topic explains how a cable with cross-linked polyethylene (XLPE) insulation is built, how its metallic screens are bonded and why, and how it is terminated and jointed. It then explains what sets a cable's current rating, how a cable is tested, and where the design uses cables.

Before this topic: Gas-insulated switchgear (GIS) · Three-phase systems

1Cables in a substation

A substation uses control cables, low-voltage and medium-voltage power cables, and high-voltage cables. Control and low-voltage cables connect the relays, meters and auxiliary loads. Medium-voltage cables supply the station service transformers and carry the bus ties and the feeders that leave the substation underground (RUS Bulletin 1724E-300 §10.3.1). High-voltage cables connect a GIS hall to the transformers and lines outside it, or carry a line underground where an overhead route is not available.

A high-voltage cable costs more than the overhead line it replaces. RUS 1724E-300 gives a rule of thumb of 3 to 20 times the cost of overhead construction. It limits high-voltage cables to special applications, such as environmental and right-of-way restrictions (RUS 1724E-300 §10.3.12). An example is the specification of the Uttar Pradesh transmission utility for a 220 kV GIS substation. It connects the indoor switchgear to an outdoor line by single-core XLPE cables in trefoil, laid on racks in trenches (UPPTCL 220 kV XLPE cable specification §1.1).

2Construction of an XLPE cable

A shielded power cable, as used from 2 kV up (RUS 1724E-300 §10.3.1), is a set of concentric layers around the conductor. Each layer has its own task, and Figure 1 draws them in the order this section describes them, from the centre outwards.

Figure 1.The layers of a single-core XLPE cable, from the conductor at the centre to the outer sheath. The drawing is schematic and not to scale.

Conductor. The conductor is copper or aluminium, stranded and compacted. Large conductors are built of segments or of shaped wires. A swelling material between the strands can seal the conductor against water along its length (ABB XLPE cable user's guide, pp. 4 and 16).

Conductor screen. A semiconducting layer covers the conductor. It smooths the outline of the outer strands, so that the electric field lines in the insulation are not distorted by the shape of the strands (RUS 1724E-300 §10.3.3).

Insulation. The insulation holds the full voltage between the conductor and earth. Cross-linked polyethylene, ethylene propylene rubber and tree-retardant XLPE are the common insulations of medium-voltage cables (RUS 1724E-300 §10.3.4). In a high-voltage cable the conductor screen, the XLPE insulation and the insulation screen are extruded together in one pass, so that their interfaces are not exposed during manufacture (ABB XLPE cable user's guide, p. 17).

Insulation screen. A second semiconducting layer covers the insulation. With the metallic screen over it, it confines the electric field within the cable and equalises the voltage stress in the insulation. It also limits interference and reduces the shock hazard (RUS 1724E-300 §10.3.5).

Metallic screen or sheath. The metallic layer is copper wires, copper tape, an extruded lead alloy sheath or a smooth or corrugated aluminium sheath (IS 7098 (Part 3) §14.3.1). It carries the leakage currents to earth and, in some designs, the earth fault current (RUS 1724E-300 §10.3.5). A lead or aluminium sheath, or a metal foil bonded to the outer sheath, keeps water out radially (ABB XLPE cable user's guide, p. 17).

Outer sheath. An extruded sheath of polyethylene or polyvinyl chloride covers the metallic layer and protects it from moisture and damage. A conductive coating on the outer sheath allows the integrity of the sheath to be tested after laying (ABB XLPE cable user's guide, p. 4).

XLPE cables operate with a conductor temperature of up to 90 °C in normal operation and 250 °C under short circuit. IS 7098 (Part 2) states these limits for XLPE cables from 3.3 kV to 33 kV (§1.2), and the utility's specification states them for its 220 kV cable (UPPTCL 220 kV XLPE cable specification §4.4).

3Single-core and three-core cables

A three-core cable holds the 3 phases in one sheath. A single-core cable holds one phase, and a three-phase circuit needs 3 of them. The choice depends on the voltage and the conductor size.

IS 7098 (Part 2) covers XLPE cables from 3.3 kV to 33 kV. It lists single-core cables, screened or unscreened, and three-core cables, armoured, screened or unscreened (IS 7098 (Part 2) §1.1). A single-core armoured cable takes a non-magnetic armour there. The standard writes a cable's voltage grade as , for example 19/33 kV. The first value is near the phase-to-earth voltage of a 33 kV system, 33 kV divided by , and the second is the phase-to-phase voltage (Three-phase systems, Phase and line quantities).

Above 30 kV the cables of IEC 60840 are single-core cables and individually screened three-core cables, up to 150 kV. Above 150 kV IEC 62067 covers single-core cables only, up to 500 kV. The 3 single-core cables of a circuit are laid in trefoil, touching at the corners of a triangle, or in flat formation side by side. The choice depends on the bonding of the screens, the conductor size and the space available (ABB XLPE cable user's guide, p. 7).

