Isolators and earth switches
A circuit breaker interrupts the current of its circuit. An isolator (disconnector, IEC 60050) then isolates the circuit with a gap in air that can be seen. An earth switch (earthing switch, IEC 60050) connects the isolated part to the earth mat, so that people can work on it. This topic explains these devices, their types and ratings, and the order in which they operate with the breaker. It closes with the isolators and earth switches the design specifies.
Before this topic: Circuit breakers · Bays and their equipment
1The duty of an isolator
An isolator is a mechanical switching device that changes the connections of a circuit, or isolates a circuit or equipment from its source (RUS Bulletin 1724E-300 §5.7.2.1). It carries the load current continuously, and the short-circuit current for a short time. It opens or closes only when a negligible current is broken or made, or when the voltage across its poles does not change significantly.
The isolator therefore does not interrupt load or fault current. The breaker of the bay interrupts the current first, and the isolator then opens with no current through it. Small currents, such as a transformer's exciting current or a short line's charging current, are broken by a horn-gap switch with arcing horns, or by an interrupter switch (RUS 1724E-300 §5.7.2.3, §5.7.2.4).
In its open position, an isolator provides an isolating distance in air that can be seen (Siemens High-Voltage Products, Disconnectors). The open gap is the safety boundary for work on the isolated part, so it is made stronger than the insulation to earth. The open gap of an outdoor air switch withstands a test voltage 10 % above the switch's rated withstand voltages (RUS 1724E-300 §5.7.6.3). Where it can be arranged, the switch is mounted so that its blade is dead when the switch is open (RUS 1724E-300 §5.7.7.2).
A substation uses isolators to isolate a circuit breaker, a power transformer or a voltage transformer, to bypass equipment and to sectionalise a bus (RUS 1724E-300 §5.7.2.1).
2Types of outdoor isolator
An outdoor isolator is named by the way its blade moves. Figure 1 shows 4 common types in the closed position, with the motion that opens them:
- Centre-break. The 2 insulators of a centre-break isolator rotate, and the arms they carry part at the centre in a horizontal plane (RUS 1724E-300 §5.7.3.5). One manufacturer names it the most frequently used type (Siemens High-Voltage Products, Disconnectors).
- Double-break. The centre one of its 3 insulators rotates, and its blade opens the circuit at 2 points (RUS 1724E-300 §5.7.3.2). It suits limited phase spacings where the blade cannot open vertically.
- Vertical-break. The blade swings up in a plane perpendicular to the base, driven by a rotating insulator at the hinge end (RUS 1724E-300 §5.7.3.1). It suits small phase spacings.
- Pantograph. A pantograph isolator has scissor arms on a single insulator that reach up and close onto a conductor above them, giving a vertical isolating distance. It connects 2 busbars, a busbar and a line, or a busbar and a transformer (Siemens High-Voltage Products, Disconnectors).
Other types include the side-break, the tilting-insulator and the vertical-reach switch (RUS 1724E-300 §5.7.3). A knee-type isolator folds its arm and needs the least space (Siemens High-Voltage Products, Disconnectors).
An isolator is operated by a motor mechanism or by hand. A motor mechanism can also be worked by a hand crank, and inserting the crank isolates the motor circuit. Its auxiliary switch signals the closed position only after the contacts are locked, and the open position only after the gap has its full dielectric strength (Siemens High-Voltage Products, Disconnectors). Its 3 poles are either ganged to one mechanism, which is group operation, or have one mechanism each.
3Earth switches
An earth switch, called a grounding switch in ANSI / IEEE terms, connects a circuit or a piece of equipment to earth (RUS 1724E-300 §5.7.2.2). Its main duty is to earth a bus or a circuit for safe maintenance after it has been isolated. It connects the de-energised conductors to earth for safety during work on the circuit (Cahier Technique 193 §1).
Earth switches are often mounted on the jaw or hinge end of an isolator, as built-on earth switches. They can also stand free on their own base (Siemens High-Voltage Products, Disconnectors). An earth switch can also be designed to switch induced inductive and capacitive currents, in class A or class B of IEC 62271-102 (Siemens High-Voltage Products, Disconnectors).
An earth switch has rated short-time and peak withstand currents, as its isolator has. A rated fault-making current is optional, for a switch that must be able to close onto a live circuit (RUS 1724E-300 §5.7.5.1). A high-speed earth switch on one phase is sometimes used to trip remote breakers during a transformer fault. RUS 1724E-300 §4.4.7 states that this practice is generally not preferred, because it subjects the network to a greater shock.
4Interlocking with the breaker
Interlocks hold a bay's devices to a fixed order: the breaker opens first, then the isolators open and the earth switch closes, and the reverse order returns the circuit to service (Interlocking between the devices of a bay, The operating sequence of a bay, Interlocking between the devices of a bay, Electrical, mechanical and key interlocks).
A disconnecting circuit breaker combines both functions in one sulphur hexafluoride (SF6) device. Its isolating gap is inside the gas enclosure and is not visible. A mechanical interlock holds the breaker open while it serves as an isolator (Siemens High-Voltage Products, Circuit-Breakers).
5Ratings
An isolator is specified by the voltage it withstands, the current it carries and the fault current it withstands. RUS 1724E-300 §5.7.5 lists these ratings of a disconnecting switch:
- Rated maximum voltage, the highest root-mean-square value (RMS) of the voltage the switch is designed to operate at (RUS 1724E-300 §5.7.5.2.2).
- Rated withstand voltages, the lightning impulse withstand and the power-frequency withstand, to earth and across the open gap, with a switching impulse withstand from 362 kV.
