Transformer principles

A transformer changes an alternating voltage from one level to another through a magnetic core that links its windings. It is usually the largest and costliest item of a substation. This topic explains the principle and the ideal transformer, the losses, and the leakage reactance that sets the transformer's impedance and limits the fault current through it. It then explains the tap changer, the vector group that a three-phase transformer's connections give, and the autotransformer.

Before this topic: Voltage, current and impedance in AC circuits · Three-phase systems

1Magnetic coupling

A transformer has 2 or more windings on a common core of laminated steel (Figure 1). An alternating voltage applied to one winding, the primary, drives a small current that sets up an alternating magnetic flux in the core. That flux passes through the other winding, the secondary, and induces a voltage in it. The flux that links both windings is the mutual flux, and it carries the energy from one winding to the other.

With the secondary open, the primary draws only its exciting current. This current maintains the flux and supplies the core's losses. When a load is connected, the secondary current sets up a flux that opposes the mutual flux. The primary then draws more current from the source, and the mutual flux is restored.

Part of the flux of each winding does not link the other. This is the leakage flux. It induces no voltage in the other winding, and it acts as an inductance in series with the winding.

Figure 1.A two-winding transformer. The mutual flux in the core links the primary of turns and the secondary of turns, and the leakage flux links one winding only. The drawing is schematic and not to scale.

2The ideal transformer

An ideal transformer has no losses, no leakage flux and a core that needs no exciting current. The same flux links each turn of both windings, so each turn has the same voltage. Its voltages are in the ratio of the numbers of turns, and its ampere-turns balance:

(1)
MIT 6.061 Notes Ch. 3 §5, Eq. 33 and 34

The current ratio is the inverse of the voltage ratio. A step-down transformer lowers the voltage and raises the current in the same ratio. The power into the primary equals the power out of the secondary. An impedance connected to the secondary appears at the primary as .

The turns ratio is . In a three-phase transformer with both sides in star or both in delta, the ratio of the line voltages equals the turns ratio. With one side in star and the other in delta, it differs from the turns ratio by .

where
, voltages of the primary and the secondaryV
, currents of the primary and the secondaryA
, numbers of turns of the primary and the secondary

3Losses and efficiency

A real transformer loses part of the power it carries, as heat. The losses fall into 2 groups.

  • No-load loss, the loss in the core. Hysteresis loss is the energy spent to reverse the magnetisation of the steel twice in each cycle. Eddy-current loss is the heating by currents that the alternating flux induces in the steel. Thin laminations insulated from each other reduce the eddy currents. The no-load loss does not depend on the load, and it is present whenever the transformer is energised.
  • Load loss, the loss in the windings. The current heats the resistance of the windings, as . Leakage flux that reaches the tank and the structure adds eddy-current losses there, the stray losses. The load loss rises with the square of the current.

The efficiency is the output power over the input power, as a percentage. It rises with the size of the transformer. A small transformer in electrical equipment reaches 80 % to 90 %, and a large power transformer more than 98 %. The losses heat the transformer, and its cooling removes the heat.

4Leakage reactance and the short-circuit voltage

The leakage flux gives each winding a leakage reactance, and the winding conductors give it a resistance. Together they form the transformer's series impedance, between the source and the load. Its reactance is far larger than its resistance, so the impedance is almost a pure reactance (Voltage, current and impedance in AC circuits, Example 1).

The impedance is measured by the short-circuit test. One winding is short-circuited, and a reduced voltage is applied to the other until rated current flows. The rated short-circuit voltage is that voltage as a percentage of the rated voltage. It gives the impedance in ohms on the side of the rated voltage :

(2)
IEC 60909-0:2016 §6.3.1, Eq. 7

The impedance limits the current that a fault on one side draws through the transformer. Fed from a source of rated voltage with no impedance of its own, a fault on the other side draws times the rated current. The default interconnecting transformer (ICT) of 12.5 % passes at most 8 times its rated current from such a source. A real grid adds its own impedance, and the current is smaller.