4Bonding of the metallic screens

The bonding of the screens determines 2 quantities of a single-core circuit: the current in the screens and the voltage on them. Both affect the current rating and the safety of the circuit.

The current in the conductor of a single-core cable sets up a magnetic field that links the metallic screen. The field induces a voltage along the screen, proportional to the cable length and to the current (ABB XLPE cable user's guide, p. 7). If the screens of a circuit are connected to each other and to earth at both ends, the induced voltages drive a current around the loop. If the screens are earthed at one point only, no current flows, and the voltage appears at the open end. Figure 2 draws the 3 bonding methods.

Figure 2.The bonding methods of the metallic screens of a single-core cable circuit: both-ends bonding, single-point bonding with sheath voltage limiters (SVLs) at the open end, and cross-bonding in 3 sections with link boxes. The drawing is schematic and not to scale.

Both-ends bonding. The screens are joined and earthed at both ends of the circuit. They provide a path for circulating currents in normal operation. These currents cause losses in the screens, and the losses lower the current the cable can carry. The losses are smaller in trefoil than in flat formation with spacing (ABB XLPE cable user's guide, p. 7). One manufacturer's rating tables show the size of the effect. A 69 kV to 138 kV cable with a copper conductor of 1000 kcmil (507 mm²) in a single circuit carries 570 A with both ends bonded. With single-point bonding or cross-bonding it carries 845 A (ABB XLPE cable user's guide, Table 2, at 100 % load factor). The utility's specification bonds its 220 kV cable at both ends (UPPTCL 220 kV XLPE cable specification §3.3).

Single-point bonding. The screens are earthed at one point, and they provide no path for circulating currents or external fault currents. A voltage is induced between the screens of adjacent phases and between screen and earth, but no current flows. The voltage rises with the cable length and the current, so the accepted screen voltage limits the route length (ABB XLPE cable user's guide, p. 7). The open end is connected to earth through a sheath voltage limiter (SVL) in a link box, which limits the voltage on the screen.

Cross-bonding. The route is divided into 3 sections. The screens are sectionalised at the joints and crossed over between the phases, so that the induced voltages of the 3 sections cancel over the route. The screens are earthed at both ends of the route, and no significant current flows. The highest induced voltage appears at the link boxes. Cross-bonding gives the current rating of single-point bonding on longer routes, but it needs joints with screen separation and link boxes (ABB XLPE cable user's guide, p. 7).

The bonding method follows from a calculation of the screen voltages and currents. The utility's specification requires a calculation of the screen voltage at full load and during an external three-phase fault. It also requires the bonding method that keeps the induced voltage within 65 V (UPPTCL 220 kV XLPE cable specification §1.2, §4.9). IEEE 575 covers the bonding systems of single-conductor shielded cables from 5 kV to 500 kV and the calculation of these voltages and currents. In the ANSI / IEEE set the metallic screen is called the shield.

5Terminations and joints

A cable ends at a termination and is extended by a joint. Both must control the electric field where the cable's insulation screen ends.

Field control. Inside the cable the insulation screen confines the field and keeps the stress in the insulation uniform. Where the screen is cut back at a termination, the field changes abruptly, and the stress concentrates on the insulation surface at the edge of the screen. This concentration can break the insulation down. A termination places a stress cone over the insulation at that point to spread the stress (RUS 1724E-300 §10.3.9).

Indoor and outdoor terminations. A termination indoors or in a controlled environment needs the stress cone only. Outdoors, contaminants settle on the termination and can cause flashover. An outdoor termination therefore adds skirts that lengthen the creepage path (RUS 1724E-300 §10.3.9). Its insulator is porcelain or a composite of a fibreglass tube with silicone sheds (ABB XLPE cable user's guide, p. 4).

GIS and transformer terminations. A cable entering a GIS ends in a cable termination inside a gas-filled connection enclosure. IEC 62271-209 covers this connection, with a barrier that separates the cable insulation from the gas insulation of the switchgear. It sets the interfaces so that cable terminations and switchgear of different manufacturers fit, and it sets the limits of supply between them. A cable entering a transformer ends in a termination in a cable box on the tank. For the cable box of a generator transformer, the standard specification for transformers and reactors of the Central Electricity Authority requires an oil-filled box that withstands the forces of a short circuit, to EN 50299 (Ch. 2 §16.1). Separable connectors serve medium-voltage switchgear and transformers (ABB XLPE cable user's guide, p. 4).

