Overvoltage protection by surge arresters
A surge arrester protects the insulation of the equipment beside it only if the voltage it lets through stays below what that insulation withstands. The comparison is the core of insulation coordination with arresters. It is not made at the arrester's terminals alone. A lightning surge travels along the conductors, and the voltage at the protected equipment rises above the arrester's residual voltage with the distance between them. This topic explains how the arrester's protective levels are compared with the equipment's withstand voltages, the safety factor and the protective margin, the separation distance and the protective zone, and the energy the arrester absorbs. It closes with what the design takes and places, and what it leaves to the insulation coordination study.
Before this topic: Lightning, switching and temporary overvoltages · Surge arresters · Insulation levels
1Insulation coordination with arresters
Insulation coordination selects the dielectric strength of the equipment for the overvoltages it can meet, with the protective devices in place. The arrester takes part in it as the device that sets the largest fast-front and slow-front overvoltage at the equipment. This section names the quantities of the procedure, because the checks of the later sections compare them.
IEC 60071-1 sets out the procedure, and Schneider Electric's Cahier Technique 151 (§4) describes its chain of steps. The first is the representative overvoltage , found from a study of the network and the protective levels of its arresters. The second is the coordination withstand voltage . It is the lowest withstand that meets the performance criterion, an acceptable rate of insulation failure, under the representative overvoltages. The coordination factor takes it from and allows for the statistical spread of the overvoltages and the inaccuracy of the data.
The third step converts into the required withstand voltage under standard test conditions. The atmospheric correction factor allows for altitude, and the insulation coordination safety factor for the dispersion of production, the quality of installation, ageing in service and other factors not known. The last step selects the standard withstand voltages from the standard insulation levels, at or above (Insulation levels, The ratings of a level).
| representative overvoltage of a class at the equipment | kVp | |
| coordination withstand voltage | kVp | |
| coordination factor | ||
| atmospheric correction factor for altitude | ||
| safety factor | ||
| required withstand voltage under standard test conditions | kVp | |
| standard withstand voltage of the equipment; for lightning, its basic lightning impulse insulation level (BIL) | kVp |
For the lightning impulse, the standard withstand voltage of a level is its BIL. The arrester's part is to keep the representative fast-front overvoltage at the equipment low. Hinrichsen (Metal-Oxide Surge Arresters p. 51) describes the representative fast-front overvoltage with arresters in IEC 60071-2. It is the arrester's lightning impulse protective level plus a term for the distance to the equipment, the corona damping and span length of the line, the number of lines and the rate of strokes to the line. The method is statistical and is set out in an annex of IEC 60071-2. The sections below use the simpler deterministic checks that the arrester guides give.
Figure 1 shows the voltages that the checks compare at the equipment's terminals. The arrester's protective level is the lowest of them. The rise between the arrester and the equipment, and the safety factor, take up part of the margin between the protective level and the BIL.
2Protective levels against the withstand voltages
The protective levels of an arrester are its residual voltages at standard current impulses (Surge arresters, Ratings and terms). This section states the criterion each must meet against the equipment's withstand, and why the lightning and the switching checks differ.
Lightning. Hinrichsen (Metal-Oxide Surge Arresters pp. 50, 138) states the rule of IEC 60071-2 for non-self-restoring insulation, such as a transformer winding. The highest lightning overvoltage at the equipment's terminals stays below its standard lightning impulse withstand divided by a safety factor of at least 1.15:
| highest voltage of a surge at the protected equipment's terminals | kVp |
In Hinrichsen's example, a 420 kV transformer of 1425 kVp withstand may be subjected to at most 1425 kVp / 1.15 = 1239 kVp at its bushings. An arrester of 790 kVp lightning impulse protective level leaves a wide reserve at its own terminals. The voltage at the bushings is higher, for 3 reasons: the travelling wave between the arrester and the equipment (The voltage at the protected equipment), the inductive drop along the arrester's leads (Surge arresters, Eq. (4)), and discharge currents above the nominal discharge current. For a current of twice the nominal value, the residual voltage rises by 5 % to 15 % (Hinrichsen, Metal-Oxide Surge Arresters p. 15). For the external insulation of its example of a 24 kV network, Cahier Technique 151 (§4) applies a smaller factor, 1.05, to the switching and lightning withstand.