A lower impedance gives a smaller voltage drop under load and a higher efficiency. It also gives higher fault currents, which the switchgear on the load side must be rated for (Per-unit quantities, The transformer gives the impedance per unit for the fault calculation). The impedance is therefore a compromise between voltage regulation and fault current.

where
rated short-circuit voltage%
impedance of the transformer, on the side of Ω
rated voltage of the transformer on the side consideredV
rated apparent power of the transformerVA

5Taps and the tap changer

A tap is a connection to a winding at a point other than its end. Selecting a tap changes the number of turns in use, and with it the turns ratio. Taps hold the secondary voltage near its rated value while the supply voltage or the load changes.

A no-load tap changer can only be moved with the transformer de-energised, since it cannot interrupt current. Its range is typically 10 %, from 5 % below to 5 % above the rated voltage, in steps of 2.5 %, as the substation design guide of the Rural Utilities Service (RUS) gives it. An on-load tap changer (OLTC) changes the tap while the transformer carries load. The ANSI / IEEE set calls it a load tap changer (LTC).

6Vector groups

A three-phase transformer has one set of windings per phase. It is built as one unit, with the 3 phases on a common core, or as a bank of 3 single-phase units. Each side's windings connect in star or in delta. The vector group names the connections and the phase displacement between the 2 sides.

  • Letters: Y for a star, D for a delta and Z for a zigzag. A capital letter is the high-voltage side, a small letter the low-voltage side. N or n marks a neutral brought out to a terminal.
  • Number: the clock number. Each hour of the clock is 30°. With the high-voltage phasor at 12 o'clock, the number is the hour at which the low-voltage phasor stands (Figure 2).

A star-star or delta-delta transformer has the 2 sides in phase, clock number 0. A star-delta or delta-star transformer shifts the voltages, by 30° in the common connections, clock number 1 or 11. Other connections give other numbers, such as Dyn5. The phasors turn counterclockwise, so a low-voltage phasor at 11 o'clock leads the high-voltage phasor by 30°, and one at 1 o'clock lags it by 30°. Dyn11 is a delta high-voltage winding and a star low-voltage winding with its neutral brought out, the low-voltage side leading by 30°.

The ANSI / IEEE set connects a standard delta-wye step-down transformer with the high side leading the low side by 30° (RUS Bulletin 1724E-300 §5.2.6). In the clock notation that is Dyn1. Transformers run in parallel only with the same phase displacement, the same voltage ratio and similar impedances.

Figure 2.The clock notation. The high-voltage phasor stands at 12 o'clock, and the low-voltage phasor at the hour of the clock number: 12 o'clock for 0, 11 o'clock for 11, 30° ahead. The drawing is schematic and not to scale.

7Autotransformers

An autotransformer has one winding per phase, part of which is common to the 2 sides. The low-voltage side is taken from a tap of the high-voltage winding. An autotransformer is smaller and lighter than a two-winding transformer of the same rating, with lower losses and a smaller exciting current. RUS Bulletin 1724E-300 gives it a cost advantage at voltage ratios up to 3 to 1, which diminishes beyond.

The 2 sides of an autotransformer share the common winding, so the voltages of its 2 sides are in phase. Its windings are usually connected in star. Its impedance is lower than that of a two-winding transformer, and the fault currents through it are higher. The bulletin also names its effect on earth-fault relaying as a drawback.

8In the design

The design's ICTs at the default 220 kV pooling substation connect its high-voltage (HV) bus to its medium-voltage (MV) bus. They are 2 two-winding units of 160 MVA, 220/33 kV, vector group YNyn0. Each has an OLTC of ±10 % in steps of 1.25 %, which gives 17 positions and 2.75 kV per step at 220 kV.

