Faults and fault current
A power network carries its load current through insulation that keeps the conductors apart and away from earth. When that insulation fails, current flows through the failure instead of through the load. This topic explains what a fault is, why it happens, and the shape of the current it draws. It then explains why the size of that current sets the ratings of the substation's equipment.
Before this topic: Voltage, current and impedance in AC circuits · Three-phase systems
1What a fault is
A short circuit is an accidental connection of low impedance between 2 conductors at different voltages. The connection may be between phases or between a phase and earth. Its impedance is small compared with the load's, so the current is limited mainly by the impedance of the network up to the fault. The result is a current many times the load current, called the fault current or short-circuit current.
A fault may be transient or permanent. A bird or a branch may bridge 2 conductors for a moment, and the arc clears when the circuit is opened. A line is therefore often reclosed automatically after a short dead time. A fault that is still present at reclosure is permanent, and the circuit stays open until it is repaired.
The consequences depend on the fault's current, its duration and its location. At the fault, the arc damages insulation and can weld conductors. Along the faulted circuit, the current heats the conductors and drives electrodynamic forces between them. Elsewhere in the network, the voltage dips until the fault is cleared.
2Causes of faults
Faults have mechanical, electrical and environmental causes. A foreign conducting body, such as a tool or an animal, can bridge 2 conductors. A branch or a bird can do the same on an overhead line. A conductor can break and fall.
Overvoltages cause faults when they exceed the insulation's withstand. A lightning stroke on or near a line raises its voltage until an insulator flashes over (Lightning, switching and temporary overvoltages). Switching operations inside the network cause overvoltages of their own.
Insulation also breaks down under heat, humidity or a corrosive atmosphere. Such a breakdown can occur inside equipment, such as a machine or a switchboard, or outside it.
3Fault types
A fault is named by the conductors it connects. Figure 1 shows the fault types on the 3 phases a, b and c:
- a three-phase fault connects the 3 phases, with or without earth
- a line-to-line fault connects 2 phases, clear of earth
- a line-to-line-to-earth fault, also called double line-to-earth, connects 2 phases and earth
- a line-to-earth fault, also called single line-to-earth, connects one phase to earth
The line-to-earth fault is the most frequent, at 70 % to 80 % of faults. The three-phase fault is the least frequent, at a few percent of faults, and a line-to-line fault often develops into one. The three-phase fault loads the phases equally and is the one a balanced calculation describes. The other types are unbalanced, and their currents are calculated by the method of symmetrical components (Symmetrical components).
4The fault current and its components
The network up to the fault behaves, for this purpose, as a voltage source behind a resistance and an inductance . The current through an inductance cannot change suddenly. With the load current taken as negligible, the fault current therefore starts from zero, and it is the sum of 2 components:
The first term is the AC component, a sine wave at the network frequency whose root-mean-square value (RMS) is . The second term is the DC component. It starts at the value that makes the total current zero at , and decays with the time constant .
| instantaneous fault current | A | |
| RMS phase voltage of the source | V | |
| magnitude of the impedance up to the fault, | Ω | |
| angular frequency, | rad/s | |
| angle on the voltage wave at which the fault starts | ° | |
| angle of the impedance, | ° | |
| time constant of the DC component, | s |
The size of the DC component depends on when the fault starts. It is zero when , and the current is symmetrical from the start. It is largest when , and the current is then fully offset. The ratio of reactance to resistance, the X/R ratio, sets how long the offset lasts. A network with a high X/R ratio has a long time constant, and its DC component decays slowly.
Figure 2 shows the fully offset current at the high-voltage (HV) bus of the default project, where the X/R ratio is 14.3 and the time constant 45.5 ms. After one period of 20 ms, the DC component is still 64 % of its initial value. The first peak reaches 1.80 times the peak of the AC component, at 9.8 ms.