Switching. A slow-front overvoltage reaches its peak in 20 µs to 5000 µs (Cahier Technique 151 §4). Over that time the travelling-wave rise and the lead drop are small, and the voltage at the equipment is the arrester's switching impulse protective level . That level must therefore not exceed the switching impulse withstand voltage (SIWL) divided by 1.15, and it need not be lower (Hinrichsen, Metal-Oxide Surge Arresters p. 52). The switching impulse residual voltage is typically 75 % to 90 % of the residual voltage at a 10 kA lightning current impulse (Hinrichsen, Metal-Oxide Surge Arresters p. 51). At the extra-high voltages the switching impulse protective level determines the arrester's protective characteristic.
A close arrester. Where the arrester stands close to the equipment, Hinrichsen states that a lightning impulse protective level equal to the BIL divided by 1.4 normally protects against fast-front overvoltages (Metal-Oxide Surge Arresters p. 15). The ratio is deterministic and serves as an estimate. A long separation distance, a very-fast-front overvoltage or an unusual arrangement calls for a calculation of the voltages in the insulation coordination study.
3Protective margin
The protective margin expresses the same check as a ratio of the withstand to the protective level, taken at the arrester. Surge arresters, Protective margin introduces it and the practice of RUS Bulletin 1724E-300, the design guide of the ANSI / IEEE set. This section gives that practice in full and relates it to the safety factor. The IEC + CEA / CBIP set's levels take the safety factor and the ratio of Protective levels against the withstand voltages in its place.
RUS 1724E-300 §5.8.7.6 compares 3 pairs of values. The transformer's front-of-wave strength is compared with the arrester's front-of-wave value at 0.5 µs. The BIL is compared with the lightning protective level, and the basic switching impulse insulation level (BSL) with the switching surge protective level:
| protective ratio for the front of wave | ||
| protective ratio for the lightning impulse | ||
| protective ratio for the switching surge | ||
| front-of-wave withstand of the transformer | kVp | |
| front-of-wave protective level of the arrester | kVp | |
| lightning impulse protective level of the arrester | kVp | |
| switching impulse protective level of the arrester | kVp |
RUS 1724E-300 writes the ratios as F, L and S, without the letter R. The same section notes that a transformer's switching surge withstand is usually specified at 83 % of its BIL. A metal-oxide arrester has no sparkover, so its front-of-wave level takes the place of the sparkover voltage of a gapped arrester.
The ratio of 1.20 of the ANSI / IEEE set's practice and the safety factor of 1.15 apply at different points. The ratio compares the BIL with the voltage at the arrester. The safety factor applies to the voltage at the equipment's terminals, after the rise of The voltage at the protected equipment. With at the BIL divided by 1.20, the equipment is protected while the rise stays below the difference between the BIL divided by 1.15 and that level. A larger ratio, such as the 1.4 of Protective levels against the withstand voltages, leaves room for a longer distance.
4The voltage at the protected equipment
A lightning surge reaches the equipment as a travelling wave, and a transformer acts on its steep front as an open line end (Lightning, switching and temporary overvoltages, Lightning overvoltages). This section follows the wave between an arrester and a transformer to find the highest voltage at the transformer. The derivation follows the example of Hinrichsen (Metal-Oxide Surge Arresters pp. 11 to 13), drawn in Figure 2.
Assumptions. The arrester is ideal: it is an insulator below its protective level and holds its terminals at above it. The surge has a linear front of steepness and travels at the speed . The transformer, at the distance , reflects the wave in full. The amplitude of the surge does not enter, provided it exceeds .
Step 1: the wave reaches the transformer. The front passes the arrester at the time 0 and reaches the transformer after the travel time . Until then the voltage at the arrester rises at the rate . At the transformer the wave is reflected with the same sign, so from the voltage there rises at the rate .
Step 2: the reflection reaches the arrester. The reflected wave arrives back at the arrester at . From then the voltage at the arrester also rises at , until it reaches . The arrester then conducts, and sends a negative wave both ways that holds its voltage at .