The vector groups of the design's transformers are these:

TransformerVector group
ICT, default 220/33 kVYNyn0
ICT, 400/33/33 kV, 2 MV windingsYNyn0yn0 + d
ICT, 33/11 kVDyn11
Autotransformer of a switching substation, 400/220/33 kVYNa0d11
Auxiliary transformerDyn11
Auxiliary transformer, ANSI / IEEE setDyn1

The ANSI / IEEE set prints the delta-star groups with the clock number 1, as RUS Bulletin 1724E-300 §5.2.6 connects them. The short-circuit study models an ICT by Eq. (2) at the user's X/R ratio (Short-circuit currents by IEC 60909-0, The impedances of the network).

Example 1Ratio, currents and through-fault current of the default ICT

Given: one ICT of 160 MVA, 220/33 kV, YNyn0, rated short-circuit voltage 12.5 %, X/R ratio 40.

Voltage ratio, equal to the turns ratio for a star-star transformer: = 6.667.

Rated currents by Active, reactive and apparent power, Eq. (5): 419.9 A on the HV side and 2799 A on the MV side. Their ratio is the voltage ratio inverted, as Eq. (1) states.

Impedance on the HV side by Eq. (2): = 37.81 Ω, with = 37.80 Ω and = 0.945 Ω.

Short-circuit voltage in volts: of the phase voltage of 127.0 kV is 15.88 kV, the voltage that drives the rated current through .

Through-fault current from a source of rated voltage with no impedance, for a fault at the MV terminals:

Result: the ICT limits a fault at its MV terminals to 22.39 kA from an ideal source. The design's short-circuit study, with the grid's impedance and the factors of IEC 60909-0:2016, finds 21.63 kA at the MV bus without the plant's infeed, below that value (Short-circuit currents by IEC 60909-0, The initial symmetrical currents).

Review questions
  1. Explain how a voltage is induced in the secondary of a transformer.
    Answer 1

    The primary current sets up an alternating flux in the core, and the mutual flux that passes through the secondary induces a voltage in it (Magnetic coupling).

  2. Calculate the secondary current of an ideal transformer of turns ratio 10 whose primary carries 50 A.
    Answer 2

    The ampere-turns balance, so the secondary current is 10 × 50 A = 500 A (Eq. (1)).

  3. Distinguish the no-load loss from the load loss.
    Answer 3

    The no-load loss is the hysteresis and eddy-current loss of the core and does not depend on the load; the load loss is the loss in the windings and rises with the square of the current (Losses and efficiency).

  4. Calculate the most current the default ICT of 12.5 % can pass to a fault at its MV terminals from an ideal source.
    Answer 4

    It passes = 8 times its rated current, 22.39 kA (Leakage reactance and the short-circuit voltage, Example 1).

  5. State the phase displacement of a Dyn11 transformer.
    Answer 5

    The low-voltage phasor stands at 11 o'clock, so the low-voltage side leads the high-voltage side by 30° (Vector groups).

  6. Give the reason why an autotransformer keeps its 2 sides in phase.
    Answer 6

    Its 2 sides share the common winding, so their voltages are in phase (Autotransformers).

Sources

[1]MIT 6.061 Notes Ch. 3, 6.061 Introduction to Power Systems, Class Notes Chapter 3: Polyphase Networks. §5, Eq. 33 and 34.

[2]NEETS Module 2, Navy Electricity and Electronics Training Series, Module 2: Introduction to Alternating Current and Transformers.

[3]Virginia Tech ECE 3354, Transformer Model: Transformer Equivalent Circuit, Steady-State Testing and Performance of Single-Phase Transformers.

[4]Noratel, Technical information: The three-phase transformer.

[5]RUS Bulletin 1724E-300, Design Guide for Rural Substations.

[6]IEC 60909-0:2016, Short-circuit currents in three-phase AC systems, Part 0: Calculation of currents. §6.3.1, Eq. 7.

Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.

CitationSubstationLayout Reference, Transformer principles, revision 3, 9 Nov 2026, https://substation.solarlayout.app/library/reference/transformer-principles