This first peak is what the peak factor of IEC 60909-0:2016 describes. For the bus's R/X ratio of 0.0699, its formula gives 1.81 (Peak current and thermal equivalent current, Eq. (2)). A circuit breaker must close onto this peak current, and the busbars must withstand its forces. The design takes the peak factor by method B of IEC 60909-0: 1.15 times the factor of the formula, limited to 2.0, which gives 2.000 at the HV bus (Peak current and thermal equivalent current, The switchgear rating checks).
5Why the fault level matters
The fault level at a bus is the largest symmetrical fault current that can flow there, stated here as a current in kA. It is set by the grid's strength, the transformers and lines up to the bus, and the generators and converters that feed the fault. It is the basis of the following parts of the substation design.
Switchgear ratings. A circuit breaker must interrupt the fault current and close onto its peak. The busbars, isolators (disconnectors, IEC 60050) and current transformers must carry it for the fault's duration without damage. The equipment is therefore rated at a short-time current at or above the calculated fault level (Short-circuit currents by IEC 60909-0, Peak current and thermal equivalent current, The switchgear rating checks).
The earth mat. An earth fault drives current into the earth mat. That current raises the mat's potential and sets the touch and step voltages a person can meet (Grid current). The fault level therefore sets the earth-fault current for which the mat is designed. The design takes the HV design fault level, 50 kA at the default project, as that current.
Protection. Relays detect a fault by its current and trip the breakers that isolate it. The largest fault current sets the duty of the breakers. The smallest, at the far end of a circuit, must still be large enough to be detected.
6In the design
The design calculates the fault currents of a project by IEC 60909-0:2016, or by IEEE C37.010-2016 in the ANSI / IEEE set (Short-circuit currents by IEC 60909-0, Short-circuit duty by IEEE C37.010). The grid enters as its three-phase and single-phase fault levels with an X/R ratio. These are inputs on the Define page, and their defaults for the default project are 40 kA, 40 kA and X/R 15.
At the default 220 kV HV bus, the study gives these currents:
| Fault type | Current at the HV bus |
|---|---|
| Three-phase | 22.95 kA |
| Line-to-line | 19.15 kA |
| Line-to-line-to-earth | 21.46 kA |
| Line-to-earth | 20.34 kA |
The largest is the three-phase current, and the switchgear is rated at the design fault level of the 220 kV voltage level, 50 kA. The peak current the design checks against the breaker's making current is 64.90 kA, with the peak factor of 2.000 (Peak current and thermal equivalent current, The switchgear rating checks). SubstationLayout sets no protection relays.
- Define a short circuit, and state what limits its current.
Answer 1
A short circuit is an accidental connection of low impedance between conductors at different voltages, and its current is limited mainly by the impedance of the network up to the fault (What a fault is).
- Name the fault types, and state which is the most frequent.
Answer 2
The types are the three-phase, line-to-line, line-to-line-to-earth and line-to-earth faults, and the line-to-earth fault is the most frequent, at 70 % to 80 % of faults (Fault types).
- Explain why a fault current has a DC component.
Answer 3
The inductance of the network resists a sudden change of current, so the current starts from zero, and a DC component that decays with the time constant makes up the difference (The fault current and its components).
- Explain how the X/R ratio affects the fault current.
Answer 4
A higher X/R ratio gives a longer time constant, so the DC component decays more slowly and the first peak is higher (The fault current and its components, Eq. (1)).
- Give the reasons the fault level sets the ratings of the switchgear.
Answer 5
A breaker must interrupt the fault current and close onto its peak, and the busbars, isolators and current transformers must carry it for its duration (Why the fault level matters).
- Find the largest fault current at the default project's HV bus.
Answer 6
The three-phase current of 22.95 kA is the largest, within the design fault level of 50 kA (In the design).
[1]Cahier Technique 158, Cahier Technique no. 158: Calculation of short-circuit currents. §1.2.
[2]ECE 3600 Transmission Line Faults, ECE 3600 Transmission Line Faults.
[3]IEC 60909-0:2016, Short-circuit currents in three-phase AC systems, Part 0: Calculation of currents.
[4]IEEE C37.010-2016, IEEE Application Guide for AC High-Voltage Circuit Breakers.
[5]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.