Step 3: the arrester's wave reaches the transformer. The negative wave needs more to reach the transformer. In that time the transformer's voltage rises by a further above the value it had when the arrester began to conduct. That value equals , because from both voltages rise at the same rate and are equal. The highest voltage at the transformer is therefore
| front steepness of the incoming surge | kV/µs | |
| separation distance, along the conductor from the arrester's connection to the protected equipment | m | |
| propagation speed of the travelling wave | m/µs |
In Hinrichsen's example, a front of 1000 kV/µs, a distance of 60 m and an ideal arrester of 800 kVp give = 800 + 2 × 1000 × 60 / 300 = 1200 kVp. After the peak, the transformer's voltage oscillates with a period of , damped in practice by effects the simple model ignores. As the separation distance grows, the voltage at the transformer approaches twice the arrester's discharge voltage at most (RUS Bulletin 1724E-300 §5.8.8.2.2). Eq. (3) reaches that cap when equals , so it holds while . Beyond that distance, approaches and no longer grows with . Cahier Technique 151 (Appendix 2) reaches the same result from the superposition of the incident and reflected waves at an open point.
The inputs. The speed is the speed of light, 300 m/µs, on an overhead line, and 150 m/µs to 210 m/µs in a cable (Hinrichsen, Metal-Oxide Surge Arresters p. 133). For the steepness, Hinrichsen gives 1000 kV/µs as a typical value. RUS 1724E-300 §5.8.9 states that lightning fronts may approach 1000 kV/µs, that most do not exceed 500 kV/µs, and that 500 kV/µs is a basis for good practice. The lead length adds its inductive drop to in Eq. (3) (Surge arresters, Eq. (4)), and RUS 1724E-300 §5.8.8.2.3 states that the drop adds to the discharge voltage.
5The protective zone
The protective zone of an arrester is the largest separation distance at which the insulation coordination requirement is still met, for a given protective level and withstand. IEEE application guides express the zone as a maximum separation distance, while remains the actual distance of an arrangement (Hinrichsen, Metal-Oxide Surge Arresters pp. 132 to 133). This section turns Eq. (3) into the zone and states where the estimate holds.
Setting of Eq. (3) equal to the limit of Eq. (1) and solving for the distance gives Hinrichsen's estimate of the protective zone, for a transformer at the end of a single feeder:
| protective zone of the arrester, the largest separation distance that meets Eq. (1) | m |
For a 420 kV system with = 1425 kVp and = 790 kVp, at 1000 kV/µs and 300 m/µs, the zone is (1239 − 790) × 300 / 2000 = 67 m. For a 24 kV distribution system with = 125 kVp and = 80 kVp, it is (109 − 80) × 300 / 2000 = 4.3 m. Hinrichsen states the zone as a few metres in distribution systems and up to approximately 60 m in high-voltage systems (Metal-Oxide Surge Arresters p. 50). Cahier Technique 151 (Appendix 2) works a medium-voltage case without the safety factor: 125 kVp withstand, 75 kVp residual voltage and 300 kV/µs give a zone of 25 m.
Validity. Eq. (4) is a deterministic rule of thumb. Hinrichsen notes that IEC 60071-2 recommends the statistical method of Insulation coordination with arresters in its place. The zone shrinks with a steeper front, a slower wave and a higher protective level. In a cable the wave is slower, so the zone is shorter. RUS 1724E-300 §5.8.8.3.4 specifies arresters at the equipment end of a cable when twice the protective level of the arrester at the cable's junction exceeds 80 % of the substation's BIL.
Curves of the ANSI / IEEE set. RUS 1724E-300 §5.8.8.2.4 gives the maximum separation distances of high-side arresters as curves against the lead length, for nominal voltages of 23 kV to 345 kV. They are reproduced from IEEE C62.22-1991 and rest on AIEE Transactions Paper 63-229. IEEE C62.22 is the guide for the application of metal-oxide arresters in alternating-current systems, and IEC 60099-5 gives the selection and application recommendations of the IEC set.
Open points. An open breaker reflects a wave as a transformer does. A wave reaching it is reflected at nearly twice its rate of rise (RUS 1724E-300 §5.8.9). The arrester at the line entry keeps the open breaker within a short distance of its connection (Surge arresters, Placement and the separation distance).
6Arrester energy
The arrester must absorb the energy of the surges it limits and stay thermally stable afterwards (Surge arresters, The voltage-current characteristic). Its ratings for charge and energy are described in Surge arresters, Ratings and terms. This section explains which duties set the energy in a substation and how the energy is estimated.