Joints. A cable joint, or splice, connects 2 lengths of cable. It is a short piece of cable built in the field, and it continues each layer of the cable to keep the stresses low (RUS 1724E-300 §10.3.9). A joint on a cross-bonded route also separates the screens and brings them out to the link box. Prefabricated termination and joint kits are the preferred practice (RUS 1724E-300 §10.3.9).

6Current rating

The current rating of a cable is the current that holds the conductor at its maximum temperature, 90 °C for XLPE in continuous operation. The conductor's temperature is set by the heat the cable produces and by the thermal resistance between the conductor and the surroundings.

Losses. The load current heats the conductor and, in a both-ends bonded circuit, the metallic screens. The dielectric losses in the insulation are present at no load and depend on the operating voltage (ABB XLPE cable user's guide, p. 8). IEC 60287-1-1 gives the equations for the current rating at 100 % load factor and for these losses. Its scope covers steady-state operation of cables buried directly in the ground, in ducts, troughs or steel pipes, and cables in air.

Thermal path. The heat flows from the conductor through the insulation, the sheath and any serving to the surface of the cable, and from there through the soil or the air. Each step has a thermal resistance per metre of cable, in K·m/W, and the standard writes them to from the insulation to the surrounding medium. The soil's thermal resistivity is the property that sets the last of them. It depends on the moisture of the soil and can change with the soil type, the terrain, the weather and the load of the cable itself, as the introduction of IEC 60287-1-1 notes.

Installation conditions. The rating falls when the heat cannot escape. A manufacturer's tables show how far the conditions move it (the table). The tables are for planning, and an accurate calculation confirms the rating once the layout is fixed (ABB XLPE cable user's guide, p. 12).

ConditionDirection of its effectRating factor in the manufacturer's tables (ABB XLPE cable user's guide, Tables 7 to 9)
Laying depthA deeper cable is rated lower1.11 at 0.3 m (1 ft), 1.00 at 0.9 m (3 ft), 0.89 at 3 m (10 ft)
Ground temperatureA warmer ground lowers the rating1.00 at 20 °C, 0.89 at 35 °C
Soil thermal resistivityA drier, more resistive soil lowers the rating1.00 at 0.9 K·m/W, 0.87 at 1.5 K·m/W, 0.68 at 3.0 K·m/W
GroupingCables close together heat each otherLower for 2 circuits than for 1 circuit

A group of cables heats itself, and in a duct bank the inner cables run hottest. Their current-carrying capacity is reduced by a position factor, which depends on the bank's configuration and spacing (RUS 1724E-300 §10.6.3). A cable specification states the conditions of its rating. The utility's specification, for example, states a ground temperature of 35 °C, a burial depth of approximately 1.5 m, trefoil formation and a soil thermal resistivity of 1.5 K·m/W, written 150 °C·cm/W there (UPPTCL 220 kV XLPE cable specification §3.3).

Fault current. A cable must also carry the fault current until the protection clears it. RUS 1724E-300 sizes the conductor and the screen for the available three-phase and line-to-earth fault currents, which can call for a larger conductor than the load (§10.3.8). A manufacturer's table gives the conductor's rating for 1 s. For another duration the rating scales with the square root of the time, since the heat of a short fault grows with :

(1)
ABB XLPE cable user's guide p. 13
where
short-circuit current the conductor or screen withstands for the duration kA
short-circuit current rating for 1 skA
short-circuit duration, from 0.2 s to 5.0 ss

The equation holds for durations from 0.2 s to 5.0 s, with a maximum conductor temperature of 250 °C for XLPE insulation. A cable may be overloaded for short periods, and IEC 60853 gives the method for cyclic and emergency ratings (ABB XLPE cable user's guide, p. 12).

7Testing

A cable system is tested at the factory and again after it is laid. The tests check the insulation, the sheath and the accessories.

Routine tests. Each manufactured length and accessory is tested before it leaves the factory: a partial discharge measurement, a high-voltage test of the main insulation and an electrical test of the outer sheath (ABB XLPE cable user's guide, p. 5). IEC 60840 sets these routine tests for cables above 30 kV up to 150 kV.

Sample and type tests. Sample tests on cables taken from production check the conductor, its resistance, the dimensions, the capacitance and the curing of the insulation (ABB XLPE cable user's guide, p. 5). Type tests on a complete cable system prove its design, with bending, partial discharge, heating cycle and impulse voltage tests among them. IEC 60840 adds a prequalification test of the cable system and sets electrical tests after installation.

Tests after installation. After laying, the outer sheath is tested with a direct current (DC) voltage, and the main insulation is tested with an alternating-current voltage (ABB XLPE cable user's guide, p. 5). The sheath test finds damage to the outer sheath from the laying, which would let water reach the metallic screen.

8In the design

The design uses a power cable in one place: the link of a gas-insulated high-voltage yard to its transformers. It models the cable's route and lists the cable and its sealing ends in the bill of materials (BOM). It does not size or rate a cable.