- Rated continuous current, the current the switch carries continuously within its limit of temperature rise (RUS 1724E-300 §5.7.5.2.3).
- Rated short-time withstand current and its duration, and the rated peak withstand current. In the preferred ratings of ANSI C37.32, the duration is 3 s and the peak is 2.6 times the short-time current (RUS 1724E-300 §5.7.3).
- Mechanical ratings: the number of operations, the load on the terminals, and the ice the switch breaks when it operates.
A manufacturer's rating table for isolators to the IEC standards covers the same quantities. It gives the rated voltage and the power-frequency and lightning impulse withstand voltages, to earth and across the isolating distance. It then gives the rated normal current, the peak and short-time withstand currents with a duration of 1 s or 3 s, and an icing class (Siemens High-Voltage Products, Disconnectors). The withstand across the isolating distance is the higher value. An earth switch has the withstand voltage and withstand current ratings, and no rated continuous current (RUS 1724E-300 §5.7.5.1).
IEC 62271-102 covers alternating current (AC) isolators and earth switches, which it calls disconnectors and earthing switches, for indoor and outdoor installations above 1000 V, with their operating devices. ANSI C37.32 gives the preferred ratings of outdoor air switches in the ANSI / IEEE practice (RUS 1724E-300 §5.7.1).
6In the design
The design's high-voltage (HV) isolator is a three-phase, motor-operated, horizontal centre-break (HCB) isolator. It carries the bay's rated current and the level's ratings. The bill of materials (BOM) lists the isolators in 2 lines: the isolators without an earth switch, and the isolators with one earth switch.
The bus isolators connect a bay to each bus, and they have no earth switch. The line isolator and the transformer isolator carry one earth switch each (Bays and their equipment, Line bay). A bus voltage transformer bay has 1 isolator. The design sets no interlocking scheme between the isolators, the earth switches and the breaker.
The IEC + CEA / CBIP set designates the bus isolators −Q1 and −Q2, the line or transformer isolator −Q9 and its earth switch −Q8. The ANSI / IEEE set calls the isolator a disconnect switch and the earth switch a grounding switch. Its single-line diagram (SLD) prints 89 for the disconnect switches, after IEEE C37.2-1996, and draws the grounding switch with its 89. The key diagram prints the grounding switch as device 57 of IEEE C37.2-1996, the short-circuiting or grounding device, beside its 89. A ring bus has no main buses, so its disconnect switches stand on both sides of the breakers. In a full diameter of a one-and-a-half breaker scheme, the design places 6 disconnect switches, one on each side of the 3 breakers.
In a gas-insulated switchgear (GIS) yard, a three-position isolator and earth switch and a fast-acting earth switch are part of each bay module (Gas-insulated switchgear (GIS), Bay modules). An outdoor medium-voltage (MV) bay carries 2 isolators with its vacuum breaker, and an indoor MV panel carries a withdrawable breaker (Circuit breakers, Metal-clad switchgear with withdrawable breakers).
Given: the default project, a 220 kV double main bus with 1 line bay, 2 transformer bays, a bus coupler and 2 bus voltage transformer bays.
Per bay, from the yard layout:
| Bay | Bus isolators | Isolator with earth switch | Breakers |
|---|---|---|---|
| Line | 2 | 1 | 1 |
| Transformer | 2 | 1 | 1 |
| Bus coupler | 2 | 0 | 1 |
| Bus voltage transformer | 1 | 0 | 0 |
BOM lines: 10 × Isolator, HCB, 3-phase, motor operated, 245 kV, BIL 1050 kVp, 50 kA 1 s, 1600 A, without earth switch. 3 × Isolator, HCB, 3-phase, with 1 earth switch.
Structures: the 13 isolators stand on 39 isolator support structures, one per pole.
Result: the 220 kV yard has 10 bus isolators without an earth switch and 3 line and transformer isolators with one earth switch each.
- Explain why an isolator is opened only after the breaker of its bay.
Answer 1
An isolator opens or closes only at a negligible current, so the breaker interrupts the current first and the isolator then opens with no current through it (The duty of an isolator).
- Explain why the open gap of an isolator is made stronger than its insulation to earth.
Answer 2
The open gap is the safety boundary for work on the isolated part, so the open gap of an outdoor air switch withstands a test voltage 10 % above the switch's rated withstand voltages in RUS 1724E-300 §5.7.6.3 (The duty of an isolator).
- Distinguish a centre-break isolator from a pantograph isolator.
Answer 3
In a centre-break isolator, 2 insulators rotate and their arms part at the centre, and in a pantograph isolator, scissor arms on one insulator close onto a conductor above, giving a vertical isolating distance (Types of outdoor isolator).
- State the order of operations that isolates and earths a circuit.
Answer 4
The breaker opens first, then the isolators open, and then the earth switch closes (Interlocking with the breaker).
- Name the isolators of the default project's line bay with their designations.
Answer 5
The bus isolators −Q1 and −Q2 without an earth switch, and the line isolator −Q9 with its earth switch −Q8 (In the design, Example 1).
[1]RUS Bulletin 1724E-300, Design Guide for Rural Substations.
[2]Siemens High-Voltage Products, High-Voltage Products.
[3]Cahier Technique 193, Cahier Technique no. 193: MV breaking techniques.
[4]IEC 62271-102:2018, High-voltage switchgear and controlgear, Part 102: Alternating current disconnectors and earthing switches.
[5]IEEE C37.2-1996, Standard Electrical Power System Device Function Numbers.
[6]IEC 60050-441, International Electrotechnical Vocabulary, Part 441: Switchgear, controlgear and fuses.
Reference topics explain the methods of the standards for study. For a design, apply the standards and regulations in force.