Lightning. A station arrester takes only a part of the charge of a lightning stroke. A stroke to a line flashes over the line's insulators, and most of the charge flows to earth through the flashover. The surge that reaches the substation is limited to the insulators' flashover voltage (Hinrichsen, Metal-Oxide Surge Arresters p. 18). The largest lightning current to expect in the arrester follows from that limit:
| largest lightning current to expect in the arrester | kA | |
| flashover voltage of the line's insulators | kVp | |
| surge impedance of the line | Ω |
The factor 2 arises because the arrester acts almost as a short-circuited line end, so the current nearly doubles in it. For a 420 kV line with = 2700 kVp, = 790 kVp and = 350 Ω, Hinrichsen obtains 13.2 kA. The value guides the choice of the nominal discharge current.
Switching. The largest energy duty of a station arrester comes from switching. An open line charged to a switching overvoltage discharges into the arrester as a travelling wave (Hinrichsen, Metal-Oxide Surge Arresters p. 18). RUS 1724E-300 §5.8.7.4.2 states that switching surges are seldom a consideration below 345 kV. It estimates the arrester's current and energy as
| surge current in the arrester | kA | |
| surge voltage of the line | kVp | |
| discharge voltage of the arrester | kVp | |
| energy absorbed by the arrester | J | |
| length of the line | m |
RUS 1724E-300 writes for the line's length, for the speed of light, and for the energy, in kilojoules. With the units of the symbol table, the product of kilovolts, kiloamperes and microseconds is in joules. The current flows for , twice the travel time of the line. The bulletin compares the result with the maker's discharge capability, and an electromagnetic transient study gives the values more accurately.
Energy and protective level. A lower residual voltage gives a lower protective level, and the arrester then absorbs more energy from the same line discharge (Hinrichsen, Metal-Oxide Surge Arresters p. 48). Hinrichsen's example shows the charge and the energy ratings checked together. An arrester rated 336 kV, of class SM, transfers 2.0 C at a switching current of 1 kA, with a residual voltage of 650 kVp. The energy of that event is 2.0 C × 650 kV = 1.3 MJ. Its thermal energy rating of 7 kJ/kV gives 7 × 336 = 2.35 MJ, so it stays thermally stable after the event (Metal-Oxide Surge Arresters p. 49).
7In the design
The design takes the insulation levels and the arrester rating per voltage level from its level table (Insulation levels, the table), and places the arresters in the yard. It calculates no protective level, protective margin, separation distance, protective zone or arrester energy, and performs no insulation coordination study.
Ratings. At the default 220 kV high-voltage (HV) level the equipment is rated 1050 kVp, and the HV arresters 216 kV. At 400 kV and 765 kV the level table also carries a switching impulse withstand. Note 1 of the single-line diagram (SLD) states that the arrester rating follows the insulation coordination study. The checklist item "Arrester rated voltage against temporary overvoltage" reads Needs your review, and the neutral earthing study answers it (Earthing of the neutral, The HV system: solid earthing).
Placement. The yard places the line bay's arrester 4.0 m inside the line gantry, as the first device from the line. In a transformer bay it is the last device before the transformer, 9.0 m in plan from the face of the tank, and its conductor runs on to the HV bushings (Surge arresters, In the design).
Limits from the level table. the table applies the criteria of IEC 60071-2, as Hinrichsen and Cahier Technique 151 state them, to the BIL and the switching impulse withstand of the IEC + CEA / CBIP set's levels. The columns give the highest voltage at the terminals by Eq. (1), and the highest lightning impulse protective level for Hinrichsen's ratio of 1.4 (Protective levels against the withstand voltages). The next column gives the protective zone by Eq. (4) of an arrester at the ratio of 1.4, which takes 1000 kV/µs and 300 m/µs. The values follow from the sources' criteria and the design's insulation levels. They are not ratings of an arrester.
| Level | BIL | BIL / 1.15 | BIL / 1.4 | Protective zone at BIL / 1.4 | SIWL / 1.15 |
|---|---|---|---|---|---|
| 11 kV collector bus | 75 kVp | 65 kVp | 54 kVp | 1.7 m | |
| 33 kV collector bus | 170 kVp | 148 kVp | 121 kVp | 4.0 m | |
| 66 kV | 325 kVp | 283 kVp | 232 kVp | 7.6 m | |
| 132 kV | 650 kVp | 565 kVp | 464 kVp | 15.1 m | |
| 220 kV | 1050 kVp | 913 kVp | 750 kVp | 24.5 m | |
| 400 kV | 1425 kVp | 1239 kVp | 1018 kVp | 33.2 m | 913 kVp |
| 765 kV | 2100 kVp | 1826 kVp | 1500 kVp | 48.9 m | 1348 kVp |
The zone grows with the BIL, because a higher level leaves a larger difference between the ratios of 1.15 and 1.4. In the ANSI / IEEE set the BIL comes from IEEE C37.04-2018 Table 6 (Insulation levels, the table). At 230 kV the BIL of 900 kVp gives a lightning protective level of at most 750 kVp by the ratio of 1.20 of RUS 1724E-300 (Eq. (2)). At 345 kV the BSL of 825 kVp gives a switching protective level of at most 717 kVp by its ratio of 1.15.