GIS links. A GIS yard reaches its interconnecting transformers (ICTs) by a gas-insulated bus duct at 220 kV and above, and by XLPE cable below (Gas-insulated switchgear (GIS), Exits and links). At 132 kV the yard has 2 cable links, of 7.5 m and 13.3 m on the yard layout. The single-line diagram marks the exit as a cable end. The yard plan places a cable end at the hall wall. Section B-B and the 3D model draw the XLPE cable in a trench from the hall to the transformer.

BOM lines. The BOM line "XLPE cable, single core, Cu" specifies 145 kV, rated for 1250 A. Its quantity is 69 m, for 2 transformer links × 3 phases + 10 %. The line "Cable sealing end (GIS) and outdoor termination" specifies 145 kV, IEC 62271-209, with a quantity of 6. The specification states the voltage and the bay's rated current, and leaves the conductor size and the bonding to the cable's supplier.

MV feeders. The default project's indoor MV switchgear has 17 feeder panels at 1250 A (Circuit breakers, MV switchgear). They feed the plant's collector cables, which the BOM does not list. In the ANSI / IEEE set, the indoor MV breakers take the preferred ratings of class S1 for cable systems, 1200, 2000, 3000 and 4000 A at 34.5 kV.

Auxiliary and control cables. The auxiliary supply drawing notes that the DC feeder fuses and cables are sized at detail design. The yard drawing notes that cable trenches are not part of the drawing set (Roads, trenches and buildings, Trenches, foundations and drainage in the design).

SubstationLayout sizes no cable conductor, calculates no current rating, screen voltage or bonding, and routes no cable or trench.

Review questions
  1. Name the layers of an XLPE cable from the conductor outwards.
    Answer 1

    The conductor, the semiconducting conductor screen, the XLPE insulation, the semiconducting insulation screen, the metallic screen or sheath, and the outer sheath (Construction of an XLPE cable).

  2. Explain why both-ends bonding lowers the current rating of a single-core cable circuit.
    Answer 2

    The screens joined and earthed at both ends carry circulating currents driven by the induced voltages, and the losses they cause heat the cable (Bonding of the metallic screens).

  3. Compare single-point bonding and cross-bonding.
    Answer 3

    Single-point bonding stops the circulating currents and leaves an induced voltage at the open end, which limits the route length. Cross-bonding cancels the induced voltages over 3 sections and allows longer routes (Bonding of the metallic screens).

  4. Explain the task of the stress cone of a termination.
    Answer 4

    Where the insulation screen is cut back, the stress concentrates at the edge of the screen, and the stress cone spreads it (Terminations and joints).

  5. State how the soil thermal resistivity affects the current rating.
    Answer 5

    A more resistive soil slows the heat leaving the cable, so the rating falls, from a factor of 1.00 at 0.9 K·m/W to 0.87 at 1.5 K·m/W in a manufacturer's tables (Current rating).

  6. Read the cable line in the BOM of a 132 kV GIS project.
    Answer 6

    The line "XLPE cable, single core, Cu" specifies 145 kV, rated for 1250 A, with a quantity of 69 m for 2 transformer links × 3 phases + 10 % (In the design).

Sources

[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[2]CEA standard specification for transformers and reactors, Standard Specifications and Technical Parameters for Transformers and Reactors (66 kV & above voltage class).

[3]ABB XLPE cable user's guide, XLPE AC Land Cable Systems: User's Guide. p. 13.

[4]UPPTCL 220 kV XLPE cable specification, Technical Specification of 220 kV XLPE Cable.

[5]IS 7098 (Part 2), Crosslinked polyethylene insulated thermoplastic sheathed cables, Part 2: For working voltages from 3.3 kV up to and including 33 kV.

[6]IS 7098 (Part 3), Cross-linked polyethylene insulated thermoplastic sheathed cables, Part 3: For working voltages from 66 kV up to and including 220 kV.

[7]IEC 60840:2020, Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV): Test methods and requirements.

[8]IEC 62067:2022, Power cables with extruded insulation and their accessories for rated voltages above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV): Test methods and requirements.

[9]IEC 60287-1-1:2006+AMD1:2014, Electric cables: Calculation of the current rating, Part 1-1: Current rating equations (100 % load factor) and calculation of losses, General.

[10]IEC 62271-209:2019, High-voltage switchgear and controlgear, Part 209: Cable connections for gas-insulated metal-enclosed switchgear for rated voltages above 52 kV.

[11]IEEE 575-2014, IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV.

[12]IEC 60853, Calculation of the cyclic and emergency current rating of cables.

[13]EN 50299, Oil-immersed cable connection assemblies for transformers and reactors having highest voltage for equipment Um from 72,5 kV to 550 kV.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.