Given: the default 220 kV project, and an arrester whose lightning impulse protective level is the BIL divided by 1.4, the ratio of Protective levels against the withstand voltages.
| Quantity | Value |
|---|---|
| BIL of the HV level | 1050 kVp |
| Safety factor | 1.15 |
| Lightning impulse protective level | 750 kVp |
| Front steepness | 1000 kV/µs |
| Propagation speed | 300 m/µs |
| Arrester to the face of the transformer tank, in plan | 9.0 m |
| Line arrester to the line bay's circuit breaker | 19.0 m |
Limit By Eq. (1) the voltage at the transformer's terminals may reach = 913 kVp. The arrester's protective margin is a ratio of 1.4 (a margin of 40 %).
Protective zone By Eq. (4), = 24.5 m.
Voltage at the transformer For a separation distance equal to the plan distance of 9.0 m, the travel time is 0.03 µs. By Eq. (3) the rise is 60 kVp, and = 810 kVp, below 913 kVp. The conductor also rises to the bushings on the tank's cover, so the separation distance measured along it is longer than the plan distance.
Line entry The line bay's circuit breaker stands 19.0 m from the line arrester along the bay, inside the protective zone of 24.5 m. An open breaker is an open point as the transformer is (The protective zone).
Result: an arrester at the ratio of 1.4 to the 1050 kVp BIL has a protective zone of 24.5 m, and the transformer bay's plan distance of 9.0 m is inside it. The insulation coordination study confirms the separation distance along the conductor with the arrester's own protective level.
- Name the steps of insulation coordination from the representative overvoltage to the standard withstand voltage.
Answer 1
The representative overvoltage gives the coordination withstand voltage through the coordination factor, the safety and atmospheric factors give the required withstand voltage, and the standard withstand voltage is chosen at or above it (Insulation coordination with arresters).
- State the criterion for the lightning overvoltage at a transformer protected by an arrester.
Answer 2
The highest overvoltage at its terminals stays below its BIL divided by the safety factor of 1.15 (Eq. (1)).
- Explain why the switching impulse check ignores the separation distance.
Answer 3
A switching surge rises slowly, so the travelling-wave rise and the lead drop are small, and the switching protective level is compared directly with the switching impulse withstand divided by 1.15 (Protective levels against the withstand voltages).
- Derive the voltage at a transformer at the distance S from an ideal arrester.
Answer 4
The transformer's voltage rises at twice the front steepness from the wave's arrival, and the arrester's reflection reaches it after the arrester conducts, so (The voltage at the protected equipment, Eq. (3)).
- Calculate the protective zone of the default HV transformer arrester at the ratio of 1.4.
- Explain why a lower protective level raises the energy an arrester absorbs from a line discharge.
Answer 6
The line discharges into the arrester more strongly when its residual voltage is lower, so the arrester converts more energy (Arrester energy).
[1]Hinrichsen, Metal-Oxide Surge Arresters, Metal-Oxide Surge Arresters: Fundamentals. p. 138; pp. 11 to 13; p. 133; p. 45.
[2]RUS Bulletin 1724E-300, Design Guide for Rural Substations. §5.8.7.6; §5.8.7.4.2, Eq. 5-8; §5.8.7.5, Eq. 5-9.
[3]Cahier Technique 151, Cahier Technique no. 151: Overvoltages and insulation coordination in MV and HV.
[4]IEC 60071-1:2019, Insulation co-ordination.
[5]IEC 60099-5:2018, Surge arresters, Part 5: Selection and application recommendations.
[6]IEEE C62.22-2009, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems.
[7]IEEE C37.04-2018, IEEE Standard for Ratings and Requirements for AC High-Voltage Circuit Breakers.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.